Busbar protection REB650
Version 1.1 ANSI
Table 53. IEC Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
td
(
)
ç
÷
P
-
è
ø
I
1
EQUATION1653 V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Table 54. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
td
0.236
-
0.339
I
EQUATION1656 V1 EN-US
I = I
/I
measured
set
RD type logarithmic inverse
characteristic
æ
ö
I
-
ç
×
÷
=
5.8
1.35
In
t
è
ø
td
EQUATION1657 V1 EN-US
I = I
/I
measured
set
40
Range or value
td = (0.05-999) in steps of 0.01
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
Range or value
td = (0.05-999) in steps of 0.01
td = (0.05-999) in steps of 0.01
© Copyright 2011 ABB Power Grids. All rights reserved
1MRK 505 265-BUS B
Accuracy
-
IEC 60255-151, class 5 +
40 ms
Accuracy
IEC 60255-151, class 5 +
40 ms
IEC 60255-151, class 5 +
40 ms