Intewa AQUALOOP AL-PD78 Assembly And Operating Instructions Manual

Pipe diffusor

Advertisement

Quick Links

  
 
 
 
 
 
 
 
 
 
  
 
AQUALOOP pipe diffusor 
 
 AL‐PD78 
 AL‐PD142 
 
Assembly and Operating Instructions
 
WATER, WE'RE IN OUR ELEMENT 
Water we're in our Element 
 
 
 
 
 
 
www.intewa.com 
 
 
 
 
www.intewa.de 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AQUALOOP AL-PD78 and is the answer not in the manual?

Questions and answers

Summary of Contents for Intewa AQUALOOP AL-PD78

  • Page 1                                   AQUALOOP pipe diffusor     AL‐PD78   AL‐PD142      Assembly and Operating Instructions   WATER, WE’RE IN OUR ELEMENT  Water we’re in our Element            www.intewa.com  www.intewa.de ...
  • Page 2     Table of Contents        General Information  .........................  2     Safety Precautions  ...........................  2     Scope of delivery ..........................  2     Description  ............................  3     Technical Data  .......................... 4     Installation Instructions  ........................  5     Maintenance and spare parts replacement .................. 6  ...
  • Page 3       1.  General Information    Thank  you  for  choosing  an  INTEWA  pipe  diffusor  unit.  Please  read  the  operating  instructions  carefully  before commissioning to ensure safe and correct system startup.    The pipe diffusor system is intended for aerating of bioreactor tanks of greywater plants. The system can  be used in places where aeration, saturation by air or liquid mixing is required.  AL‐PD pipe diffusors are noted for their high efficiency of air transfer into water, high clogging resistance  and low‐pressure loss. They provide the user with low operating cost and trouble‐free performance.          2.  Safety Precautions      Before installing the product, these installation and operating instructions must be  read  carefully.  The  indicated  instructions  herein  must  be  strictly  observed. ...
  • Page 4     4.  Description    The  AQUALOOP  pipe  diffusor  (AL‐PD)  is  designed  especially  for  water  treatment  plants.  The  special  construction enables easy installation in various types of tanks without the need to fix the diffusors to the  bottom.   The  diffusor  is  equipped  with  internal  weight  to  operate  against  buoyancy  force.  The  diffusor  contains,  depending on its size (AL‐PD78 and AL‐PD142), of one or two equally air‐supplied nonelastic pipes, coated  by EPDM membranes and based on two arched pillars. The pillars are coated with anti‐slip rubber parts at  the bottom to inhibit shifting of the diffusor. At the tail end of the pipe diffusor a lifting rope is installed.    Air enters the nonelastic pipe through a ball valve, shut‐off fitting, connecting air hose and hose connector ...
  • Page 5       5.  Technical Data      AL‐PD78  AL‐PD142  Air flow (Qvz,e)  1.5 – 10.0 m³/h  3.0 – 20.0 m³/h  Recommended air flow per diffusor (Qvz,e)  3.5 – 6.5 m³/h  7.0 – 13.0 m³/h  Loss of pressure depending on the air flow (Δp)  3 ‐ 7 kPa  3 ‐ 7 kPa  Maximal surface density of diffusor (Ds)  6 ks/m²  12 ks/m²  Oxygen use efficiency under standard conditions (Ea)  5 – 7 %/m  5 – 7 %/m  Standard oxygenation efficiency (E*)  3 – 5 kg O /kWh  6 ‐ 10 kg O /kWh  Length   780 mm  1420 mm  Width  140 mm  140mm  Length air hose  2 m  3 m  Amount of aerator membrane  1  2 ...
  • Page 6       Note: In the grey water application AL‐GW XXX a minimum water level of 700 mm is required before  starting the tube diffuser. Other application has to be calculated  to guarantee, that the air load  not  exceed the required operation condition.          6.  Installation Instructions    The installation in the tank, as well as the removal and re‐positioning is carried out with the help of the air  hose and lifting rope. This allows easy  installation and repair of the diffusor system, without the need to  empty the tanks. Installation, removal and re‐placement are performed manually and require one person  only.      The  special  design  of  the  pipe  diffusor  allows  easy  installation in various types of tanks without the need to fix  the diffusor to the floor.        The diffusor elements are equipped with internal weight to  compensate against the buoyancy force.      The  air  is  supplied  to  each  diffusor  through  a  ball  valve,  shut‐off fitting and connecting pipe.  ...
  • Page 7       7.  Maintenance and spare parts replacement       Removing condensate      The  condensation  water  must  be  regularly  removed  from  the  system.  We  recommend  removing  the  condensate  within  a  6‐ month  interval.  Depending  on  the  surroundings  humidity,  the  maintenance interval can be extended.    Each  pipe  diffusor  is  equipped  with  a  mechanism  to  drain  condensed water. A small drainage hose from the bleed valve is ...
  • Page 8 Amount  AL‐PD78  AL‐PD142  Spare membrane for AQUALOOP pipe diffuser   AL‐PD‐MEM  230197  1  2            9.  Warranty / Contact    The warranty terms can be found in our sales conditions. See:    www.intewa.com      For customers in Germany:   For any queries, ordering of spare parts, as well as in case of service, kindly contact INTEWA GmbH directly,  quoting your product‘s model and identification numbers and the purchase invoice details, at:   INTEWA GmbH  Auf der Hüls 182  52068 Aachen    Tel.: 0049‐241‐96605‐0  Fax: 0049‐241‐96605‐10  Email: info@intewa.de   Internet: www.intewa.de      For customers in other countries:  For  any  queries,  ordering  of  spare  parts,  as  well  as  in  case  of  service,  kindly  contact  your  installer  or  the ...