Operating instruction VS 3010 BS Pack Controller For booster / satellite systems July 2018, 1.02 - Firmware V5.06...
Page 2
All rights to any use whatever, utilisation, further development, forwarding and creation of copies remain with the Eckelmann AG company. In particular, neither the contract partners of Eckelmann AG nor other users have the right to distribute or market the IT programs/program parts or modified or edited versions without express written permission. To some extent, names of products/goods or designations are protected for the respective manufacturer (registered trademarks etc.);...
Further information for the protection rating of the device is contained in the chapter Technical Data VS 3010 BS / SIOX, page 175 1.2 Explanation of 'Safety Instructions and Hazard Warnings' Safety instructions or hazard warnings are composed of four elements: The pictogram (warning sign / symbol) at the edge of the page.
Page 9
Failure to observe the attention symbol can result in personal injury (in extreme cases serious injuries or death) and/or damage to property! Voltage symbol – warns about hazardous electrical voltage KGL Operating Manual – VS 3010 BS 2018-07-02 / 9 178...
Before using the device, check whether it is suitable for your application with regard to its limit values. Before connecting the device, it must be checked whether the power supply is suitable for the device. KGL Operating Manual – VS 3010 BS 2018-07-02...
Note the maximum load of the relay contacts (see chapter Technical Data VS 3010 BS / SIOX, page 175 Contact the supplier in the case of any malfunction. According to experience, transmission of alarms is not yet functional during commissioning (no telephone line laid etc.).
This controller has been designed exclusively for the intended use: The VS 3010 BS controller is designed for use as pack controller in commercial and industrial refrigeration facilities in accordance with the scope of functions and in accordance with the environmental conditions described in this operating manual.
ESD work places with the tools provided for them (earthed soldering irons, earthing wrist strap and similar) conductive ESD bags, conductive plastic containers, IC rods or cartons with conductive foam containers and worktops made of wood, metal, conductive plastics or paper bags. KGL Operating Manual – VS 3010 BS 2018-07-02 13 178...
7 x input / 4..20 mA (0..10 V) - e.g. pressure transducer connection 4 x output / 0..10 V (4..20 mA) - e.g. connection for continuous compressor / condenser control SIOX Supply - power supply for SIOX extension module Interfaces KGL Operating Manual – VS 3010 BS 2018-07-02 15 178...
Page 16
Emergency operation manual-automatic mode selection., page 118 SIOX Supply – power supply Interfaces SIOX IN: connection for data transfer to the base module SIOX OUT: Connection for data transfer to further extension modules KGL Operating Manual – VS 3010 BS 2018-07-02 16 178...
- Fan Cylinder head temperature Low-pressure Compressor high-pressure cutout Minimum suction gas superheat High-pressure (condenser control) Compressor speed controller LP-Z1 / LP-Z2 Liquid level in the collection tank External alarm KGL Operating Manual – VS 3010 BS 2018-07-02 17 178...
Page 18
Burst disk Data archiving Messages Starts Run times / operating hours Utilisation / activity Cascade regulation Regulation of a cascade system with continuous expansion valve(s) Discharge gas defrosting D2D two-pipe system KGL Operating Manual – VS 3010 BS 2018-07-02 18 178...
Put coding switch 2 of the DIP switch S1 in a different position: For details, see chapter VS 3010 BS Installation and start-up, page 84 Switch off controller for 5 seconds and then switch on again. Put coding switch 2 of the DIP switch S1 back in the original position.
4.2 System Configuration The VS 3010 BS pack controller has two low-pressure control loops (LP, compressor control) and a high- pressure control loop (HP, condenser control). Two different temperature zones Z1 and Z2 are provided for the compressor control; see also chapter 2 Functions. The Z1 temperature zone is operated in the NT range and Z2 in the LT range as default.
Page 21
The compressors for both temperature ranges are controlled independently of each other via the suction gas pressure. Layout of a satellite system: Cascade Mode KGL Operating Manual – VS 3010 BS 2018-07-02 21 178...
Configuration of the analogue inputs and outputs, page 90 ). These are preconfigured as 4..20 mA current inputs at the factory. The pressure transducers can be adjusted in menu 3-1-a using the following parameters: KGL Operating Manual – VS 3010 BS 2018-07-02 22 178...
Page 23
- 1 bar (at 4 mA or 0 V) and 7 bar ( at 20 mA or 10 V), the ambient pressure (1 bar) must be added. The input in this example is thus: 0..8 bar. KGL Operating Manual – VS 3010 BS 2018-07-02...
(B) At a pressure greater than the setpoint plus 1.5 times the NZ, the step switching mechanism loads stages independently of the pressure change. (C) In the case of falling pressure that is less than the setpoint plus 1.5 times the NZ and is greater than the KGL Operating Manual – VS 3010 BS 2018-07-02 24 178...
+ 1. The shifting down for step control always starts with the delay of the first stage. The calculation of the control times is identical for both temperature ranges. The variable control time tv = 0 if KGL Operating Manual – VS 3010 BS 2018-07-02 25 178...
Z1/Z2 with the highest operating time is unloaded. The speed-regulated compressor Z1/Z2 is accelerated to a value which corresponds to the capacity with the additional fixed-speed compressor Z1/Z2. KGL Operating Manual – VS 3010 BS 2018-07-02 26 178...
10 V to the maximum frequency. The input signal of the frequency converter must be configured as 0 V..10 V interface. Combined control with capacity-controlled fixed-speed compressors operating mode - parameter M.com.out. KGL Operating Manual – VS 3010 BS 2018-07-02 27 178...
Page 28
(terminals 23/24 and terminals 33/34) are assigned to the FC compressor. These capacity stages that are assigned to the FC compressor are disabled for the operation with a single- KGL Operating Manual – VS 3010 BS 2018-07-02 28 178...
The shifting up or shifting down time restarts in the neutral zone and only runs if the control variable is outside the neutral zone. The shifting up or shifting down time is calculated from the sum of KGL Operating Manual – VS 3010 BS 2018-07-02 29 178...
The calculation of the control times is identical for both temperature ranges. The variable control time tv = 0 if the booster / satellite compressors are controlled directly via the consumers. Consequently, the control time only still consists of the basic time t = tb. 4.4.4 Capacity-controlled compressors KGL Operating Manual – VS 3010 BS 2018-07-02 30 178...
Page 31
Shifting down of compressors The shifting down of compressors is illustrated using the example in the following table: Base module Relay no. terminals 13/14 terminals 23/24 terminals 33/34 terminals 43/44 KGL Operating Manual – VS 3010 BS 2018-07-02 31 178...
Page 32
A speed controlled compressor starts after expiry of the minimum standstill time and runs for the duration of the switch-on delay at the minimum speed. KGL Operating Manual – VS 3010 BS 2018-07-02 32 178...
Base load rotation, page 33 Following completion of the cycle time or when all the compressors are at standstill, compressors that can be KGL Operating Manual – VS 3010 BS 2018-07-02 33 178...
If the pressure drops below a configurable threshold, the compressor is disabled until the pressure exceeds the threshold again. This threshold (t0 Comp. OFF Z2) can be configured in menu 3-4. The monitoring of the starts is not active for KGL Operating Manual – VS 3010 BS 2018-07-02 34 178...
-5 °C, the evaporation pressure regulator (suction gas bypass) opens and lets the suction gas pressure of the Z2 compressors increase. Due to this process, all available Z2 compressors are loaded first during night operation. Z1 compressors KGL Operating Manual – VS 3010 BS 2018-07-02 35 178...
(setpoint shift) for the low-pressure control can be performed using the following operations in menu 3-2-1-2: Room temperature sensor Dependent on requirement from Z1 / Z2 consumer Humidity sensor to-Z1 setpoint shift with cascade regulation KGL Operating Manual – VS 3010 BS 2018-07-02 36 178...
In the case of controllers with electronic expansion valves, the opening degree of the refrigeration point KGL Operating Manual – VS 3010 BS 2018-07-02 37 178...
, see chapter Ambient data for setpoint adjustment, page 75 Depending on the air humidity, a temperature offset, t0-offset is then formed that is added to the t0-setpoint. KGL Operating Manual – VS 3010 BS 2018-07-02 38 178...
CompOFF.w.LdSh Z1/Z2 (menu 3-1) must be set to “Y”. The respective Z1/Z2 parameter is only displayed for capacity-controlled compressors in Z1/Z2. Independent of the load shedding signals, a minimum refrigeration capacity in both the Z2 and Z1 temperature KGL Operating Manual – VS 3010 BS 2018-07-02 39 178...
Page 40
* only for Z1. Only one load shedding stage can be effective for Z2. If the low-pressure control is performed as combined control, the compressor connected to the FC cannot be unloaded using load shedding. KGL Operating Manual – VS 3010 BS 2018-07-02 40 178...
The high-pressure measured via an A/D converter is compared with the setpoint. The following applies: control error = actual value (tc_ACTUAL) - setpoint (tc_SETPOINT) In the case of positive control error and increasing pressure, the step switch shifts up one stage. This means KGL Operating Manual – VS 3010 BS 2018-07-02 41 178...
Fans start one after the other at slow speed (S) and then switch one after the other to the fast speed (F) ↑↓ SSSF Fans start one after the other at slow speed (S) and then all switch simultaneously to the fast speed (F) ↑↓ KGL Operating Manual – VS 3010 BS 2018-07-02 42 178...
Page 43
After this, the slow speeds are unloaded one after the other. The following table shows the control of the fan outputs using the example of a system with three fans and four fan stages: KGL Operating Manual – VS 3010 BS 2018-07-02 43 178...
Min. Fan speed (menu 3-2-2-1), the speed is reduced after a configurable time (parameter basetime OFF Fan 1) to 0 using a ramp and the fan output L1 is switched off. KGL Operating Manual – VS 3010 BS 2018-07-02...
Page 45
(fan output 2) as in the event of tc- max. being exceeded the enable for the speed controller is withdrawn and switched to the bypass stage. KGL Operating Manual – VS 3010 BS 2018-07-02 45 178...
The following diagram shows the speed sequence for starting using the example of a system with five fans: KGL Operating Manual – VS 3010 BS 2018-07-02 46 178...
This is due to the fact that the fan output after the last configured fan output (No.Cond.Stages XX, menu 3-1) is used for the switching to the operation by power supply: KGL Operating Manual – VS 3010 BS 2018-07-02...
Page 48
Afterwards, the first fan is disconnected from the speed controller and activated on the mains power supply. The following diagram shows the speed sequence for starting using the example of a system with five fans: KGL Operating Manual – VS 3010 BS 2018-07-02...
The calculation of the tc setpoint is dependent on the operating mode and is described in detail in the following chapter: Setpoint calculation in normal operation, page 49 Setpoint calculation in HR mode, page 61 4.5.9.1 Setpoint calculation in normal operation KGL Operating Manual – VS 3010 BS 2018-07-02 49 178...
A distinction is made between shifting up and shifting down of the step controller. The variable time is inversely proportional to the control error. In the case of maximum control error, the KGL Operating Manual – VS 3010 BS 2018-07-02...
