Summary of Contents for ECKELMANN UA 410 L Case Controller
Page 1
Operating instruction UA 410 L Case Controller Temperature Data Logging Controller - Version V1.50 Firmware V1.50 - Doku 2.0 06. April 2016...
Page 2
All rights to any use whatever, utilisation, further development, forwarding and creation of copies remain with the Eckelmann AG company. In particular, neither the contract partners of Eckelmann AG nor other users have the right to distribute or mar ket the IT programs/program parts or modified or edited versions without express written permission. To some extent, names of products/goods or designations are protected for the respective manufacturer (registered trademarks etc.);...
Conventions Explanation of 'General Instructions' A general instruction is composed of two elements: 1. A pictogram of a hand at the side of the page as well as 2. The actual text: For example: Further information on the device's degree of protection is contained in the chapter ”Technical Data”. Explanation of 'Safety Instructions and Hazard Warnings' Safety instructions or hazard warnings are composed of four elements: 1.
Warning Signs and Symbols Employed Explanation of the warning signs and symbols employed for the safety instructions and hazard warnings in this documentation: S Attention symbol - general hazard warning 1. Hazard warning The attention symbol indicates all safety instructions in this operating and service manual, which, if not observed, could result in danger to life and limb.
Safety instructions Safety instructions The safety regulations, codes and notes contained in this section must definitely be observed and complied with at all times. During repairs on the entire E*LDS system, the accident prevention regu lations and general safety instructions must be observed. Important information (safety instructions and hazard warnings) are indicated by corresponding symbols (see page 1 of the chapter ”Conven...
Safety instructions Work on electrical equipment may only be undertaken by authorized and duly trained personnel (as defined by DIN/VDE 0105 and IEC364) with full observance of the currently valid regulations contained in the following: - VDE Regulations - Local safety codes - Intended use see chapter 1.3 - BGV A3 - Five Safety Rules...
Safety instructions 1.3 Intended use This control system may only be used for the purpose for which it is intended: The UA 410 L control system has been designed for use as a data logging controller in commercial and indus trial refrigeration systems with the intended functional scope as described in these operating instructions, and it is to be used under the environmental conditions in these instructions.
Safety instructions 1.5 Electrostatic sensitive devices (ESDs) Electronic components and assemblies (e.g. printed circuit boards) are vulnerable to electrostatic discharge. Regulations for handling and working with electrostatic sensitive devices must definitely be observed and complied with, see also section 1.5.1! All electrostatic sensitive devices (ESDs) are identified by the warning sign illustrated.
System Design of UA 410 L System Design of UA 410 L Figure: UA 410 L AC - full configuration 2.1 Application The UA 410 L AC temperature recording controller is based on the UA 400 hardware and has been developed for use as a temperature recording controller of up to 10 temperature measurement points.
System Design of UA 410 L 2.2 Hardware The temperature recording controller is housed in a plastic casing for DIN rail mounting and does not require any further optional expansion modules. Up to 99 case controllers can be used within the E*LDS system. As required, a BT 300 x Operator Interface and up to 4 BT 30 Temperature Displays can be connected.
System Design of UA 410 L Real-time clock Battery-backed, lithium cell For precise details of the UA 410 L AC see chapter 3.1. The connection and terminal configurations are described in the chapter Connection and Terminal Configuration. 2.3 New features compared to previous versions Version 1.50 S New hardware platform UA 410 L - blue main board...
Page 16
System Design of UA 410 L Version 1.50 S New hardware platform UA 410 L - for DIN rail mounting S Optimised labelling strip S Differences in the complete hardware (UA 410 L AC, see photo) compared to UA 300 L AC: - 2 analogue inputs 4..20 mA Currently reserve for future applications - 2 analogue outputs 0..
Application of UA 410 L Application of UA 410 L 3.1 Versions The UA 410 L is only available in the AC variant and has the following features: UA 410 L AC For DIN rail mounting For integration in the CAN bus of the E*LDS system Replacement controller for UA 300 L Replacement controller for the LDS1 system (connection to the LDS1 system proceeds via the CI320 interface)
Application of UA 410 L 3.2 Controller type Ttemperature recording controller UA 410 L Case Controller: Controller type Application UA 410 L Temperature Data Logging Controller for maximum 10 temperature sensors (with the option of on-off control/defrosting of five independent refrigeration points for the first five sensors).
