Vitocrossal 200 CI2 Installation

Connections on the Flue Gas Side

Connecting the neutralizing system (accessories)
The condensate trap is equipped with a float. If
Note:
there is no water in the condensate trap, the float
closes it.
The drain F must be lower than the condensate trap.
Ensure there is an air gap around the condensate hose
E at the drain F to allow the condensate to flow
freely.
Legend
A Vitocrossal 200 CI2, 399 to 1000
B Condensate trap
C Neutralizing system (accessories)
D Condensate trap hose (included with the boiler) to
neutralizing system
E Drain hose
F Drain (on-site)
Legend
A Vitocrossal 200 CI2, 1500 to 2000
B Condensate trap (included with the boiler)
C Neutralizing system (accessories)
D Condensate trap hose (included with the boiler) to
neutralizing system
E Drain hose
F Drain (on-site)
For the CI2 1500 and 2000 if the neutralization unit is
placed on the same level as the boiler:
The inlet and outlet of the neutralization unit must be less
than 6a in. (160 mm) from the base of the neutralization
system to the bottom of the inlet/outlet to ensure proper
condensate drainage (refer to dimension A). If this height
is exceeded a condensate pump will be required.
Installation
C
37