(menu 3-6) to prevent this seizure. If base load rotation is activated, the following additional entries are displayed on the operating screen: 1. Parameter "On time cond." You can select between 2 operating modes: Fan protection KGL Operating Manual – VS 3010 BS 2018-07-02 51 178...
The cascade is a plate-type heat exchanger between the Z1 and Z2 refrigeration circuits, using which the condensation temperature (high-pressure) of the Z2 circuit is regulated. The cascade can be controlled in two ways: KGL Operating Manual – VS 3010 BS 2018-07-02 52 178...
The cascade can be controlled in two ways: Variant A: Control of the cascade by the VS 3010 BS, page 53 Variant B: Control of the cascade by a case controller, page 60 4.6.1 Control of the cascade by the VS 3010 BS If required the pack controller can be used to control a cascade compressor pack.
The Z2-HP transducer is monitored if it is active. In the event of a measuring loop error, the message ”Meas. error HP Z2" is output. The message priority can be configured. The Z2 high-pressure is measured via a pressure transducer with linear characteristic and 4-20 mA output via KGL Operating Manual – VS 3010 BS 2018-07-02 55 178...
Cooling can be performed during operation with only one expansion valve or in tandem operation with two expansion valves. The setpoint for the temperature regulation (tc-Z2Soll) for the cascade controller is determined according to KGL Operating Manual – VS 3010 BS 2018-07-02 56 178...
If the opening degree is equal to zero, the enable is withdrawn. In order to prevent excessively high relay switching frequency, the enable and the disable signals remain present for at least 35 seconds. KGL Operating Manual – VS 3010 BS 2018-07-02 57 178...
An upper limit for the opening degree output by the cascade controller can be set using this function. This opening degree will never be greater than the maximum value set using the parameter “Maximaler ÖG” (menu 3-2-3). KGL Operating Manual – VS 3010 BS 2018-07-02 58 178...
Cascade regulation is disabled if disabling refrigeration points is active in the Z1 circuit (for function /criteria see chapter Disabling of refrigeration points, page 75 ). The cooling via the cascade is interrupted for as long as the disabling of refrigeration points is active. KGL Operating Manual – VS 3010 BS 2018-07-02 59 178...
If the pressure drops to a level lower than HR max. - HR dif., fan stages are unloaded taking account of the basic and variable unload times. The heat recovery mode is activated via the digital input 22 (terminals 92/93). KGL Operating Manual – VS 3010 BS 2018-07-02...
The shifted tc-setpoint via the external signal is calculated within the limits Min.HR Max.HR 0 V: Min.ht.rec 10 V: HR max. 4.8 Monitoring In addition to control and regulation functions, the following monitoring functions are integrated in the controller: Safety loop KGL Operating Manual – VS 3010 BS 2018-07-02 61 178...
If it is reset, the compressor is enabled. The monitoring of the oil pressure and/or high-pressure monitor can be activated separately for Z1 and Z2 compressors. KGL Operating Manual – VS 3010 BS 2018-07-02...
Freig. Z1/Z2-Verd. cutout. A manual enable must be performed (menu 3-1 The error message generated by the tripping of the motor overload cutout is not cancelled until after the reset KGL Operating Manual – VS 3010 BS 2018-07-02 63 178...
Comp. OFF temp and Comp. ON temp (menu 3-3). If the upper maximum value is exceeded, the associated compressor is switched off and disabled for the KGL Operating Manual – VS 3010 BS 2018-07-02 64 178...
LP type of control has been configured as "combined control" (menu 3-2-1-1 or 3-2-1-2) 4.8.5 Monitoring of the starts The number of compressor switching operations per hour is limited to prevent too high switching frequency of the compressors. KGL Operating Manual – VS 3010 BS 2018-07-02 65 178...
Page 66
Off Time S1. Using the parameter standstill S1 Z1/Z2 (menu 3-3), the time can be set that must elapse before the first stage of the circuit Z1/Z2 can be loaded again after unloading. This prevents cycling of the first compressor stage Z1/Z2 in the event of low partial load. KGL Operating Manual – VS 3010 BS 2018-07-02 66 178...
Min. Superheat Zx threshold for the delay time delay min SH Zx At least one compressor in the respective circuit must be ON (the delay time is reset if no compressor is KGL Operating Manual – VS 3010 BS 2018-07-02 67 178...
The temperature difference can be configure in menu 3-3 Verd.Überwach using the parameter Min to diff. The t0 reduction is deactivated if "--" is entered. The parameter Min to diff is used for the reduction of the setpoints for both Z1 and Z2. KGL Operating Manual – VS 3010 BS 2018-07-02 68 178...
At least 1 compressor remains in operation in each temperature range. The disabling of the compressors starts in the circuit (Z1/Z2) where the most compressors are loaded. KGL Operating Manual – VS 3010 BS 2018-07-02 69 178...
Compressor unload in the event of HP fault during booster / cascade regulation If the Z2 HP transducer is active and there is no fault in the measuring circuit, only Z1 compressor stages are KGL Operating Manual – VS 3010 BS 2018-07-02...
Parameter ”tc OFF Comp Z2” (menu 3-3) only acts on the Z2 circuit if the HP-Z2 transducer is activated (booster operation) Min: Minimum speed FC, parameter “Min. speed” (menu 3-2-1-1) Speed reduction is also active in heat recovery mode. KGL Operating Manual – VS 3010 BS 2018-07-02 71 178...
Configuration Parameter Menu Value Default Unit Description range No.Cond. 0..8 The number of fans in the system configuration (= number of digital inputs for the required motor Stages contactors) KGL Operating Manual – VS 3010 BS 2018-07-02 72 178...
