Page 1
MIURA CONNECT INSTALLATION MANUAL INFORMATION IN THIS MANUAL MAY BE CHANGED WITHOUT ANY NOTICE. Please ensure that installation manual is read and observed in full by all persons working with the product. Please also ensure that it is stored in a location where it may be easily accessed by said persons.
Page 2
Document No.: EN-MN-006-01-iii This Installation Manual explains the transport and installation of Miura Connect. Carefully read this Installation Manual and understand the contents before installing. Particularly important points are denoted as DANGER, WARNING, CAUTION, and NOTE in descending order of severity.
Page 3
NOTE (1) Product Installation Ensure that installation work is carried out correctly as set forth in the applicable MIURA Installation Manual. Furthermore, anybody who will work with the product should carefully study the content of the Operation Manual in advance and ensure that it is fully understood.
When installing the equipment and performing the instrumentation work, take due care of the following precautions. 1. When performing the grounding work, connect the ground wire to the ground terminal inside the panel. Use wire with a diameter equal to or larger than the power supply wire (AWG-14).
EN-021A, network hub with optical port and DS-NET to M-NET3 converter There must be an open port within the M-NET3 network for connection to the Miura Connect panel. If there are no open ports, an EN-type expansion panel should be ordered.
Document No.: EN-MN-006-01-iii 2.2. Specifications Communication wire standard Category 5 shielded cable or better with RJ45 connector Maximum connection distance 330’ (100 m) Operating temperature 32F–120F Operating humidity 30–85% (no condensation and freezing) Power supply 120 VAC, 50/60 Hz, single-phase Power consumption 600 VA (max.) Full load current...
Document No.: EN-MN-006-01-iii 2.3. Internal System Configuration A. 120VAC and ground landing terminals B. 24VDC power supply C. Industrial PC D. Antenna E. Exhaust fan F. Component fuses, 24VDC and common terminals G. EV-11 H. PLC PLC terminals J. Filter Page 8 of 21...
Document No.: EN-MN-006-01-iii 3. Mounting the Panel CAUTION Observe the following precautions about installation and ensure that the product is installed in an appropriate location. Installation in an inappropriate location may result in equipment failure. CAUTION Do not directly weld the box onto a column or wall. The product contains electrical equipment that may be damaged by the effects of arc welding.
Document No.: EN-MN-006-01-iii 3.2. Installation Procedures • Utilize the existing anchor holes in the back of the panel to affix the equipment to a wall, etc. • Ensure the anchor location can withstand the load 4. Field Wiring 4.1. Wiring Power Supply and Installing Ground Fault Circuit Breaker •...
2.4/5GHz correct ports. The connectors within a pair are identical and can connect to the corresponding ports on the gateway in any order. Male and Female Connectors Page 11 of 21...
Thermocouple type is set as K by default. Consult the factory if an alternate type is desired. 4.5. (Optional) PLC – Discrete Inputs (dry contacts) • Connect external dry contacts as shown between 24VDC and Zip-Link terminals while referencing the terminal labels 24VDC...
Connect analog inputs to the Zip-Link terminals while referencing the terminal labels • 2 and 3-wire devices should be powered from the Miura Connect panel’s 24VDC supply • Devices must be scaled correctly within the PLC program. Consult the factory for support...
Document No.: EN-MN-006-01-iii 4.7. (Optional) PLC – Analog Input – Yokogawa Pressure Transducer Input • Follow the diagram below when connecting the Yokogawa pressure transducer • Device must be scaled correctly within the PLC program. Consult the factory for support Page 14 of 21...
Document No.: EN-MN-006-01-iii 4.8. (Optional) PLC – Analog Input – Johnson Controls Pressure Transducer Input • Follow the diagram below when connecting the Johnson Controls pressure transducer • Device must be scaled correctly within the PLC program. Consult the factory for support shield black White...
Document No.: EN-MN-006-01-iii 5. Device Settings The following settings must be made for Miura Connect to function properly. Do not adjust settings while equipment is powered 5.1. EV-11 COM Settings (board inside Miura Connect panel) • Confirm function switch 1 is set to ON and network ID is set to 95 or similar, unused ID number •...
Document No.: EN-MN-006-01-iii 6. Modbus TCP Output (Optional) • The Miura Connect PC functions as a Modbus slave and can output all collected data via LAN 2 port • Default settings are: 10.0.0.102 Gateway: 10.0.0.1 Netmask: 255.255.255.0 • See the following pages for instructions on changing these settings •...
The gateway will now have the new Modbus settings upon reboot 7.4. Connect to a Wi-Fi Network at Startup • To connect to a Wi-Fi network in the field you may follow these steps directly or submit a request to miuraconnect@miuraz.com for support With Miura support •...
Disconnect from the PLC by choosing “Offline” On your own • Follow similar steps as above to connect to the PLC from the software, but in this case, you want to read the existing program from the PLC so it can be modified •...
Document No.: EN-MN-006-01-iii 8. Serial Number Explanations Panel Serial Number – labeled during panel production: MC-101-##-YYMMDD Note: 101 indicates panel design version and will change over time PLC Serial Number – programed by Engineering to match panel serial number: MC-PLC-##-YYMMDD Gateway Client ID –...