9.8 AEbus (LYNK) Network

9.8.1 Network Layout
AES batteries use the AEbus (LYNK) Network to coordinate voltage, temperature,
and current data. Network terminators are required for the AEbus (LYNK) Network
to function properly.
Terminate AEBus
Connector
COM1
Battery
Figure 8. Batteries connected to AEbus (LYNK) Network
9.8.2 Configuration with Power Conversion and Monitoring Devices
Set up AES batteries to work with Power Conversion and Monitoring devices in
either an Open-Loop or Closed-Loop configuration. Set up the charge and discharge
settings in an Open-Loop configuration through the Power Conversion device's
controller at the time of installation. In a Closed-Loop configuration, the BMS of the
AES Battery dynamically controls charge and discharge settings over a connection
with the Power Conversion device. Closed-Loop communication on a Power
Conversion device network requires using the LYNK II Communication Gateway
(p/n 950-0025) available from Discover Battery.
For information on Closed-Loop and Open-Loop configuration with a Power
Conversion device, refer to the appropriate Application Note for your Power
Conversion device, available from the website www.discoverbattery.com, or contact
your Discover Battery provider for assistance.