Transformer protection RET650 2.1 IEC
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
Table 13. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Min load voltage
Test voltage across open contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
Max operations with load
Max operations with no load
Making capacity at inductive load with L/R > 10 ms
0.2 s
1.0 s
Breaking capacity for AC, cos j > 0.4
Breaking capacity for DC with L/R < 40 ms
Operating time
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
Influencing factors
Table 14. Temperature and humidity influence
Parameter
Ambient temperature, operate
value
Relative humidity
Operative range
Storage temperature
32
M16705-1 v15
Reference value
+20°C
10-90%
0-95%
-
Nominal range
-25°C to +55°C
10-90%
-40°C to +70°C
1MRK 504 161-BEN C
Trip and Signal relays
24
250 V AC, DC
24VDC
1000 V rms
8 A
10 A
12 A
1000
10000
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
< 6 ms
Influence
0.02%/°C
-
-
M12441-1 v10
IP15846-1 v1