↑↓ Step Type type of control is controller Step controller Combined control - stages Combined control - parallel Time delay Time delay in seconds for External Alarm message 0..250 sec. KGL Operating Manual – VS 3010 BS 2018-07-02 73 178...
Temperature setpoints Z1/ Z2 Neutral Zone Z1/Z2 Control constant Z1/Z2 Control times Z1/Z2 Humidity shift Z1/Z2 The toggle setpoint is performed jointly for the two temperature ranges Z1 and Z2. KGL Operating Manual – VS 3010 BS 2018-07-02 74 178...
This function is only available if the base load rotation of speed controlled compressors and cascade controllers are deactivated The consumer enable is performed for both temperature ranges. KGL Operating Manual – VS 3010 BS 2018-07-02 75 178...
1 hour average values and 24 hour average values. The archiving period differs for each of these archives. After this archiving period has elapsed, the oldest KGL Operating Manual – VS 3010 BS 2018-07-02 76 178...
CAN bus node number for the associated pack controller (see the description of the case controller UA 300 /UA 400). If discharge gas defrosting of the Z2 refrigeration points is performed, Z2 cases and Z2 cold rooms can be KGL Operating Manual – VS 3010 BS 2018-07-02 77 178...
Z2 cold rooms. The actual defrost process begins after expiry of this heating time. The parameter Defrost Z2 specifies the defrost duration of the Z2 cases. The parameter Comp. OFF Z2 KGL Operating Manual – VS 3010 BS 2018-07-02...
NT instead of Z1 and LT instead of Z2 must be selected). Furthermore, each case controller must be provided with the CAN bus node number of the associated pack controller (see operating manuals of the case controllers). KGL Operating Manual – VS 3010 BS 2018-07-02 79 178...
3 Defrost command to Z2/2 cases via CAN bus 4 Toggle setpoint Z1 circuit (no shift) AL 300/CI 3000/CI4000 show an before the t0-Z1 setpoint in the overview 5 Forced cooling of all Z1 cases via CAN bus KGL Operating Manual – VS 3010 BS 2018-07-02 80 178...
5 Forced cooling of all Z2 cases via CAN 6 Disable of the message LP-Z1 5 minutes after opening the suction line measuring loop error KGL Operating Manual – VS 3010 BS 2018-07-02 81 178...
Z2 or disable defrost Z2 cold rooms, the message Disable D2D Z2 or Disable D2D Z2R is registered in the log memory. If there is a serious fault (safety loop), no defrost is initiated. As well as the system fault, the message KGL Operating Manual – VS 3010 BS 2018-07-02 82 178...
Page 83
If there is a serious fault (safety loop), no defrost is initiated. As well as the system fault, the message "Fault D2D Z1" is also registered in the log memory. KGL Operating Manual – VS 3010 BS 2018-07-02 83 178...
If the device is used in any way not specified by Eckelmann AG, the protection supported by the device can be compromised! The system centre, the operator terminal and the PC software LDSWin are used for the configuration of the controller for the start-up and for later changes.
Page 85
/ without discharge gas defrosting Service mode 6 and 7 Firmware update mode For details, see chapter Default settings with S1, page 88 2. CAN bus address selector switch S2 KGL Operating Manual – VS 3010 BS 2018-07-02 85 178...
Wiring of the digital inputs: All digital inputs of the SIOX extension module must be set to 230 V AC for the operation. If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of the control component. KGL Operating Manual – VS 3010 BS 2018-07-02 86 178...
Switch position Pack type Coding switch 3 not used not used A maximum of 12 compressors and 12 fans can be used, see chapter System design VS 3010 BS, page 15 KGL Operating Manual – VS 3010 BS 2018-07-02 88 178...
Page 89
(power failure) of the controller and a first start is performed. After changing the switch positions of both S1 and S2 (address selector switch for CAN bus), the KGL Operating Manual – VS 3010 BS 2018-07-02 89 178...
(terminals 9/10/11/12) For details, see chapter CAN bus, SIOX and Modbus (ebmpapst fans) terminal assignment, page 114 5.2.5 Configuration of the analogue inputs and outputs at the factory KGL Operating Manual – VS 3010 BS 2018-07-02 90 178...
The pack controller is connected to the power cable on the top right terminal block N/L/PE; for further details, see chapter Terminal assignment of the 230 V AC power supply, page 107 KGL Operating Manual – VS 3010 BS 2018-07-02 91 178...
A relay is activated outputs ATTENTION: External voltage can be present at these terminals! LED10 Information for the precise terminal assignment can be found in chapter Pin assignments VS 3010 KGL Operating Manual – VS 3010 BS 2018-07-02 92 178...
AnzVerd.m.LS Z1 and AnzVerd.m.LS Z2 Number of capacity controlled compressors in Z1 and Z2 No. cond.stages Number of condenser capacity stages Menu 3-4 Comp. monitor t0 OFF Comp. Z1 and t0 OFF Comp. Z2 KGL Operating Manual – VS 3010 BS 2018-07-02 93 178...
1 (terminals 13/14). In the case of combined compressor control, the Z2 frequency converter is enabled via the relay output for compressor (x+1) (x = number of Z1 compressor stages). KGL Operating Manual – VS 3010 BS 2018-07-02 94 178...
Page 95
If a fault report is detected via the speed controller / external alarm input when speed control is configured, the message "HP Speed contr" is sent. The external alarm function is not active in this case. KGL Operating Manual – VS 3010 BS 2018-07-02 95 178...
Page 96
The fault report is active when there is no voltage at the "Motor protection fan" (n+1) input, i.e. the FC / speed controller must be configured and connected so that 230 V AC is applied to this pack controller input in the good state. KGL Operating Manual – VS 3010 BS 2018-07-02 96 178...
