Siemens ISGS Operator's Manual page 25

Intelligent switchgear system
Hide thumbs Also See for ISGS:
Table of Contents

Advertisement

3
Operation
this, it is extremely important that the physical wimg
con-
nections of the protective circuit, includilg connections to
the circuit breaker, match the output connections of the
relay. If the matrixing of the ISGS relay is changed,
double-
check conformance to the wiring of the protective circuit,
and always perform a test to assure that operation of a
pro-
tective function results i1 trippilg of the circLit breaker.
Note:
Do not change matrixing of ISGS relay when the
associated prmary circuit is in service. In order to change
matrixilg, the ISGS relay must reinitialize. Durilg reilitializa-
tion, the ISGS relay does not provide protection.
Use address block
6400
to display or change matrix
infor-
mation for Trip Contact
1
and
Trip Contact
2.
The available
parameters are listed i1 Figure
3
.
7.
Subaddress
Parameter
Matrix
Position
6401
6402
Trip Contact 1
1
001
Trp Contact
2
002
003
020
Figure
3.7.
Matrix Menu Structure
To configure the matrixing:
Options
-
so
Ph Trip
50
N
Trip
51 PhTrip
51 N
Trip
67Ph Trp
67N
Trip
27Trip
59 Trip
PSVTrip
OvrAmpsDmd PU
OvrKWDmd PU
OVTKVAA
PU
OvrKVA
PU
PFLAG PU
PFLEAD PU
50BF
Trip
TripSrcMon PU
TripCoiiCntPU
Brkr Mech PU
Comm Event 1
Comm Event 2
Comm
Event
3
Comn Evenl
4
Comm EventS
Not
Matrixed
1
.
Ensure power is applied to the relay, the System
LED
is
on, then press the
Direct Addr
key.
2.
Enter
"6400"
using the numeric keypad and press the
Enter
key.
3.
Use the
arrow
keys
and
scroll to the desired subad-
dress listed i1 Figure 3. 7, or press the
Direct Addr
key
and enter the subaddress via the numeriG keypad and
press the
Enter
key.
4.
Press the
F
key
and
LSe
the
arrow
keys to scroll
to
the
C'3sired matrix position (001-020).
5.
Press the
Password
key and enter the password
"000000"
and press the
Enter
key. The message
"PW
ACCEPTED" will appear on the dispey.
32
6.
Press the
Enter
key again
and
the relay will retum to
the parameter you wanted to change; observe the
blinking dispey cursor. If the display cursor is not blink-
ing, you will be unable to change a parameter; retry the
last step.
7.
Press the
No
key until the desired matrixing option
appears on the relay display and press the
Enter
key.
Scroll to the next matrix position to change additional
parameters or proceed to the next step.
8.
Press the
F
key and then the
Enter key.
The message
"SAVE
NEW
SET
TING" will
be
displayed.
9.
Press the
Yes
key and the ISGS relay will reset to the
new parameters.
3.12
Operating Parameters (Address
7000)
3.12.1 Power
On
Meter Display (Address 7000)
Use this address block to select which metered values will
displayed by the Power On Meter Display (see section
3.6.2).
Two values may be displayed - one i1 each of the
two lines of the
LCD.
The
ava~able
parameters are listed in
Table
3.31.
Subaddress
Parameter
Selection
7005
LCD
Li1e 1
lx
(x
=
1,
2, 3, or N)
lavg
ldmdx(x
=
1, 2, or 3)
ldmdavg
Vx(x=
1-2,2-3,
or3-1)
Vllavg
Vx-N (x
=
1, 2, or 3)
VLNavg
w
WH
Wdmd
VA
VAR
VARH
PF
f
7006
LCD Line 2
(same
as
7005)
Table 3.31
PONer On Meter DISplay Conf1gurat1on, Major
Block 7000
3.12.2 Alternate Parameter Sets
The ISGS relay supports two sets of protection settings,
denoted as parameter set A and parameter set B. The relay
uses the parameter set designated as the active set in major
address block 7100. The parameter sets may
be
configured
as the system needs dictate. For example, parameter
set
A
may be used for protective settings used in the summer-
tme, whereas parameter set B might comprise the settings
appropriate to
w
ilter, when
low
er ambient temperatures
colid
allow
higher loadilg than i1 the summer. Alternatively,
parameter
set
A might be for normal production periods,
w
ith parameter set B for construction, periodic shutdowns
Siemens Energy & Automation, Inc.