• Schneider Electric Conext branded devices communicate over Xanbus, forming a
Closed-Loop configuration using the Xanbus Port on the AES battery, and do not
require the LYNK II Communication Gateway (p/n 950-0025). For instructions on using
Xanbus, refer to Application Note 885-0013 Closed-Loop Integration with Xanbus
Enabled Schneider Electric Conext Products.
9.8.3 Network Installation
Networking Guidelines:
• Separate data and power cables. Allow for separation between data and power
cables. Avoid data interference caused by running network cables bundled with
power cables.
• Allow for AEbus (LYNK) Network cable slack. Ensure that AEbus (LYNK) Network
cables are slack and not in tension.
• Isolate the AEbus (LYNK) Network. Do not mix other networks with the AEbus
(LYNK) Network.
• Mixing the AEbus (LYNK) Network with other networks may result in equipment
malfunction and damage.
9.8.4 Installation Procedure
1. Before beginning a network installation, mount the devices according to their
instructions.
2. Attach a CAT5 cable to the AEbus (LYNK) Port on a battery.
3. Connect the other end of the CAT5 cable to the AEbus (LYNK) Port of the
following battery.
4. Repeat until all batteries are connected.
5. Add a terminator to the last battery in the AEbus (LYNK) Network.
6. Network with other devices and accessories as needed.
9.8.5 Testing and Verification of the AEbus Network
Perform network verification with the 950-0025 LYNK II Communication Gateway.
• If the LYNK II Network Bus indication LED is illuminated, power and
communication for the AEbus (LYNK) Network are active.
• Use LYNK ACCESS software through a computer to confirm the number of
batteries in the AEbus (LYNK) Network.
NOTE
NOTICE