Page 97
A. For speed-controlled condenser fans The relay output for fan stage 2 (terminals 28/25) is used for bypassing the FC / speed controller for the speed- KGL Operating Manual – VS 3010 BS 2018-07-02 97 178...
Page 98
Number (n) of the digital outputs for fans (F) = 3: Outputs for fan 1 … 3 Digital output for power supply bridging (n+1 = 4): Output fan 4 5. Analogue input for reading the analogue input signal of the FC / speed controller KGL Operating Manual – VS 3010 BS 2018-07-02 98 178...
10 years. If the " battery voltage " message is displayed, the controller must be sent to Eckelmann AG to guarantee correct replacement of the battery. Opening the device is not authorised, see chapter 3010 BS Installation and start-up, page 84 Replacement of the battery after expiry of the warranty is subject to a charge.
If no RS232 interface at the laptop (or PC) available, a RS232 interface must be equipped with the device: Laptop: PCMCIA-COM-Port adapter PC: PCI-COM-Port carte IMPORTANT: A USB-COM-Port adapter is recommended! KGL Operating Manual – VS 3010 BS 2018-07-02 100 178...
Page 101
3. Connect controller (A) to flash cable (B) (both 4-pin plug connectors at the terminal s 5/6/7/8 and 13/14//15 /16). 4. Connect flash cable (B) to null modem cable (C). 5. Connect null modem cable to COM port of the PC. KGL Operating Manual – VS 3010 BS 2018-07-02 101 178...
Page 102
. In Windows Explorer, run the unpacked file by double clicking on it and select the COM port on the screen. The following screen opens: 7. Press Enter (Return) key. The following screen opens: KGL Operating Manual – VS 3010 BS 2018-07-02 102 178...
Page 103
10. Close the screen by pressing the Return key after completion of the firmware update. 11. Set DIP switch S1 coding switches 6 and 7 back to ON, see Default settings with S1, page 88 KGL Operating Manual – VS 3010 BS 2018-07-02 103 178...
Page 104
After changing the switch positions of both S1 and S2, the controller must be disconnected from the power supply for a short time so that the new settings will be adopted! KGL Operating Manual – VS 3010 BS 2018-07-02 104 178...
6 VS 3010 BS connection and terminal assignment The illustrations and tables show the terminal assignments for the pack controller and its SIOX extension modules. A detailed description of the connection and terminal assignment of the controller and its components is shown below.
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and disconnecting, it must be ensured that no voltage is present at all connections of the controller. 6.1.2 Pin assignments for SIOX extension module KGL Operating Manual – VS 3010 BS 2018-07-02 106 178...
Base module in complete design with one SIOX extension module 6.2.1 Terminal assignment of the 230 V AC power supply Connection: Only on base module – terminal block, upper right at the back KGL Operating Manual – VS 3010 BS 2018-07-02 107 178...
6.2.2 Terminal assignment of the digital inputs - 230 V AC Connection: On the base module – terminal block upper right – 23 digital inputs Connection: On the SIOX extension module – terminal block upper right – 12 digital inputs KGL Operating Manual – VS 3010 BS 2018-07-02 108 178...
Connection: On the base module – terminal block upper left – 10 relay outputs Connection : On the SIOX extension module – terminal block upper left – 8 relay outputs Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and KGL Operating Manual – VS 3010 BS 2018-07-02 110 178...
Page 111
For Z2, this means that, e.g. in the case of a compressor configuration Z1 with 4 compressors , the compressor 5 relay contact is used for the enable of the FC compressor Z2. KGL Operating Manual – VS 3010 BS 2018-07-02 111 178...
Cylinder head temperature C4 17, 18 Cylinder head temperature C5 19, 20 Cylinder head temperature C6 21, 22 Cylinder head temperature C7 23, 24 Cylinder head temperature C8 25, 26 Temperature sensor R4.1 KGL Operating Manual – VS 3010 BS 2018-07-02 112 178...
(e.g. pressure transmitter). Furthermore, this will destroy the controller! Malfunctions due to interference! All supply lines from and to the controller (with the exception of the KGL Operating Manual – VS 3010 BS 2018-07-02 113 178...
In the event of any mix-up of the SIOX data cable (RJ45) with an Ethernet network cable with PoE (Power over Ethernet), involved network devices can be damaged! KGL Operating Manual – VS 3010 BS 2018-07-02 114 178...
Complete design of the controller – with the SIOX-D2D extension module for discharge gas defrosting in the last position. 6.2.7.1 D2D - Terminal assignment of the 230 V AC digital inputs Connection: Only on SIOX-D2D KGL Operating Manual – VS 3010 BS 2018-07-02 115 178...
58/59) is used for a safety-critical application, additional measures for monitoring must be taken. 6.2.7.2 D2D - Terminal assignment of the 230 V AC relay outputs Connection: Only on SIOX-D2D KGL Operating Manual – VS 3010 BS 2018-07-02 116 178...
- even if the software does not envisage this , e.g. pump remains on continuously! The Manual OFF and Manual ON positions override the state desired by the software! KGL Operating Manual – VS 3010 BS 2018-07-02 118 178...
HP_Actual X 15.45 b ↓ + Fan capacity stages will be loaded. = No switching of fan capacity stages will be performed. HP_Actual in neutral zone. - Fan capacity stages will be unloaded. KGL Operating Manual – VS 3010 BS 2018-07-02 119 178...
Page 120
T The controller operates with the parameters for daytime operation. N The controller operates with the parameters for night operation. HR The controller operates with the parameters for HR mode. KGL Operating Manual – VS 3010 BS 2018-07-02 120 178...