Function of UA 410 L Function of UA 410 L Parameters mentioned in this section are described in the Menu Structure section. It will normally not be necessary to change the default settings of these parameters. Parameters that do not allow changing are termed fixed parameters below.
Function of UA 410 L 4.2 Required and optional sensors On the standard UA 400 controllers the Sensor Scan function determines the number of sensors connected. This enables sensors that are not connected to be removed from sensor break monitoring. However, the following procedure is required with the UA 410 L Temperature Data Logging Controller: If specific sensors are deactivated for the alarm signalling, the sensor priority must be configured accordingly.
Function of UA 410 L Cooling relay operation N.O. control, i.e. cooling is OFF when the case controller is de-energized. Cooling (not the controller itself) can be stopped via Digital Input 1 (Terminals D11/12). Control is suppressed when a 230 V AC signal is applied to this input. Cooling is active when the input is not connected or not active.
Function of UA 410 L 4.3.1.3 Temperature recording Refrigeration point controller Rx.6 Rx.1 Rx.7 Rx.2 Rx.8 Rx.3 Rx.9 Rx.4 Rx.0 Rx.5 Rx.1 .. Rx.0: 10 temperature sensors for temperature recording A separate sensor name can be assigned to each sensor for better identification of the measuring location.
Function of UA 410 L 4.3.2 Defrosting Defrosting (available only with the first five temperature sensors Rx.1 .. Rx.5) frees the evaporator of ice forming from normal operation. Defrosting always takes place either by off-cycling the compressor. During defrosting, temperature control of the refrigeration point is inactivated. Refrigeration point controller Rx.1...
Function of UA 410 L Defrost termination Defrosting can be terminated by two methods: ‐ Defrost termination temperature obtained on corresponding temperature sensor ‐ Expiration of safe defrost time Defrosting is always terminated by the safe defrost time when the defrost termination temperature is set to ”--”, in which case no ”Defrost Termination By Time”...
Function of UA 410 L 4.3.4 Archiving operating data 4.3.4.1 Temperature recording to EU Regulation 37/2005 If the controller is connected to the CAN bus, only the sensors Rx.1 and Rx.2 in the system centre / store computer are archived. This archiving can cover a full year. Local temperature recording Temperature is recorded at 15-minute intervals in the internal flash memory.
Page 26
Function of UA 410 L CI 4x00: All 10 temperature sensors are supported in system centres. CI 3x00: Whether the version in use supports this function can be checked in the System Centre / Store Com puter User Guide. Store Computers of all versions are always capable of archiving two temperatures. With all, the recording interval is 15 minutes and data is archived for a period of one year.
Function of UA 410 L Values 3 to 10 of the EU Archive Zone parameter are to be used only for recording in conjunction with the Temperature Data Logging Controller itself. Only values 1 or 2 may be used for recording in conjunction with a case/EU archiving must also be active on the System Centre / Store Computer in order to commence recording (see System Centre / Store Computer operating instruction).
Function of UA 410 L 4.4 Temperature display BT 30 4.4.1 Offset for temperature display An offset (parameter Offset in Menu 2) can be applied to temperature values as a means of compensating dif ferences between readings on thermometers in the refrigerated display case and on the case controller. This offset affects the complete functionality (cooling, defrosting, recording, etc.) for which the sen...
Page 29
Function of UA 410 L Before connecting to the case/coldroom controller, all BT 30 Temperature Displays must be addressed by means of the exposed leads (see illustration): Leads Konfiguration BT 30 Address 1 Address 2 Address 3 Address 4 Green Closed Open Closed...
Page 30
Function of UA 410 L Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
Installation and Startup of UA 410 L Installation and Startup of UA 410 L Important safety instructions! Before the installation and commissioning of the controller, chapter 1 should be carefully read in its entirety and all safety instructions and hazard warnings observed. The controller should only be used with compatible versions of the PC software LDSWin, otherwise the range of functions could be restricted.
Installation and Startup of UA 410 L 5.1.1.1 Mounting on the DIN rail Step 1: The two retaining springs on the underside of the device are to be pulled out using a flat-bladed screw driver until they click into place. In order to carry out the assembly/disassembly there must be a distance of at least 8 mm between the bottom of the case controller and the next component (e.g.
Installation and Startup of UA 410 L 5.1.1.2 Disassembling from the DIN rail Warning - hazardous electrical voltage! Danger of electric shock! When disassembling the safety instructions and work safety instructions in chapter 1 must be observed. All connectors may only be connected and disconnected when power is off.
