Page 1
R410A Commercial Air Conditioners Service Manual Series...
Page 2
CHV Mini VRF 50/60Hz CONTENTS Part 1 General Information ................. 3 Part 2 Outdoor Units ……………………..............12 Part 3 Installation ....................65 Part 4 Troubleshooting ..................81 201908...
CHV Mini VRF 50/60Hz Part 1 General Information Indoor and Outdoor Unit Capacities ............4 External Appearance................5 Nomenclature…………………..............7 Combination Ratio................. 7 Features……………................... 8 201908...
CHV Mini VRF 50/60Hz 1. Indoor and Outdoor Unit Capacities 1.1 Indoor Units Table 1-1.1: Standard indoor unit abbreviation codes Abbreviation Abbreviation Type Type code code One-way Cassette Wall-mounted Two-way Cassette Floor & Ceiling Compact four-way Cassette Low ESP Short Ducted Four-way Cassette Medium ESP Ducted Round-flow Cassette...
Cooling Capacity ( 100W ) × Side Discharge Outdoor Unit All DC Inverter Chigo VRF 4. Combination Ratio Sum of capacity indexes of the indoor units Combination ratio = Capacity index of the outdoor units Table 1-4.1: Indoor and outdoor unit combination ratio limitations...
9 zones with one outdoor unit. Such as villa, restaurant, school etc. Chigo offers various indoor units, more than 100 models of 11 types. Capacity ranges are from 2.2kW to 16kW. It is all compliance with residential and light commercial place. Our systems can be operated up to 130% of capacity which allows any system to be designed to the customers’...
Page 10
CHV Mini VRF 50/60Hz 5.2 High efficient DC inverter compressor All DC inverter Mini VRF adopts highly intelligent inverter-driven compressor. This advanced technology enables the output of the outdoor unit to be modulated by the real heat load demands. This advanced system ensures precise temperature regulation and highly efficient energy usage, making a significant contribution to the limiting the impact on the environment.
Page 11
CHV Mini VRF 50/60Hz 5.6 Wide operation temperature range No matter in extremely cold winter when outdoor temperature gets as low as -15°C or in hot summer when temperature is up to 55°C, the Mini VRF system will keep stable performance. 5.7 Flexible piping design Table 1-5.1: Piping parameters Piping Length...
Page 12
CHV Mini VRF 50/60Hz 5.10 Smart electronic control design The radiation fin is made of aluminum panels fitting together seamlessly. This helps to cool down the IPM, it has better performance compared to air cooling for PCB. With PFC(Power Factor Corrector) module, the power utilization rate is increased, the power factor is capable to be 98%, lead to higher efficiency.
CHV Mini VRF 50/60Hz 3. Service Space 3.1 Single unit installation Air inlet >300 Air inlet >600 Air outlet 3.2 Parallel connect the two units or above 201908...
CHV Mini VRF 50/60Hz 4. Piping Diagrams Electronic Evaporator expansion valve High pressure Electronic switch expansion valve Condensor Oil seperator Oil return capilary Compressor pressure pressure switch liquid accumulator can Oil separator: It is used to separate oil from high pressure & temperature gas refrigerant that is pumped out from compressor.
CHV Mini VRF 50/60Hz 6. Field Wiring If needed, the user can purchase a centralized controller, as shown in the dashed box. For the specific method of installation, please contact your local supplier. Power supply Power supply Switch / power supply Switch / power supply Junctionbox Power line of outdoorunit...
Page 48
CHV Mini VRF 50/60Hz 7.2 Heating CHV-DH080W/R1 TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor) Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5...
Page 49
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -9.1 -7.6 100% -5.6 -3.7 -0.7 10.4 10.5 10.5 10.5 11.8 10.5 13.7 10.5 -19.8...
Page 50
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -9.1 -7.6 -5.6 -3.7 -0.7 11.8 13.7 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5...
Page 51
CHV Mini VRF 50/60Hz CHV-DH100W/R1 TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor) Outdoor Air Indoor temperature(°C WB) Combination temperature (%) (Capacity (°C DB) index) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -9.1...
Page 52
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -9.1 -7.6 100% -5.6 10.0 10.0 10.0 10.0 10.0 -3.7 10.5 10.5 10.5 10.5 10.5...
Page 53
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination temperature (%) (Capacity (°C DB) index) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -9.1 -7.6 -5.6 -3.7 -0.7 11.8 13.7 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5...
Page 54
CHV Mini VRF 50/60Hz CHV-DH125W/R1 TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor) Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 10.0 -11.8 10.4 10.4 10.3...
Page 55
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 10.2 10.2 10.2 10.2 10.2 10.1 -9.8 10.7 10.7 10.7 10.7 10.6 10.6 -9.5 11.0 10.9 10.9 10.9...
