Section 1. Introduction
EntelliGuard G short circuit & interrupting ratings
ANSI/UL1066
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
Type
240V
480V
600V
N
65,000
65,000
65,000
H
85,000
85,000
65,000
E
85,000
85,000
85,000
M
100,000 100,000 85,000
B
100,000 100,000 100,000 100,000
L
150,000 150,000 100,000 100,000
UL489
Interrupting Rating Tier UL489 Devices, ICCB
Type 240V
480V
600V
N
65,000
65,000
65,000
H
85,000
85,000
65,000
M
100,000
100,000
85,000
L
150,000
150,000
100,000
Non-Automatic Circuit Breaker – ANSI Version
Rated
Envelope
Type Amps
Interrupting
Current
1
N
800
42
1
N
1600
42
1
N
2000
42
2
H
3200
65
3
L
4000
100
3
L
5000
100
NOTE: GE internal quality testing requirements exceeded 20,000 mechanical operations.
Non-Automatic Circuit Breaker/Molded Case Switch – UL Version
Short
Envelope
Type Amps
Interrupting
Current
1
N
800
42
N
1
1600
42
1
N
2000
42
2
H
3000
65
3
L
4000
100
3
L
5000
100
3
L
6000
100
NOTE: GE internal quality testing requirements exceeded 20,000 mechanical operations.
Type E = Sq. Rated (ICW = ICU) 400-2000A, 85kAIC @ 480/508V
Type B = Sq. Rated (ICW = ICU) 3200-6000A, 100kAIC @ 480/508V
Type N = 65kAIC @ 480/508/600/635V
Type H = 85kAIC @ 480/508V, 65kAIC @ 600/635V
Type M = 100kAIC @ 480/508V, 85kAIC @ 600/635V
Type L = 150kAIC @ 480/508V, 100kAIC @ 600/635V
2
Courtesy of NationalSwitchgear.com
Envelope 1 Envelope 2
1/2S Withstand 400-2000
65,000
X
65,000
X
85,000
85,000
Envelope 1 Envelope 2
1/2S Withstand 400-2000
42,000
X
50,000
X
65,000
85,000
Rated Endurance
Minimum Mechanical
Minimum Electrical
Endurance
Endurance at 480V
12,500
10,000
12,500
10,000
12,500
7,500
5,000
5,000
5,000
3,000
5,000
2,000
Rated Endurance
Minimum Mechanical
Minimum Electrical
Endurance
Endurance at 480V
12,500
10,000
12,500
10,000
12,500
7,500
5,000
5,000
5,000
3,000
5,000
3,000
5,000
2,000
Envelope 3
3200
400-3200 3200
4000-5000
X
X
X
X
X
Envelope 3
2500-3000 400-3000 3000
X
X
X
X
Minimum Electrical
Endurance at 600V
7,500
7,500
5,000
5,000
2,000
1,500
Minimum Electrical
Endurance at 600V
7,500
7,500
5,000
5,000
2,000
1,500
1,000
X
X
X
4000
5000-6000
X
X
X

Hide quick links: