ABB i-bus® KNX PARAMETERS
7.5.6
Enable group object "Frost alarm"
This parameter can be used to enable the group object Frost alarm . The group object applies to the en-
tire device, but each output can react differently to receipt of a frost alarm. The reaction of the respec-
tive output can be set in the Parameter window Safety/Weather.
Options
No
Yes
—
7.5.6.1
DEPENDENT PARAMETER
Cyclical monitoring interval (0 = cycl. monitoring deactivated)
This parameter can be used to define the monitoring cycle in the device.
The monitoring cycle in the device should be at least four times as large as the cyclic transmission time
of the sensor. As a result, the parameterized alarm reactions will not be triggered immediately if a signal
is missing (e.g. due to high bus load).
Options
00:00:00 ... 12:00:00 hh:mm:ss
Condition for visibility:
Parameter window Safety/Weather alarms \ Parameter Enable group object "Frost alarm" \ Option Yes
The group object is not enabled.
The group object is enabled.
•
Cyclical monitoring interval (0 = cycl. monitoring deactivated)
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 116