Components
Service manual
72
A
a
A Class 42+50 unit
a Compressor pipe
8 Stop the nitrogen supply when the piping has cooled down.
INFORMATION
It is ALSO possible to cut the component pipe(s) using a pipe cutter. Make sure to
remove the remaining component pipe end(s) from the refrigerant pipes by heating
the brazing point(s) of the component pipe(s) using an oxygen acetylene torch.
9 Remove the nuts and bolts and remove the compressor from the unit.
A
a
c
A Class 20~35 unit
a Nut
b Compressor
c Damper
b
a
c
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04B – 2022.08