Page 56
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination temperature (%) (Capacity (°C DB) index) °C DB °C WB -19.8 -18.8 -16.7 -13.7 -11.8 10.1 10.1 -9.8 10.6 10.4 -9.5 10.8 10.4 -8.5 -9.1 11.0 10.4 -7.6 11.0 10.4 -5.6 11.0 10.4...
Page 57
CHV Mini VRF 50/60Hz CHV-DH140W/R1 TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor) Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 10.4 10.3 10.3 10.3 10.2 10.2 -18.8 10.5...
Page 58
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 10.2 10.2 10.2 10.1 10.1 10.1 -18.8 10.4 10.4 10.3 10.3 10.3 10.3 -16.7 10.8 10.7 10.7 10.7 10.7 10.7 -13.7 11.2...
Page 59
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 10.0 10.0 10.0 10.0 10.0 -18.8 10.2 10.2 10.1 10.1 10.1 -16.7 10.6 10.6 10.5 10.5 10.4 -13.7 11.0 11.0 11.0 10.8...
Page 60
CHV Mini VRF 50/60Hz CHV-DH160W/R1 TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor) Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 12.0 11.9 11.9 11.9 11.8 11.8 -18.8 12.2...
Page 61
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 11.8 11.7 11.7 11.7 11.7 11.6 -18.8 12.0 12.0 11.9 11.9 11.9 11.9 -16.7 12.4 12.4 12.4 12.3 12.3 12.3 -13.7 13.0...
Page 62
CHV Mini VRF 50/60Hz Outdoor Air Indoor temperature(°C WB) Combination (%) temperature (Capacity index) (°C DB) °C DB °C WB -19.8 11.6 11.5 11.5 11.5 11.5 11.3 -18.8 11.8 11.8 11.7 11.7 11.7 11.3 -16.7 12.2 12.2 12.2 12.2 12.1 11.3 -13.7 12.8...
CHV Mini VRF 50/60Hz 8. Electric Characteristics Power Line Signal Wire between Indoor and Capacity (kW) Power Supply Breaker/Fuse (A) (mm2) Outdoor Units (mm) 8/10 220-240V 50Hz/60Hz 3×4.0 40/30 three-core shielded cable 3×1.0 12.5/14/16 220-240V 50Hz/60Hz 3×6.0 63/45 201908...
CHV Mini VRF 50/60Hz 1. Precautions 1.1 This air conditioner is a comfortable unit. Don't use it in some special places for machine rooms, precise instruments, foods, plants, animals, artworks, etc. (1) The installation shall be done by the distributor or the professional staff. The installation staff must have related professional knowledge.
CHV Mini VRF 50/60Hz 2. Outdoor Unit Installation 2.1 Installation space selection (1) Install the outdoor unit at a place where discharge air is not blocked. When an outdoor unit is installed in a place that is always exposed. There also should be enough space for installation and maintenance. (2) To a strong wind like a coast or on the high store of a building, secure a normal fan operation by using a duct or a wind shield.
CHV Mini VRF 50/60Hz 3. Piping Installation 3.1 Piping connection (1) Flaring Use a pipe cutter to cut the refrigerant pipe and a pipe expander to flare A(mm) Outer Diameter Burr Rough Maximum Minimum (mm) Inclined Φ6.35 Φ9.52 12.4 12.0 Φ12.7 15.8 15.4...
Page 70
CHV Mini VRF 50/60Hz (1) Connecting mode I First distributor (2) Connecting mode II (28) (28) (28) First distributor (28) (22) (28) 3.3 Determination of main pipe (L1) diameter Pipe Dimension of Main Pipe (mm) ≥30m <30m Capacity of Outdoor Unit (kW) First distributor Liquid pipe Gas pipe...
Page 71
CHV Mini VRF 50/60Hz CHV Mini VRF 50/60Hz 3.4 Determination of main pipe (L2-L5) diameter Length of Downstream Equivalent Pipe Capacity of Downstream Indoor Unit Dimension of main pipe of indoor unit (kW) Applicable to distributor Liquid pipe Gas pipe W<6.5 Φ9.52 Φ12.7...
Page 72
CHV Mini VRF 50/60Hz (2) Connecting mode II Equivalent length to the nearest distributor Equivalent length to the farthest pipe of the indoor unit Equivalent length to the farthest pipe of the first distributor First distributor +a+b+c+d+e+f Total Pipe Length ≤100m Actual length ≤60m...
Page 73
CHV Mini VRF 50/60Hz 3.6 Installation of distributor (1) The distributor shall use U-type or Y-type, instead of T-type. (2) The distributor shall be installed horizontally, with the deviation angle of no greater than ± 10℃. (3) The distributor cannot be turned directly, with the straight pipe of no less than 0.8m. Direction A Direction B >0.8m...