No operation at the pack controller itself is possible apart from the manual / automatic mode selection (see VS 3010 BS operating modes, page 118 The connection of LDSWin to the system centre (that functions as gateway for the controller) can either be...
Changes and inputs are not possible. However, if any parametrisation is required, the lock-down for the input must be removed first, see Cancelling entry block, page 127 Numbering of menus and screens KGL Operating Manual – VS 3010 BS 2018-07-02 122 178...
Page 123
Each line of this selection list in the display has a digit between 1 and 9 and 0 for menu item 10 with the associated name of the corresponding menu item. The various menu items can be selected directly by tapping KGL Operating Manual – VS 3010 BS 2018-07-02...
Page 124
For fields that enable input of texts, the text input is also possible using the alphanumeric keyboard. Letters are generated by multiple tapping of the digit buttons. To accept the entered value / text, tap the ENTER button ( KGL Operating Manual – VS 3010 BS 2018-07-02 124 178...
Page 125
äöüß0, space character 2ABC 3DEF 4GHI 5JKL 6MNO 7PQRS 8TUV 9WXYZ . _ - Insert space character Upper case and lower case can be toggled by tapping the MODE button. KGL Operating Manual – VS 3010 BS 2018-07-02 125 178...
8.2.2.2 CI 3x00 store computer / AL 300 operator terminal - remote control The main menu of the controller is called in the store computer or operator terminal via the remote control as follows: KGL Operating Manual – VS 3010 BS 2018-07-02 126 178...
The deactivation of the lock is exclusively reserved for service personnel! Before entering values, the entry block must be deactivated. 8.2.3.1 CI 4x00 system centre - login and logout Login to and logout (unlock and lock-down) of the system centre: KGL Operating Manual – VS 3010 BS 2018-07-02 127 178...
1..99) after the time for the service mode has elapsed, the audible warning devices and the alarm relays are activated and the alarms are forwarded using the automatic transmission of alarms. 8.2.4.1 CI 4x00 system centre service mode Activating/deactivating service mode KGL Operating Manual – VS 3010 BS 2018-07-02 128 178...
(1..255 minutes). The service mode is now activated for the duration entered above. Step 4: The service mode can be reset / revoked again by the input of 0 minutes. KGL Operating Manual – VS 3010 BS 2018-07-02 129 178...
CAN bus interface using which the communication with the pack controller takes place. It makes no difference for the operation of the pack controller whether this is done with a system centre, a store computer or an operator terminal; see chapter System design VS 3010 BS, page 15 9.1 Menu tree Main menu...
2 Actual values Continue to menu 2 3 Setpoints Continue to menu 3 4 Clock Continue to menu 4 5 Messages Continue to menu 5 6 Operating data Continue to menu 6 KGL Operating Manual – VS 3010 BS 2018-07-02 131 178...
Ist ND Z2 +/-/= X.XX b Current evaporating pressure Z2 Soll ND Z2 T/N/A X.XX b Evaporating pressure setpoint for comparison Z2 Ist to Z2 +/-/= XX °C Current evaporating temperature Z2 KGL Operating Manual – VS 3010 BS 2018-07-02 132 178...
Page 133
Base module: max. number of total compressor stages: 4 with first SIOX extension module max. number of total compressor stages: 8 Z1 compressors: 1..n compressor stages: 1..max. 3/7, depending on system configuration KGL Operating Manual – VS 3010 BS 2018-07-02 133 178...
Page 134
Compressor 8 motor overload cutout digital input (only displayed if parametrised in the system configuration - menu 3-1) Öldruck Vmax XXX Compressor 8 low oil pressure switch digital input (only displayed if parametrised in the system configuration - menu 3-1) KGL Operating Manual – VS 3010 BS 2018-07-02 134 178...
Page 135
Base load rotation of frequency controlled compressors. Only visible when Z2 base load rotation is activated. Freig.E-Vent.1 Enable of the EE valve 1 of the cascade controller. Only visible when cascade controller is activated. Freig.E-Vent.2 KGL Operating Manual – VS 3010 BS 2018-07-02 135 178...
V 0% Display of currently output expansion valve opening degree 9.1.4 Menu 3 Setpoints SETPOINTS ID: XXXXX 1 System configuration Continue to menu 3-1 2 Regulation Continue to menu 3-2 KGL Operating Manual – VS 3010 BS 2018-07-02 136 178...
Page 137
Mot.sch.Verd.Z1 Enable motor overload cutout YES/NO Motsch.sperr.Z1 Enable motor protection lock YES/NO (only visible if Mot.cutout C. Y Oil/HP fault Z1 Oil pressure difference switch / HP switch compressor YES/NO KGL Operating Manual – VS 3010 BS 2018-07-02 137 178...
Page 138
Pressure for 4 mA / 0 V at the output of the pressure transducer 0..2.0 LP Z2 Max XXX b Pressure for 20 mA / 10 V at the output of the pressure transducer 8..80.0 10.0 KGL Operating Manual – VS 3010 BS 2018-07-02 138 178...
Page 139
Capacity stage 1 ON/OFF Only the available capacity stages (depending on configuration) are displayed. Comp. stage n XXX Capacity stage n ON/OFF Base module: 1 – max. 4 capacity stages KGL Operating Manual – VS 3010 BS 2018-07-02 139 178...
Page 140
3 Cascade regulation * Continue to menu 3-2-3 * The function must be activated in menu 3-1. Menu 3-2-1 LP control LP-Control ID: XXXXX 1 Compressor control Z1 Continue to menu 3-2-1-1 KGL Operating Manual – VS 3010 BS 2018-07-02 140 178...
