Calibration of Pressure Input
In order to calibrate the pressure input apply the proper pressure to the sensor
to be calibrated.
References given in psi / mmH
• 250 mmH
• 1 psi Sensor
• 5 psi Sensor
DCY - 2057 Pressure Controller
O Sensor
2
Reference
0.00 mmH
O
2
50.00 mmH
O
2
100.00 mmH
O
2
150.00 mmH
O
2
200.00 mmH
O
2
250.00 mmH
O
2
Reference
0.0000 psi
0.2000 psi
0.4000 psi
0.6000 psi
0.8000 psi
1.0000 psi
Reference
0.0000 psi
1.0000 psi
2.0000 psi
3.0000 psi
4.0000 psi
5.0000 psi
O are listed below for each type of sensor.
2
Mnemonic
0 mmH
50 mmH
100 mmH
150 mmH
200 mmH
250 mmH
Mnemonic
0psi
0.2psi
0.4psi
0.6psi
0.8psi
1.0psi
Mnemonic
0psi
1psi
2psi
3psi
4psi
5psi
O
2
O
2
O
2
O
2
O
2
O
2
Maintenance
Page 58