Carrier 45 Series Installation, Start-Up And Service Instructions Manual page 23

Fan powered variable air volume terminals
Table of Contents

Advertisement

Table 20 — 45J Size 3 ECM Calibration
REMOTE 0-10VDC
VCU
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
VDC
1100
100
10.0
1089
99
9.9
1078
98
9.8
1067
97
9.7
1056
96
9.6
1045
95
9.5
1034
94
9.4
1023
93
9.3
1012
92
9.2
1001
91
9.1
990
90
9.0
979
89
8.9
968
88
8.8
957
87
8.7
946
86
8.6
935
85
8.5
924
84
8.4
913
83
8.3
902
82
8.2
891
81
8.1
880
80
8.0
869
79
7.9
858
78
7.8
847
77
7.7
836
76
7.6
825
75
7.5
814
74
7.4
803
73
7.3
792
72
7.2
781
71
7.1
770
70
7.0
759
69
6.9
748
68
6.8
737
67
6.7
726
66
6.6
715
65
6.5
704
64
6.4
693
63
6.3
682
62
6.2
671
61
6.1
660
60
6.0
649
59
5.9
638
58
5.8
627
57
5.7
616
56
5.6
605
55
5.5
594
54
5.4
583
53
5.3
572
52
5.2
561
51
5.1
550
50
5.0
ACU-P
ACU-0
REMOTE
2-10VDC
(0-20mA)
(4-20mA)
DC SIGNAL
DC SIGNAL
(OPTION 7)
(OPTION 8)
mA
VDC
(20.0)
10.0
(20.0)
(19.8)
9.9
(19.8)
(19.6)
9.8
(19.7)
(19.4)
9.8
(19.5)
(19.2)
9.7
(19.4)
(19.0)
9.6
(19.2)
(18.8)
9.5
(19.0)
(18.6)
9.4
(18.9)
(18.4)
9.4
(18.7)
(18.2)
9.3
(18.6)
(18.0)
9.2
(18.4)
(17.8)
9.1
(18.2)
(17.6)
9.0
(18.1)
(17.4)
9.0
(17.9)
(17.2)
8.9
(17.8)
(17.0)
8.8
(17.6)
(16.8)
8.7
(17.4)
(16.6)
8.6
(17.3)
(16.4)
8.6
(17.1)
(16.2)
8.5
(17.0)
(16.0)
8.4
(16.8)
(15.8)
8.3
(16.6)
(15.6)
8.2
(16.5)
(15.4)
8.2
(16.3)
(15.2)
8.1
(16.2)
(15.0)
8.0
(16.0)
(14.8)
7.9
(15.8)
(14.6)
7.8
(15.7)
(14.2)
7.8
(15.5)
(14.0)
7.7
(15.4)
(13.8)
7.6
(15.2)
(13.6)
7.5
(15.0)
(13.6)
7.4
(14.9)
(13.4)
7.4
(14.7)
(13.2)
7.3
(14.6)
(13.0)
7.2
(14.4)
(12.8)
7.1
(14.2)
(12.6)
7.0
(14.1)
(12.4)
7.0
(13.9)
(12.2)
6.9
(13.8)
(12.0)
6.8
(13.6)
(11.8)
6.7
(13.4)
(11.6)
6.6
(13.3)
(11.4)
6.6
(13.1)
(11.2)
6.5
(13.0)
(11.0)
6.4
(12.8)
(10.8)
6.3
(12.6)
(10.6)
6.2
(12.5)
(10.4)
6.2
(12.3)
(10.2)
6.1
(12.2)
(10.0)
6.0
(12.0)
Table 20 — 45J Size 3 ECM Calibration (cont)
SET
MANUAL %
POINT
DISPLAY
CFM
(OPTION 6)
mA
539
528
517
506
495
484
473
462
451
440
429
418
407
396
385
374
363
352
341
330
319
308
297
286
275
264
253
242
231
220
209
198
187
176
165
154
143
132
121
110
99
88
77
66
55
44
33
22
11
NOTE: CFM values below recommended minimum may affect life of
motor.
23
ACU-0
REMOTE 0-10VDC
(0-20mA)
VCU
DC SIGNAL
(OPTION 7)
VDC
mA
49
4.9
(9.8)
48
4.8
(9.6)
47
4.7
(9.4)
46
4.6
(9.2)
45
4.5
(9.0)
44
4.4
(8.8)
43
4.3
(8.6)
42
4.2
(8.4)
41
4.1
(8.2)
40
4.0
(8.0)
39
3.9
(7.8)
38
3.8
(7.6)
37
3.7
(7.4)
36
3.6
(7.2)
35
3.5
(7.0)
34
3.4
(6.8)
33
3.3
(6.6)
32
3.2
(6.4)
31
3.1
(6.2)
30
3.0
(6.0)
29
2.9
(5.8)
28
2.8
(5.6)
27
2.7
(5.4)
26
2.6
(5.2)
25
2.5
(5.0)
24
2.4
(4.8)
23
2.3
(4.6)
22
2.2
(4.4)
21
2.1
(4.2)
20
2.0
(4.0)
19
1.9
(3.8)
18
1.8
(3.6)
17
1.7
(3.4)
16
1.6
(3.2)
15
1.5
(3.0)
14
1.4
(2.8)
13
1.3
(2.6)
12
1.2
(2.4)
11
1.1
(2.2)
10
1.0
(2.0)
9
0.9
(1.8)
8
0.8
(1.6)
7
0.7
(1.4)
6
0.6
(1.2)
5
0.5
(1.0)
4
0.4
(0.8)
3
0.3
(0.6)
2
0.2
(0.4)
1
0.1
(0.2)
ACU-P
REMOTE
2-10VDC
(4-20mA)
DC SIGNAL
(OPTION 8)
VDC
mA
5.9
(11.8)
5.8
(11.7)
5.8
(11.5)
5.7
(11.4)
5.6
(11.2)
5.5
(11.0)
5.4
(10.9)
5.4
(10.7)
5.3
(10.6)
5.2
(10.4)
5.1
(10.2)
5.0
(10.1)
5.0
(9.9)
4.9
(9.8)
4.8
(9.6)
4.7
(9.4)
4.6
(9.3)
4.6
(9.1)
4.5
(9.0)
4.4
(8.8)
4.2
(8.6)
4.2
(8.5)
4.1
(8.3)
4.0
(8.2)
3.9
(8.0)
3.8
(7.8)
3.8
(7.7)
3.6
(7.5)
3.7
(7.4)
3.6
(7.2)
3.5
(7.0)
3.4
(6.9)
3.4
(6.7)
3.3
(6.6)
3.2
(6.4)
3.1
(6.2)
3.0
(6.1)
3.0
(5.9)
2.9
(5.8)
2.8
(5.6)
2.7
(5.4)
2.6
(5.3)
2.6
(5.1)
2.5
(5.0)
2.4
(4.8)
2.3
(4.6)
2.2
(4.5)
2.2
(4.3)
2.1
(4.2)

Advertisement

Table of Contents
loading

Table of Contents