Table 27 — 45Q DOAS Size 5 ECM Calibration
REMOTE 0-10VDC
VCU
DC SIGNAL
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
VDC
1625
100
10.0
1609
99
9.9
1593
98
9.8
1577
97
9.7
1560
96
9.6
1544
95
9.5
1528
94
9.4
1512
93
9.3
1495
92
9.2
1479
91
9.1
1463
90
9.0
1447
89
8.9
1430
88
8.8
1414
87
8.7
1398
86
8.6
1382
85
8.5
1365
84
8.4
1349
83
8.3
1333
82
8.2
1317
81
8.1
1300
80
8.0
1284
79
7.9
1268
78
7.8
1252
77
7.7
1235
76
7.6
1219
75
7.5
1203
74
7.4
1187
73
7.3
1170
72
7.2
1154
71
7.1
1138
70
7.0
1122
69
6.9
1105
68
6.8
1089
67
6.7
1073
66
6.6
1057
65
6.5
1040
64
6.4
1024
63
6.3
1008
62
6.2
992
61
6.1
975
60
6.0
959
59
5.9
943
58
5.8
927
57
5.7
910
56
5.6
894
55
5.5
878
54
5.4
862
53
5.3
845
52
5.2
829
51
5.1
813
50
5.0
797
49
4.9
ACU-P
ACU-0
REMOTE
2-10VDC
(0-20mA)
(4-20mA)
DC SIGNAL
(OPTION 7)
(OPTION 8)
mA
VDC
(20.0)
10.0
(20.0)
(19.8)
9.9
(19.8)
(19.6)
9.8
(19.7)
(19.4)
9.8
(19.5)
(19.2)
9.7
(19.4)
(19.0)
9.6
(19.2)
(18.8)
9.5
(19.0)
(18.6)
9.4
(18.9)
(18.4)
9.4
(18.7)
(18.2)
9.3
(18.6)
(18.0)
9.2
(18.4)
(17.8)
9.1
(18.2)
(17.6)
9.0
(18.1)
(17.4)
9.0
(17.9)
(17.2)
8.9
(17.8)
(17.0)
8.8
(17.6)
(16.8)
8.7
(17.4)
(16.6)
8.6
(17.3)
(16.4)
8.6
(17.1)
(16.2)
8.5
(17.0)
(16.0)
8.4
(16.8)
(15.8)
8.3
(16.6)
(15.6)
8.2
(16.5)
(15.4)
8.2
(16.3)
(15.2)
8.1
(16.2)
(15.0)
8.0
(16.0)
(14.8)
7.9
(15.8)
(14.6)
7.8
(15.7)
(14.2)
7.8
(15.5)
(14.0)
7.7
(15.4)
(13.8)
7.6
(15.2)
(13.6)
7.5
(15.0)
(13.6)
7.4
(14.9)
(13.4)
7.4
(14.7)
(13.2)
7.3
(14.6)
(13.0)
7.2
(14.4)
(12.8)
7.1
(14.2)
(12.6)
7.0
(14.1)
(12.4)
7.0
(13.9)
(12.2)
6.9
(13.8)
(12.0)
6.8
(13.6)
(11.8)
6.7
(13.4)
(11.6)
6.6
(13.3)
(11.4)
6.6
(13.1)
(11.2)
6.5
(13.0)
(11.0)
6.4
(12.8)
(10.8)
6.3
(12.6)
(10.6)
6.2
(12.5)
(10.4)
6.2
(12.3)
(10.2)
6.1
(12.2)
(10.0)
6.0
(12.0)
(9.8)
5.9
(11.8)
Table 27 — 45Q DOAS Size 5 ECM Calibration (cont)
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
mA
780
764
748
732
715
699
683
667
650
634
618
602
585
569
553
537
520
504
488
472
455
439
423
407
390
374
358
342
325
309
293
277
260
244
228
212
195
179
163
147
130
114
98
82
65
49
33
17
NOTE: CFM values below recommended minimum may affect life of
motor.
30
ACU-0
REMOTE 0-10VDC
(0-20mA)
VCU
DC SIGNAL
(OPTION 7)
VDC
mA
48
4.8
(9.6)
47
4.7
(9.4)
46
4.6
(9.2)
45
4.5
(9.0)
44
4.4
(8.8)
43
4.3
(8.6)
42
4.2
(8.4)
41
4.1
(8.2)
40
4.0
(8.0)
39
3.9
(7.8)
38
3.8
(7.6)
37
3.7
(7.4)
36
3.6
(7.2)
35
3.5
(7.0)
34
3.4
(6.8)
33
3.3
(6.6)
32
3.2
(6.4)
31
3.1
(6.2)
30
3.0
(6.0)
29
2.9
(5.8)
28
2.8
(5.6)
27
2.7
(5.4)
26
2.6
(5.2)
25
2.5
(5.0)
24
2.4
(4.8)
23
2.3
(4.6)
22
2.2
(4.4)
21
2.1
(4.2)
20
2.0
(4.0)
19
1.9
(3.8)
18
1.8
(3.6)
17
1.7
(3.4)
16
1.6
(3.2)
15
1.5
(3.0)
14
1.4
(2.8)
13
1.3
(2.6)
12
1.2
(2.4)
11
1.1
(2.2)
10
1.0
(2.0)
9
0.9
(1.8)
8
0.8
(1.6)
7
0.7
(1.4)
6
0.6
(1.2)
5
0.5
(1.0)
4
0.4
(0.8)
3
0.3
(0.6)
2
0.2
(0.4)
1
0.1
(0.2)
ACU-P
REMOTE
2-10VDC
(4-20mA)
DC SIGNAL
(OPTION 8)
VDC
mA
5.8
(11.7)
5.8
(11.5)
5.7
(11.4)
5.6
(11.2)
5.5
(11.0)
5.4
(10.9)
5.4
(10.7)
5.3
(10.6)
5.2
(10.4)
5.1
(10.2)
5.0
(10.1)
5.0
(9.9)
4.9
(9.8)
4.8
(9.6)
4.7
(9.4)
4.6
(9.3)
4.6
(9.1)
4.5
(9.0)
4.4
(8.8)
4.2
(8.6)
4.2
(8.5)
4.1
(8.3)
4.0
(8.2)
3.9
(8.0)
3.8
(7.8)
3.8
(7.7)
3.6
(7.5)
3.7
(7.4)
3.6
(7.2)
3.5
(7.0)
3.4
(6.9)
3.4
(6.7)
3.3
(6.6)
3.2
(6.4)
3.1
(6.2)
3.0
(6.1)
3.0
(5.9)
2.9
(5.8)
2.8
(5.6)
2.7
(5.4)
2.6
(5.3)
2.6
(5.1)
2.5
(5.0)
2.4
(4.8)
2.3
(4.6)
2.2
(4.5)
2.2
(4.3)
2.1
(4.2)