Carrier 45 Series Installation, Start-Up And Service Instructions Manual page 32

Fan powered variable air volume terminals
Table of Contents

Advertisement

Table 29 — 45R Size 4 ECM Calibration
REMOTE 0-10VDC
VCU
DC SIGNAL
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
VDC
885
100
10.0
877
99
9.9
868
98
9.8
859
97
9.7
850
96
9.6
841
95
9.5
832
94
9.4
824
93
9.3
815
92
9.2
806
91
9.1
797
90
9.0
788
89
8.9
779
88
8.8
770
87
8.7
762
86
8.6
753
85
8.5
744
84
8.4
735
83
8.3
726
82
8.2
717
81
8.1
708
80
8.0
700
79
7.9
691
78
7.8
682
77
7.7
673
76
7.6
664
75
7.5
655
74
7.4
647
73
7.3
638
72
7.2
629
71
7.1
620
70
7.0
611
69
6.9
602
68
6.8
593
67
6.7
585
66
6.6
576
65
6.5
567
64
6.4
558
63
6.3
549
62
6.2
540
61
6.1
531
60
6.0
523
59
5.9
514
58
5.8
505
57
5.7
496
56
5.6
487
55
5.5
478
54
5.4
470
53
5.3
461
52
5.2
452
51
5.1
443
50
5.0
ACU-P
ACU-0
REMOTE
2-10VDC
(0-20mA)
(4-20mA)
DC SIGNAL
(OPTION 7)
(OPTION 8)
mA
VDC
(20.0)
10.0
(20.0)
(19.8)
9.9
(19.8)
(19.6)
9.8
(19.7)
(19.4)
9.8
(19.5)
(19.2)
9.7
(19.4)
(19.0)
9.6
(19.2)
(18.8)
9.5
(19.0)
(18.6)
9.4
(18.9)
(18.4)
9.4
(18.7)
(18.2)
9.3
(18.6)
(18.0)
9.2
(18.4)
(17.8)
9.1
(18.2)
(17.6)
9.0
(18.1)
(17.4)
9.0
(17.9)
(17.2)
8.9
(17.8)
(17.0)
8.8
(17.6)
(16.8)
8.7
(17.4)
(16.6)
8.6
(17.3)
(16.4)
8.6
(17.1)
(16.2)
8.5
(17.0)
(16.0)
8.4
(16.8)
(15.8)
8.3
(16.6)
(15.6)
8.2
(16.5)
(15.4)
8.2
(16.3)
(15.2)
8.1
(16.2)
(15.0)
8.0
(16.0)
(14.8)
7.9
(15.8)
(14.6)
7.8
(15.7)
(14.2)
7.8
(15.5)
(14.0)
7.7
(15.4)
(13.8)
7.6
(15.2)
(13.6)
7.5
(15.0)
(13.6)
7.4
(14.9)
(13.4)
7.4
(14.7)
(13.2)
7.3
(14.6)
(13.0)
7.2
(14.4)
(12.8)
7.1
(14.2)
(12.6)
7.0
(14.1)
(12.4)
7.0
(13.9)
(12.2)
6.9
(13.8)
(12.0)
6.8
(13.6)
(11.8)
6.7
(13.4)
(11.6)
6.6
(13.3)
(11.4)
6.6
(13.1)
(11.2)
6.5
(13.0)
(11.0)
6.4
(12.8)
(10.8)
6.3
(12.6)
(10.6)
6.2
(12.5)
(10.4)
6.2
(12.3)
(10.2)
6.1
(12.2)
(10.0)
6.0
(12.0)
Table 29 — 45R Size 4 ECM Calibration (cont)
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
mA
434
425
416
408
399
390
381
372
363
354
346
337
328
319
310
301
293
284
275
266
257
248
239
231
222
213
204
195
186
177
169
160
151
142
133
124
116
107
98
89
80
71
62
54
45
36
27
18
9
NOTE: CFM values below recommended minimum may affect life of
motor.
32
ACU-0
REMOTE 0-10VDC
(0-20mA)
VCU
DC SIGNAL
(OPTION 7)
VDC
mA
49
4.9
(9.8)
48
4.8
(9.6)
47
4.7
(9.4)
46
4.6
(9.2)
45
4.5
(9.0)
44
4.4
(8.8)
43
4.3
(8.6)
42
4.2
(8.4)
41
4.1
(8.2)
40
4.0
(8.0)
39
3.9
(7.8)
38
3.8
(7.6)
37
3.7
(7.4)
36
3.6
(7.2)
35
3.5
(7.0)
34
3.4
(6.8)
33
3.3
(6.6)
32
3.2
(6.4)
31
3.1
(6.2)
30
3.0
(6.0)
29
2.9
(5.8)
28
2.8
(5.6)
27
2.7
(5.4)
26
2.6
(5.2)
25
2.5
(5.0)
24
2.4
(4.8)
23
2.3
(4.6)
22
2.2
(4.4)
21
2.1
(4.2)
20
2.0
(4.0)
19
1.9
(3.8)
18
1.8
(3.6)
17
1.7
(3.4)
16
1.6
(3.2)
15
1.5
(3.0)
14
1.4
(2.8)
13
1.3
(2.6)
12
1.2
(2.4)
11
1.1
(2.2)
10
1.0
(2.0)
9
0.9
(1.8)
8
0.8
(1.6)
7
0.7
(1.4)
6
0.6
(1.2)
5
0.5
(1.0)
4
0.4
(0.8)
3
0.3
(0.6)
2
0.2
(0.4)
1
0.1
(0.2)
ACU-P
REMOTE
2-10VDC
(4-20mA)
DC SIGNAL
(OPTION 8)
VDC
mA
5.9
(11.8)
5.8
(11.7)
5.8
(11.5)
5.7
(11.4)
5.6
(11.2)
5.5
(11.0)
5.4
(10.9)
5.4
(10.7)
5.3
(10.6)
5.2
(10.4)
5.1
(10.2)
5.0
(10.1)
5.0
(9.9)
4.9
(9.8)
4.8
(9.6)
4.7
(9.4)
4.6
(9.3)
4.6
(9.1)
4.5
(9.0)
4.4
(8.8)
4.2
(8.6)
4.2
(8.5)
4.1
(8.3)
4.0
(8.2)
3.9
(8.0)
3.8
(7.8)
3.8
(7.7)
3.6
(7.5)
3.7
(7.4)
3.6
(7.2)
3.5
(7.0)
3.4
(6.9)
3.4
(6.7)
3.3
(6.6)
3.2
(6.4)
3.1
(6.2)
3.0
(6.1)
3.0
(5.9)
2.9
(5.8)
2.8
(5.6)
2.7
(5.4)
2.6
(5.3)
2.6
(5.1)
2.5
(5.0)
2.4
(4.8)
2.3
(4.6)
2.2
(4.5)
2.2
(4.3)
2.1
(4.2)

Advertisement

Table of Contents
loading

Table of Contents