ABB RELION 650 Series Product Manual page 28

Transformer protection
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Transformer protection RET650 2.1 IEC
Maximum 176 binary input channels
may be activated simultaneously with
influencing factors within nominal
range.
Table 9. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
*Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
28
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
3 ms
1MRK 504 161-BEN C
M50609-2 v9
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
-
ABB

Advertisement

Table of Contents
loading

Table of Contents