Installation and Startup of UA 410 L 5.1.2 Handling of the spring terminals All terminal connections of the controller are implemented with grey mating connectors with spring terminals (push-in spring connection). The connectors have the following characteristics: S Conductors with cross sections between 0.25 and 2.5 mm² can be used. S All mating connectors are coded and any reverse polarity is therefore ruled out.
Installation and Startup of UA 410 L 5.2 Basic configuration The following basic settings on the hardware and software side must be made during the commissioning of the case controller: Settings before connection of the power supply S Set CAN bus address (Nd.nnn = 1 to 99) by Decade Switches S1 and S2. S Set controller type and Mster/Slave mode on DIP Switch S3.
Installation and Startup of UA 410 L 5.3 Setting CAN bus address CAN bus address (Nd.nnn = 1 to 99) are set by Decade Switches S1 and S2. For all case controllers installed in refrigerated cases, a unique CAN bus address must first be set at the two selector switches (S1, S2) before commissioning.
Installation and Startup of UA 410 L 5.4 Setting the controller type Caution: data loss! All parameters are reset to their factory settings if the controller type is changed or due to a first start (see chapter 5.8)! Setting controller type The required controller type is set via the DIP switch S3 by adjusting the coding switches 1..8 with a thin screw...
Installation and Startup of UA 410 L 5.5 Terminal assignment for 230 V AC power supply Warning - hazardous electrical voltage! Danger of electric shock! BEFORE and AFTER connection it must checked that the 230 V AC supply cable is off load! The power supply cable is connected to the case controller using the right hand terminal block PE/L/N: 230 V AC 11 VA...
Installation and Startup of UA 410 L 5.5.1 Status LEDs Warning - hazardous electrical voltage! Danger of electric shock! The device is never to be operated without its casing. Before opening the casing the equipment must be switched to zero potential. CAN-BUS BATTERY LED12...
Installation and Startup of UA 410 L 5.6 Basic configuration of the controller The lock-down must previously be deactivated on the higher level controller (system centre / store computer or operator terminal) so that configuration settings can be made on the controller. Deactivating the input lock-down A.
Page 41
Installation and Startup of UA 410 L Basic configuration of the controller - select refrigeration point (Menu 6-1) The menus shown below only provide the overview; the display can be different for certain controller ty pes. Details are described in the "Menu Structure" chapter. 6 Configuration - 1 Refrigeration Point REFR.
Page 42
Installation and Startup of UA 410 L Menu 6 Configuration - select 2 Select Controller 6 Configuration - 2 Controller CONTROLLER POS: XXX Type, serial number and master-slave (ON/OFF) 1 Type and Version Select temperature sensor type 2 Sensor Type Exit Configuration: Press the ESC key twice to exit the menu.
Installation and Startup of UA 410 L 5.6.1 Naming of the controller The following parameters are available for naming the controller: - refrigeration point name (19 characters, can be freely edited) - refrigeration point position (5 characters, can be freely edited) The controller can be named using the system centre, store computer, operator terminal or the PC software LDSWin.
Installation and Startup of UA 410 L 5.9 Maintenance and battery replacement Only UA 410 L AC The case controller contains a backup battery of Type CR 2450 N, 3V Lithium. The case controller must be re moved from the system to change the battery. During this time, control and monitoring of the refrigeration point are disabled.
Page 45
Installation and Startup of UA 410 L Do not touch the new battery with metal pliers, as it might be short-circuited and destroyed: - wipe the new battery with a clean, dry cloth, - do not touch the contact faces on the edges of the new battery. Never dispose of this product with other household waste.
Installation and Startup of UA 410 L 5.10 Firmware Update The case controller is supplied with the current firmware, ready for operation. Future software versions can be loaded into the case controller as required by means of a firmware update, and thus updated. A software update is only to be carried out by trained staff or factory-side by the manufacturer.
Page 47
Installation and Startup of UA 410 L Step 1: Install the software 1. Before first connecting the controller to the PC the installation program ”Firmware_Up loader_Setup_vxx.exe” must be executed once. Please follow the instructions given by the installation assistant. In the following window the components to be installed can be selected. Now select the target folder: Following installation the PC must be restarted: Firmware V1.50 - Doku 2.0 06.
