ABB i-bus® KNX PARAMETERS
7.4
Parameter window Manual operation
The following settings can be made in the Parameter window Manual operation:
• Enable operating state Manual operation
• Automatically reset the device to KNX operation
More information → Manual operation, Page 242.
Fig. 36: Parameter window Manual operation
Parameter
• Enable manual operation
• Automatically reset from manual operation to KNX operation
• State after end of manual operation
7.4.1
Enable manual operation
This parameter can be used to enable the operating state Manual operation .
Options
No
Yes
• Automatic reset after
The operating state Manual operation is disabled. The device cannot be operated using the mem-
brane keypad.
The device can be operated using the membrane keypad. The operating states Manual operation and
KNX operation can be switched via the Manual operation button or via the group object Enable/
disable manual operation .
The following group objects will be enabled:
•
Status Manual operation
•
Enable/disable manual operation
•
End manual operation
•
Automatically reset from manual operation to KNX operation
•
State after end of manual operation
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 111