Busbar protection REB650
Version 1.1 ANSI
Table 37. Disturbance report DRPRDRE
Function
Current recording
Voltage recording
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the Trip Value recorder per recording
Maximum number of indications in a disturbance report
Maximum number of events in the Event recording per recording
Maximum number of events in the Sequence of events
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
Sampling rate
Recording bandwidth
Table 38. Event list DRPRDRE
Function
Buffer capacity
Resolution
Accuracy
Table 39. Indications DRPRDRE
Function
Buffer capacity
Maximum number of indications presented for single disturbance
Maximum number of recorded disturbances
36
Maximum number of events in the list
© Copyright 2011 ABB Power Grids. All rights reserved
M12760-1 v7
Range or value
-
-
(0.05–3.00) s
(0.1–10.0) s
(0.5–8.0) s
100, first in - first out
1 ms
30 + 10 (external + internally
derived)
96
30
96
150
1000, first in - first out
340 seconds (100 recordings)
at 50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
M12700-1 v4
Value
1000
1 ms
Depending on time synchronizing
M13765-1 v4
1MRK 505 265-BUS B
Accuracy
± 1,0% of I
at I ≤ I
r
r
± 1,0% of I at I > Ir
at V≤ V
± 1,0% of V
n
n
± 1,0% of Vat V> V
n
-
-
-
-
See time
synchronization
technical data
-
-
-
-
-
-
-
-
-
Value
96
100