System Layout

System Layout 3

Multiple (up to 16 boilers) Vitocrossal 200, CI2 with...
- 3 heating circuits with mixing valves
- low-loss header
- 3 zone circuits
- DHW
Legend
A
Vitocrossal 200, CI2 boiler
B
Low-loss header/common supply temperature
sensor TSI on lead boiler
Low-loss header
C
D
DHW storage tank
Zone circuit
E
Low temperature heating circuit
F
Connection to BMS (BACnet/MODbus)
G
Each boiler in a cascade system must be able to be
individually isolated from the heating system through the use
of boiler isolation valves.
42
When designing a multiple Vitocrossal 200, CI2 system
as shown above, please reference applicable multiple
Vitocrossal 200, CI2 technical documentation, and contact
your local Viessmann Sales Representative for further
assistance.
This installation example depicts a possible piping layout
for multiple Vitocrossal 200, CI2 boilers equipped with
Viessmann System Technology. Please note that this
example is based on a simplified conceptual drawing only!
Piping and necessary componentry must be field verified.
A low water cut-off (LWCO) must be installed where
required by local codes.
Proper installation and functionality in the field is the
responsibility of the heating contractor.
WARNING
If a DHW storage tank other than a Viessmann Vitocell
300 tank is used, the installer must verify proper
operation of the Viessmann DHW tank temperature
sensor with the original manufacturer of the tank.
Viessmann strongly recommends the installation of a
temperature tempering valve in the DHW supply line.