Page 74
CHV Mini VRF 50/60Hz High pressure liquid pipe Low pressure gas pipe Outdoor unit (set) Oil return bend Indoor unit set 3.8 Remove Dirt or Water in the Piping Make sure there is no any dirt or water before connecting the piping to the outdoor units. Wash the piping with high pressure nitrogen, never use refrigerant of outdoor unit.
Page 75
CHV Mini VRF 50/60Hz Connect the vacuum pump Run the vacuum pump (above 2 hours) 1. Close the valve of the pressure After dropping up to -0.1MPa, the vacuum pump keeps on gauge; running for 20-60minutes. 2. Disconnect the pressure gauge and the vacuum pump;...
Page 76
CHV Mini VRF 50/60Hz 3.14 Stop valve instructions (1) It is closed when leaving the factory, open the valve counterclockwise or close the valve clockwise with a 6mm socket head wrench. (2) After completing the operation, tighten the valve cover. (3) R410A special tool shall be used to vacuumize the valve and fill the refrigerant at the service entrance.
CHV Mini VRF 50/60Hz 4. Electric Wiring Installations 4.1 Outdoor unit wiring Power Line Signal Wire between Indoor and Outdoor Capacity (kW) Power Supply Breaker/Fuse (A) (mm2) Units (mm) 8/10 220-240V 50Hz/60Hz 3×4.0 40/30 three-core shielded cable 3×1.0 12.5/14/16 220-240V 50Hz/60Hz 3×6.0 63/45 Power supply...
Page 78
CHV Mini VRF 50/60Hz 4.2 Indoor unit power supply wiring Indoor power supply Current leakage protection Manual switch Junction box Indoor unit When the power wire is parallel to the signal wire, please put the electrical wires into their own wire pipes, with proper wire spacing (10A or below: 300mm, 50A or below: 500mm).
CHV Mini VRF 50/60Hz 5. Test Running 5.1 Inspection and confirmation before debugging (1) Check and make sure the refrigerating pipeline and communication line connecting with the indoor and outdoor units are connected with the same refrigerating system. Otherwise, some running faults occur. (2) The power supply voltage is within the rated voltage of ±10%.
CHV Mini VRF 50/60Hz 6. Precautions on Refrigerant Leakage 6.1 Inspection and confirmation before debugging (1) The refrigerant of the air conditioner is harmless and nonflammable. (2) The room for the air conditioner shall have an appropriate space. In case of refrigerant leak, it cannot go beyond the critical concentration.
Page 81
CHV Mini VRF 50/60Hz (5) Measures against exceeding the critical concentration. a). To reduce the refrigerant concentration below the critical concentration, install a mechanical ventilation device (for frequent ventilation). b). If frequent ventilation cannot be performed, please install a leak warning device interlinked with the mechanical ventilation device.
Page 84
CHV Mini VRF 50/60Hz Part name Quantity Part name Quantity Top cover cotton component Seat plate sealing cover Condenser part Seat plate Condenser assembly Right side panel Condenser gas collection component Four-way valve component Condenser splitter assembly High pressure valve component Condenser supercooled outlet Solenoid valve component Top beam...
CHV Mini VRF 50/60Hz 3. Dialing Setting 3.1 Silent mode choosing by SW5 dialing definition Dialing Silent Mode Standard Mode (Factory default) Strong Silent Mode Night Silent Mode High Static Pressure Mode 3.2 Night time choosing by SW5 dialing definition Dialing Night Time 6/10...
Page 88
CHV Mini VRF 50/60Hz 3.4 Define outdoor unit capacity by SW4 dialing The number you dial means the capacity of outdoor unit selected Dialing Capacity 10kW 12.5kW 14kW 16kW 3.5 Inspection Instructions of Outdoor Unit for CHV* Series R e m a r k s Display contens Remarks Current frequency / number of indoor units...
CHV Mini VRF 50/60Hz 4. Error Code Table Fault Code Fault Contents Remark Outdoor unit phase-sequence fault Communication fault between the indoor unit and the outdoor unit 20-minute break at first or 2-minute break later T4 outdoor air temperature sensor fault T3 Condenser pipe temperature sensor fault (outlet) T5 Exhaust temperature sensor fault AC over-voltage / under-voltage protection...
CHV Mini VRF 50/60Hz 5. Troubleshooting 5.1 Warning Warning All electrical work must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations and other legislation that apply in a given situation).
Page 91
CHV Mini VRF 50/60Hz 5.2 E1: Outdoor unit phase-sequence fault 5.3 E2: Communication fault between the indoor unit and the outdoor unit 201908...
Page 92
CHV Mini VRF 50/60Hz 5.4 E4: T4 outdoor air temperature sensor fault 5.5 E6: T3 Condenser pipe temperature sensor fault (outlet) 201908...