Page 141
Screen 3-2-1-2-a Type of control Z2 REG Z2 ID: XXXXX Input Default Dim. Step controller √ Selection list LP type of control √ √ Combined control Menu 3-2-1-3 t -adjustment Z1 KGL Operating Manual – VS 3010 BS 2018-07-02 141 178...
Page 142
-setpoint for setpoint shift -50.. °C tr_Min. Z1 XXX °C minimum room temperature for setpoint shift (only visible if t -adjustment via room temperature - -25.. °C screen 3-2-2-a) KGL Operating Manual – VS 3010 BS 2018-07-02 142 178...
Page 143
B. UNLO T C8 XXX s 3..250 sec. Base module: 1 – max. 4 capacity stages with first SIOX extension module: 1 – max. 8 capacity stages Screen 3-2-1-5-d Variable time capacity stage OFF KGL Operating Manual – VS 3010 BS 2018-07-02 143 178...
Page 144
Var. load time F ID: XXXXX Input Default Dim. Vas Load T C1 XXX s Only the available capacity stages are displayed. 0..250 sec. Vas Load T C2 XXX s 3..250 sec. KGL Operating Manual – VS 3010 BS 2018-07-02 144 178...
Page 145
→ Neutral Zone XX K Switching hysteresis for step control 1..10 Control const. XX K Max. control error for variable control times 1..15 Screen 3-2-1-7-a Basic time capacity stage ON KGL Operating Manual – VS 3010 BS 2018-07-02 145 178...
Page 146
-setpoint for setpoint shift -50.. °C tr_Min. Z2 XXX °C minimum room temperature for setpoint shift (only visible if t -adjustment via room temperature - -25.. °C screen 3-2-2-a) KGL Operating Manual – VS 3010 BS 2018-07-02 146 178...
Page 147
B. UNLO T C8 XXX s 3..250 sec. Base module: 1 – max. 4 capacity stages with first SIOX extension module: 1 – max. 8 capacity stages Screen 3-2-1-8-d Variable time capacity stage OFF KGL Operating Manual – VS 3010 BS 2018-07-02 147 178...
Page 148
Selection list of the HP control type √ √ Speed controller Combi-cont.parall Combi-cont.stages Screen 3-2-2-1-a HP control type - star/delta operation Switch mode ID: XXXXX Input Default Dim. Direct √ √ √ KGL Operating Manual – VS 3010 BS 2018-07-02 148 178...
Page 149
3..250 sec. Base module: 1 – max. 4 capacity stages with first SIOX extension module: 1 – max. 8 capacity stages Screen 3-2-2-2-c Basic time for condenser capacity stages OFF KGL Operating Manual – VS 3010 BS 2018-07-02 149 178...
Page 150
0..100.0 Min. Einspr.dauer XXm Injection time of the regulation after restart 0.0..100.0 Min. Maximaler ÖG XXX% Maximum permissible opening degree 20..100 corr.off to Correction offset for pressure losses Z1 0..20 KGL Operating Manual – VS 3010 BS 2018-07-02 150 178...
Page 151
1..30 Min. Menu 3-4 Refrigerant monitoring REFR. MON ID: XXXXX Input Default Dim. Del.low level Time delay for refrigerant low liquid level message ---, 1..120 minutes Menu 3-5 External alarms KGL Operating Manual – VS 3010 BS 2018-07-02 151 178...
Page 153
Setpoint Setpoint Change -, 0.. changed X Max. Drehzahl X Threshold for speed controller exceeded -, 0.. Battery voltage X Internal battery fault -, 0.. Compressor manual control switch OFF KGL Operating Manual – VS 3010 BS 2018-07-02 153 178...
Page 154
Emergency closure of expansion valve(s) due to insufficient superheat -, 0.. SH X Meas. error R4.1 Measuring circuit fault in refrigerant temperature sensor R4.1 -, 0.. Measuring circuit fault in evaporator inlet temperature sensor R5.1 KGL Operating Manual – VS 3010 BS 2018-07-02 154 178...
Page 155
Bas.Load t. Z2 Z2 basic load time during D2D Z1 5..200 sec. Bas.unlo t. Z2 Z2 basic unload time during D2D Z1 5..100 sec. Menu 3-8 D2D Discharge gas defrosting * KGL Operating Manual – VS 3010 BS 2018-07-02 155 178...
Page 156
Discharge gas defrosting for Z1 and Z2 cases / cold rooms ↑, ↓, √ Z2 only √ Discharge gas defrosting for Z2 cases / cold rooms only ↑, ↓, √ √ KGL Operating Manual – VS 3010 BS 2018-07-02 156 178...
Page 157
Defrost timers for Z2 cold rooms for auxiliary and separate defrosting (only visible if ↑, ↓ ----- ----- - XXXXX hh: Auxiliary defrost Separate is selected in screen 3-8-b) Mo-Su Mo-Fr Mo-Sa Sa-Su ----- Mo, Tu, We, Th, Fr, Sa, Su, number KGL Operating Manual – VS 3010 BS 2018-07-02 157 178...
Setpoint ON (only visible if setpoint Mo-Su 00:00 toggle is selected - menu 4) Mo-Fr Mo-Sa 00:00 Sa-Su ----- Mo, Tu, We, Th, Fr, Sa, Su, number dd hh:mm dd hh:mm as above KGL Operating Manual – VS 3010 BS 2018-07-02 158 178...
Default Dim. XXXXX BetrZeit S n+1 Display and input of the total operating times of the Z2 compressors. Only the available Z2 ↑, ↓ Hour XXXX h compressors are displayed. 9999 KGL Operating Manual – VS 3010 BS 2018-07-02 159 178...