Page 48
Installation and Startup of UA 410 L Step 2: Changing the position of DIP switch S3 and connecting the controller The original position of the coding switches 1..8 of the DIP switch S3 must be documented! 1. In order to carry out the firmware update all coding switches 1..8 of DIP switch S3 must be set to ON. 1 2 3 4 5 6 7 8 After the firmware update has been carried out all the coding switches 1..8 of the DIP switch S3 must be returned to their original position, see chapter 5.10.2...
PC. Step 1: Under ”Start / Programs / ECKELMANN / Firmware Uploader” start the program ”KGL Firmware Uploader”. The following window opens: Select language, and then select the path to the folder for the new firmware (binary file).
Page 50
Installation and Startup of UA 410 L Step 3: Press the button ”Find Controller” in order to locate the controller. Then press the button ”Update Firmware” in order to start the firmware upload. Step 4: Following the start of the firmware upload a confirmation window appears, confirm this with ”YES”. Step 5: Following the successful firmware update the program can be closed.
Installation and Startup of UA 410 L 5.10.3 Rectification of driver problems Should the driver installation be incomplete or should the controller have been accidentally connected to the PC before the execution of the installation program, then the following instructions will provide you with information on how the problem can be rectified: Windows XP/Vista: If the controller was accidentally connected to the PC before the execution of the installer, then the driver must be updated in the system control.
Page 52
Installation and Startup of UA 410 L Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
Pin and Terminal Assignments of UA 410 L Pin and Terminal Assignments of UA 410 L 6.1 Terminal diagram Power Analog Digital Relay Outputs supply Outputs Inputs CAN bus 0..10 V 230 V AC 230 V AC 230 V AC 6(3) A 11 VA CAN-BUS...
Pin and Terminal Assignments of UA 410 L 6.2 Terminal assignment of the 230 V AC power supply Warning - hazardous electrical voltage! Danger of electric shock! BEFORE and AFTER connection it must checked that the 230 V AC supply cable is off load! 230 V AC 11 VA CAN-BUS...
Pin and Terminal Assignments of UA 410 L 6.3 Terminal assignment of the 230 V AC relay outputs Warning - hazardous electrical voltage! Danger of electric shock! BEFORE and AFTER connection it must checked that the 230 V AC relay outputs are off load! Low voltage and safety extra-low voltage must not be applied together at the relay outputs.
Pin and Terminal Assignments of UA 410 L 6.4 Mode of operation of the relay and transistor outputs The table shows operation of the outputs for the separate controller types. Relay outputs 230 V AC Transistor outputs 24 V DC/50 mA Controller type Cooling Alarm...
Pin and Terminal Assignments of UA 410 L If 230 V AC voltage is present at digital input, the associated red LED lights, see chapter 5.5.1 Status LEDs for details. 6.6 Terminal assignment of the 0..10 V analogue outputs This functionality is currently not used! Warning - hazardous electrical voltage! Connecting mains power to the analogue outputs will lead to the destruction of the controller!
Pin and Terminal Assignments of UA 410 L 6.7 Terminal assignment of the CAN bus Warning - hazardous electrical voltage! If mains voltage is connected to the CAN bus terminals, this will result in the destruction of all components connected to the CAN bus! Leads running of the CAN bus must be shielded (cable type: LiYCY)! As a general rule, care should be taken to ensure that signal leads and leads carrying a supply voltage are routed through separate cable channels.
Pin and Terminal Assignments of UA 410 L 6.8 Terminal assignment of the 24 V DC transistor outputs Warning - hazardous electrical voltage! Connecting mains power to the transistor outputs will lead to the destruction of the controller! Destruction of the transistor outputs! Due to the capacity of the transistor outputs of a max.
Pin and Terminal Assignments of UA 410 L 6.9 Terminal assignment of the DISPLAY interface DISPLAY BT 300 BT 30 An operator interface of the BT 300 series (e.g. for service purposes) and up to four BT 30 temperature displays can be connected to the DISPLAY interface.
Pin and Terminal Assignments of UA 410 L 6.11 Terminal assignment of the analogue inputs of temperature sensors Warning - hazardous electrical voltage! Connecting mains power to the analogue inputs will lead to the destruction of the controller! Malfunctions due to interference sources! All leads running to and from the case controller must be shielded (cable type: LiYCY)! No shielding is required on sensor leads when installed exclusively inside the refrigerated display case and when external interference (for example from parallel power wires) is not to be expected (see operating instruction “Basics and General Safety and Connection...