Page 93
CHV Mini VRF 50/60Hz 5.6 E8: T5 Exhaust temperature sensor fault Check if the T5 exhaust temperature sensor Connect it well connector is loose Pull out the exhaust temperature sensor If multimeter displays 0Ω or OL plug and measure the resistance Replace the sensor Normal resistance: 50K Replace outdoor main PCB...
Page 94
CHV Mini VRF 50/60Hz Check the voltage between A-N Contact the power supply Judge whether the input voltage is lower than 172V department Check if the transformer has a normal output of about 4.5V AC If lower, replace the voltage main PCB Check if the half-wave rectified voltage ((1.414 ÷...
Page 95
CHV Mini VRF 50/60Hz 5.9 EA: T3B condenser temperature sensor fault (middle) Check if the T3B sensor connector is loose Connect the sensor well Pull out the T3B sensor plug and measure the resistance The outdoor ambient temperature is between 0°C normal Replace the main PCB and 40°C, and the resistance is between 13KΩ...
Page 96
CHV Mini VRF 50/60Hz 5.11 EC: T7 refrigerant cooling pipe inlet temperature sensor fault Check if the T7 sensor connector is loose Connect the sensor well Pull out the T7 sensor plug and measure the resistance The outdoor ambient temperature is between 0°C normal Replace the main PCB and 40°C, and the resistance is between 13KΩ...
Page 97
CHV Mini VRF 50/60Hz 5.13 H0: Communication fault of master board and driver chip 5.14 H4: Display P6(IPM module protection) for 3 times within 30 minutes 201908...
Page 98
CHV Mini VRF 50/60Hz 5.15 H5: Display P2 (system pressure is too low) protection for 3 times within 30 minutes 5.16 H6: Display P4 (T5 Exhaust temperature is too high ) protection for 3 times within 100 minutes 201908...
Page 99
CHV Mini VRF 50/60Hz 5.17 H7: The decrease in number of indoor unit 5.18 H9: Display P9 (AC fan fault ) protection for 2 times within 10 minutes 201908...
Page 100
CHV Mini VRF 50/60Hz 5.19 H10: Display P3(inverter over current protection) protection for 3 times within 60 minutes 5.20 H11: Display P13 protection for 2 times within 10 minutes Check if the plug of the transformer inserted into Connect it well the outer lead of the main PCB is loose and it is threaded into the main power cord.
Page 101
CHV Mini VRF 50/60Hz 5.21 P1: High pressure protection 5.22 P2: Low pressure protection 201908...
Page 102
CHV Mini VRF 50/60Hz 5.23 P3: Inverter over current protection 5.24 P4: Exhaust overheating protection 201908...
Page 103
CHV Mini VRF 50/60Hz 5.25 P5: T3 or T3B condenser pipe overheating protection 5.26 P6: IPM protection 201908...
Page 104
CHV Mini VRF 50/60Hz Code Malfunction or protection remark Inverter compressor malfunction DC generatrix low voltage protection DC generatrix high voltage protection reserved MCE malfunction/simultaneously/cycle loop After P6 displaying for 60s, these L error codes Zero speed protection will display. reserved Wrong phase protection Speed difference >15Hz protection between the front and the...
Page 105
CHV Mini VRF 50/60Hz 5.27 P9: DC fan fault Check if the voltage at each position Replace the main PCB is normal as follows 是 Check if the feedback and PWM signals are If PWM signal is abnormal, normal when turning replace the main PCB If the feedback signal is abnormal, replace the fan motor...
Page 106
CHV Mini VRF 50/60Hz 5.28 P10: Anti-typhoon protection (1) Enter this condition: a) The fan has stopped output for several minutes; b) The current speed detected by the fan is >=400rpm. (2) Exit this condition: a) After several minutes of anti-typhoon protection; b) The fan detects the current speed <400rpm.
Page 107
CHV Mini VRF 50/60Hz 5.32 L0: DC compressor module fault (1) Over current protection(auto-recover): Lights flash once every 3s. Solution: Usually caused by bad outdoor unit heat exchanging condition, improve the heat exchanging condition. Otherwise, check if the outdoor ambient temperature sensor has a resistance offset. If the resistance value is offset, replace the sensor.
Page 108
CHV Mini VRF 50/60Hz 5.35 L4: MCE fault / sync / closed loop (1) Check if the DC bus voltage is normal: 510-580V, if it is less than 510V, go to check the rectifier circuit. (2) Check if the wiring of the rectifier circuit is correct, and confirm that the plug is not loose or the like. (3) If the rectifier circuit troubleshooting machine still does not start, please replace the main control board.
Page 109
CHV Mini VRF 50/60Hz 5.40 Pb: T6 refrigerant cooling panel temperature is too high Check the 12th and 13th parameters of the main control board. If the value is ≥85°C, the outdoor unit will stop and report Pb protection. (1) Poor heat dissipation of the outdoor unit: Solution: Improve the heat dissipation conditions of outdoor units (especially at the heat sink fins).