Liquicap M FMI52 PFM
Endress+Hauser
4

Mounting

4.1

Quick installation guide

A probe installation
1. Screw the probe onto the proper place.
2. Fasten the probe with proper torque in accordance with the thread size.
Thread size and torque value
• G½: < 80 Nm (59.0 lbf ft)
• G¾: < 100 Nm (73.7 lbf ft)
• G1: < 180 Nm (132.8 lbf ft)
• G1½: < 500 Nm (368.7 lbf ft)
Aligning the housing
1 →
A0042107
Loosen the clamping screw.
4.2

Mounting requirements

4.2.1

Mounting the sensor

The Liquicap M FMI52 can be installed vertically from above.
Make sure that:
• the probe is not installed in the area of the filling curtain
• the probe is not in contact with the container wall
• the distance from the container floor is ≥10 mm (0.39 in)
• multiple probes are mounted next to each other at the minimum distance between
the probes of 500 mm (19.7 in)
2 →
...270°
A0042108
Align the housing into the
needed possition.
Mounting
A0041919
3
A0042109
Tighten the clamping screw
with torque
< 1 Nm (0.74 lbf ft)
11