Page 160
Screen 6-4-1-a Run time Z1 RUN TIMES Z1 ID: Default Dim. XXXXX Lst.Stufe 1 hh:mm Daily run time of the Z1 compressor stages. Only the actual number of compressor stages is 00:00 hour: displayed. KGL Operating Manual – VS 3010 BS 2018-07-02 160 178...
Page 161
XXXXX Lst.Stufe 1 hh:mm Daily run time of the Z1 compressor stages - night. Only the actual number of compressor stages is 00:00 hour: displayed. Lst.Stufe n hh:mm 00:00 hour: KGL Operating Manual – VS 3010 BS 2018-07-02 161 178...
Page 162
Z2 compressors: n+1..max. compressor stages: 2..max. 4/8, depending on system configuration Number of Z1 compressor stages + number of Z2 compressor stages = max. 4/8 total compressor stages Menu 6-4-6 Compressor starts Z1 night KGL Operating Manual – VS 3010 BS 2018-07-02 162 178...
Page 163
Continue to menu 6-4-1 2 Run times -day Continue to menu 6-4-2 3 Run times -night Continue to menu 6-4-3 4 Starts Continue to menu 6-4-4 5 Starts -day Continue to menu 6-4-5 KGL Operating Manual – VS 3010 BS 2018-07-02 163 178...
Page 164
Base module: max. number of total compressor stages: 4 with first SIOX extension module max. number of total compressor stages: 8 Z1 compressors: 1..n compressor stages: 1..max. 3/7, depending on system configuration KGL Operating Manual – VS 3010 BS 2018-07-02 164 178...
Page 165
Z2 compressors: n+1..max. compressor stages: 2..max. 4/8, depending on system configuration Number of Z1 compressor stages + number of Z2 compressor stages = max. 4/8 total compressor stages Menu 6-5-5 Compressor starts Z2 day KGL Operating Manual – VS 3010 BS 2018-07-02 165 178...
Page 166
Input Date: dd/mm/yy Date Activity Z2 XXX % Activity Z2 in % ↓, ↑, ESC ↓ Selection max. 31 days in the past using ↑↓ Menu 6-5-8 Activity Z2 day KGL Operating Manual – VS 3010 BS 2018-07-02 166 178...
AnalogOut3 X.XX V Voltage at the analogue output 3 (terminals 57, 58) 0.0..10.0 AnalogOut4 X.XX V Voltage at the analogue output 4 (terminals 63, 64) 0.0..10.0 Menu 8-2 Compressor Z1 defaults ON/OFF KGL Operating Manual – VS 3010 BS 2018-07-02 167 178...
Page 168
↑, ↓ (ON/OFF) Suct.line Z2 XXX Digital output Suction line Z2 ON or OFF ↑, ↓ (ON/OFF) Discharge Z2 Discharge Z2 XXX Digital output ON or OFF ↑, ↓ (ON/OFF) KGL Operating Manual – VS 3010 BS 2018-07-02 168 178...
Page 169
↑, ↓ (ON/OFF) Suct. line Z1 XXX Digital output Suction line Z1 ON or OFF ↑, ↓ (ON/OFF) Discharge Z1 XXX Digital output Discharge Z1 ON or OFF ↑, ↓ (ON/OFF) KGL Operating Manual – VS 3010 BS 2018-07-02 169 178...
Our scope of delivery is exclusively intended as a component for further processing. As a consequence of this fact, Eckelmann AG does not undertake any measures for the taking back or municipal disposal of this product as it is not supplied directly to the free market.
11 Alarms and messages VS 3010 BS 11.1 Message system A number of messages are recognised by the system and stored with date, time and the priority in the internal Received / sent messages log memory of the system. are stored in the log memory. The time resolution is one minute.
Z2 compressor x motor overload cutout tripped 152 Mot. cutout Z1 Cx Z1 compressor x motor overload cutout tripped 153 Mot. cutout fan.x Condenser fan x motor overload cutout tripped KGL Operating Manual – VS 3010 BS 2018-07-02 172 178...
Page 173
203 Sens. type change A parameter for calibration of the pressure transducers has been changed Z1 compressor stage x has been automatically disabled (5x cylinder temperature too high per day) KGL Operating Manual – VS 3010 BS 2018-07-02 173 178...
Page 174
Only for compressor combined control: Motor overload cutout FC compressor Z1 or frequency converter Z1 fault 249 Mot.cutout / FC-Z2 Only for compressor combined control: Motor overload cutout FC compressor Z2 or frequency converter Z2 fault KGL Operating Manual – VS 3010 BS 2018-07-02 174 178...
12 Technical Data VS 3010 BS / SIOX 12.1 Electrical Data VS 3010 BS / SIOX Warning about dangerous electrical voltage! Danger to life - Danger of electric shock! Overvoltage category III (test voltage 4.0 kV) / contamination degree 2: All connections of the device...
Page 176
Official Journal of the EU L96, 29/03/2014, pages 357-374 EMC Directive 2014/30/EU; Official Journal of the EU L96, 29/03/2014, pages 79-106 RoHS Directive 2011/65/EU; Official Journal of the EU L174, 01/07/2011, pages 88-110 KGL Operating Manual – VS 3010 BS 2018-07-02 176 178...
Base module with manual control switch, all dimensions in mm. 12.3 Mechanical Data SIOX Extension Module With manual control switch SIOX extension module with manual control switch, all dimensions in mm. KGL Operating Manual – VS 3010 BS 2018-07-02 177 178...
13 Part numbers and accessories VS 3010 BS Visit our E*LDS Shop: More information at https://ldsshop.eckelmann.de 13.1 Pack controller VS 3010 BS / SIOX extension module Type Description Part number VS 3010 BS VS 3010 BS pack controller LIVS301012 SIOX...