5.4.1.8 Replacing an EEV
Prerequisites
●
●
Context
Tools: flat-head screwdriver, welding tool, refrigerant reclaiming device (required
based on local conditions), nitrogen injection and pressure preservation tool,
vacuumization tool, refrigerant charging tool
Procedure
Step 1 Hold down
screen displayed.
Step 2 Open the front door, and turn off the indoor unit power switch and the indoor
unit switch in the PDF.
Step 3 Remove the return air filter.
Step 4 Reclaim the refrigerant.
Step 5 Gently shake the EEV coil leftwards or rightwards and pull it upwards, as shown in
Figure
Step 6 Weld the two ends of the EEV using a welding torch, as shown in
Then, remove the EEV.
Figure 5-8 Removing the EEV
Step 7 Weld a new EEV, and install the coil for the EEV.
Issue 04 (2022-11-25)
An EEV or its coil needs to be replaced.
A spare EEV or a coil of the same model is available and functional.
on the home screen. Tap Yes on the shutdown confirmation
5-8.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Operation and Maintenance
Figure
5-8.