Pin and Terminal Assignments of UA 410 L 6.12 Terminal assignment of the USB interface The USB interface facilitates the uploading of a firmware update. Furthermore, in future (currently not available) it will be possible to read out the operating data of the case controller via a PC equipped with LDSWin. USB-LED DISPLAY Typ B...
Operation of UA 410 L Operation of UA 410 L 7.1 Operation possibilities The controller provides menus and screens for the display and adjustment of values. However, no operation for this is provided on the controller itself. The actual operation of these menus is performed externally using the following possibilities: S Local operation with a BT 300 x operator interface: The operation is performed directly on-site at the con...
Operation of UA 410 L 7.2 Local operation with a BT 300 x operator interface BT 300 x RESET DISPLAY An operator interface in the BT 300 series is connected locally via the DISPLAY interface. Thereby, the con troller can be operated standalone as shown or also connected to the CAN bus. The operation here largely corresponds to the possibilities as described for the system centre, the store com...
Operation of UA 410 L 7.3 Remote control via a terminal Further details for the operation of a system centre, store computer or operator terminal can be found in their operating manuals. For the remote control of a controller, it makes no difference whether this is done with a system centre (A), a store computer or with an operator terminal (B) as the user interfaces on the terminals are almost identical and the same functions are available.
Operation of UA 410 L 7.3.1 Menus and operating screens If the system centre, store computer or operator terminal remain locked down, settings on the con troller are read-only. Changes and inputs are not possible. However, if any parametrisation is required, the lock-down for the input must be removed first, see chapter 7.3.3.
Page 67
Operation of UA 410 L Menus A menu can contain up to ten menu items (0 .. 9; 0 for menu item 10). After the selection of a menu item using the cursor buttons (↑) and (↓) and by tapping the ENTER button (↵) or by tapping the buttons 0..9), other sub menus or operating screens are displayed.
Operation of UA 410 L Entering text In fields that allow text entry, text can also be entered by the alphanumeric keypad. Repeatedly press the nu meric keys to generate letters. Press the ENTER key (↵) to confirm the entered value or text. Letter/Character PQRS PQRS...
Operation of UA 410 L 7.3.2.1 System Centre CI 4x00 The terminal for remote control of the controller (Menu 2-2 or Menu 4-2) is called in the system centre as fol lows: Step 1: Tap "2 - System overview" or "4 - Configuration" in the main menu. If "2"...
Operation of UA 410 L 7.3.3 Deactivating the input lock-down Operation via system centre, store computer or operator terminal is only possible for controllers with CAN bus connection; the removal of the lock-down is then applicable for all components in the CAN bus system. The lock-down is automatically reactivated 15 minutes after the last button tap.
Operation of UA 410 L 7.3.4 Activating service mode For repair and maintenance work, service personnel can deactivate the remote alarm function of the system centre and of the store computer for a limited period using the service mode. The activation of the service mode must only be carried out by service personnel. If there are still pending alarms (with the priority 1..2) after the time of the Service Mode has elapsed, the audible warning devices and the alarm relays are activated and the alarms are forwarded using the automatic transmission of alarms.
Page 72
Operation of UA 410 L Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
Menu Structure of UA 410 L Menu Structure of UA 410 L The sensor wanted must first be selected to open the main menu of a temperature sensor (Rx.1 .. Rx0). REFR. PT. POS: XXX Select 1st temperature sensor Rx.1 1 Temp.
Menu Structure of UA 410 L 8.2 Menu 0 Main menu Temp. Rx.y POS: XXXXX Move to menu 1 1 Actual Value Move to menu 2 2 Setpoints Move to menu 3 3 Clock Move to menu 4 4 Messages Move to menu 5 5 Archive Move to menu 6...
Menu Structure of UA 410 L 8.4 Menu 2 Setpoints Entry Default SETPOINTS POS: XXXXX High temperature setpoint -50..100 10°C High Temp: xxx°C Low temperature setpoint -50..100 -5°C Low Temp: xxx°C High or low temperature delay 0..150 Delay: ↑, ↓, Priority: High or low temperature alarm priority --, 0..2...
Menu Structure of UA 410 L S Menu 3-1 Current Time When connected to the CAN bus, the default time is provided via the time master (system centre / store computer, operator terminal). Any entry made will then be overwritten by the default value. Entry Default CLOCK...
