3.9.5
Frequency Metering (Address 4400)
Use this address block to display the system frequency. The
available measured value is listed in Table 3.25.
Access the desired sl.t>address using steps 1-3 of the stan-
dard operation sequence, Table 3.4.
J
Subaddress
j
Data
I
Range
1
4401
j Frequency
j
45 - 65 Hz
Table
3.25
Frequency Metering, Major Block 4400
3.9.6
Min/Max Log Amps (Address 4600)
Use this address block to display the minimlJTI and maxi-
mlJTI current values measured by the relay. The available
measured values are listed in Table 3.26.
This log contains minimlJTI and maximlJTI values measured
by the relay while not in pickup. The collected information is
coJ'Tl)ared against previously stored values and the log is
updated.
AI
logged values are tine stamped and resetting
the log (see section 3.13.2, address block 8200) will reset all
log values.
Access the desired sl.t>address using steps 1-3 of the stan-
dard operation sequence, Table 3.4.
Siemens Energy & Automation, Inc.
3
Operation
Subaddress
Data
I
Description
I
4601
11 min
I
Phase 1 minimum
I
current
4602
11 max
Phase 1 maximum
I
current
4603
112min
Phase 2 minimum
I
current
4604
112max
Phase 2 maximum
I
current
4605
113
min
Phase 3 minimum
I
current
4606
113
max
Phase 3 maximum
I
current
4607
liN min
Ground minimum
I
current
4608
liN max
G'ound maximum
I
current
4609
llavmin
Minimum average
I
current
4610
llavmax
Maxinum average
I
current
4611
111dmin
Minimum demand
I
current on Phase 1
4612
111dmax
Maximum demand
I
current on Phase 1
4613
112dmin
Minimum demand
I
current on Phase 2
4614
12dmax
Maximum demand
current on Phase 2
4615
113dmin
Minimum demand
I
current on Phase 3
4616
113dmax
Maximum demand
I
current on Phase 3
4617
lavdmin
Mnimum average
demand caiCUated
4618
lavdmax
Maximum average
demand calcUated
Table 3.26
Q.Jrrent M1n/Max Log, Major Block 4600
3.9.7
Min/Max Log Volts (Address 4700)
Use this address block to display the minimlJTI and maxi-
mum voltage values measured by the relay. The available
measured values are listed in Table 3.27. No voltages are
metered unless the voltage input option is installed.
This log contains minimlJTI and maximlJTI values gathered
by the relay while not in pickup. The collected information is
compared against previously stored values and the log is
updated. All logged values are time stamped and resetting
the log (see section 3.13.2, address block 8200) will reset all
log values.