Menu Structure of UA 410 L S Menu 4-1 View messages MESSAGES POS: XXXXX Fault 1 message text Error Message 1: Start of Fault 1 dd.mm.yy hh:mm ON/OFF End of Fault 1 (only when Fault 1 terminated) dd.mm.yy hh:mm ON/OFF Fault n message text Error Message n: Start of Fault n...
Menu Structure of UA 410 L Following selection, the following menu will appear: Temp. Rx.y POS: XXXXX Time of archiving Record 1 dd.mm.yy hh:mm Status and temperature of Zone 1, see Note *) Zone 1: x °C *) Status ab covers following states of the refrigeration point. Display will be ”-- ” if state is not active. Status R = Cooling (with sensors Rx.1 ..
Page 79
Menu Structure of UA 410 L S Menu 6-2 Controller CONTROLLER POS: XXXXX Move to menu 6-2-1 1 Type and Version Move to menu 6-2-5 2 Sensor type S Menu 6-2-1 Type and Version Entry Default VERSION POS: XXXXX Set by DIP switch S3 UA400L CTRLR.
Page 80
Menu Structure of UA 410 L Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
The scope of our delivery is designated as a component exclusively for further processing. As a consequence of this fact, Eckelmann AG does not undertake any measures for the taking back or munici pal recycling of this product as it is not supplied directly to the free market.
Page 82
Decommissioning and disposal Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
Alarms and Messages of UA 410 L 10 Alarms and Messages of UA 410 L Message Cause Correction Hardware faults EEPROM Fault Component for saving configuration defective or confi Save parameters in LDSWin software, guration data in EEPROM implausible. perform first start if necessary and load parameters from LDSWin.
Alarms and Messages of UA 410 L 10.1 Alarm signaling and monitoring 10.1.1 High or low temperature alarm High or low temperature is alarmed when temperature rises or falls to the alarm setpoint and the set delay has expired. °C OVER TEMPERATURE TEMPERATURE REFERENCE VALUE...
Alarms and Messages of UA 410 L 10.1.4 Sensor break alarm Alarm is generated after the set delay expires (Menu 6-2-1) if the controller detects breakage or short circuit on a sensor. This delay time is global for the controller and applies equally for all sensors. Sensor break alarm is only generated when priority of the sensor concerned is set to a value other than ”-”.
Alarms and Messages of UA 410 L 10.2.1 Transient alarms and messages Transient alarms are one-time event alarms and are not time stamped for send time. As a result, transient alarms are not deleted automatically after the event and must be cancelled manually. This applies regardless of the setting made for Selfholding (Menu 6-2-3).
Specifications of UA 410 L 11 Specifications of UA 410 L 11.1 Electrical data Warning - hazardous electrical voltage! Danger of electric shock! Overvoltage category III (test voltage 4,0 kV) / pollution degree 2: All device connections designed for use with 230 V AC supply voltage must be connected to the same phase conductor.
Page 88
Specifications of UA 410 L UA 410 L AC Fieldbus port CAN bus, floating Data port DISPLAY: BT 300x Operator terminal and up to 4 BT 30 Temperature displays CI320 (TTY) Communication with the PC software for reading off the operating data USB interface For firmware update (in future it will be possible to connect a notebook (PC) to this interface for the direct parameterisation via LDSWin)
Page 89
Specifications of UA 410 L Supplement to standard DIN EN 12830 for temperature recorders (UA 410 L AC with L243 temperature sensor) Metrological characteristics Accuracy class Maximum permissible error +/- 1 K Resolution internal: 0.1 °C / display and recording: 1 K Recording interval 15 min.
Specifications of UA 410 L 11.2 Mechanical data of the controller DIN rail mounting of UA 410 L AC (C stands for ”In Cabinet”, meaning DIN rail mounting.) Gegenstecker mit Kabel Darstellung ohne Gegenstecker Connector set with cable View without connector set Set de connecteur s avec...
Order numbers and accessories of UA 410 L 12 Order numbers and accessories of UA 410 L 12.1 Case Controller Type Description Order number UA 410 L AC For DIN rail mounting, with CAN bus, real time clock, KGLUA4L016 internal archive, analog inputs and analog outputs 12.2 Accessories Accessories Description...
Page 92
Order numbers and accessories of UA 410 L Notice: Firmware V1.50 - Doku 2.0 06. April 2016...
Need help?
Do you have a question about the UA 410 L Case Controller and is the answer not in the manual?
Questions and answers