Pipe size determined in
Table 10A through 10C.
Figure 16. Typical Intake Pipe Connections (Direct Vent Applications)
Intake Piping
The NF96DV furnace may be installed in either direct
vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
Use the following steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1.
Use cement or a sheet metal screw to secure the
intake pipe to the inlet air connector.
2.
If intake air is drawn from a ventilated crawlspace
(Figure 19) or ventilated attic (Figure 18) the exhaust
vent length must not exceed those listed in Table 10C.
If 3" diameter pipe is used, reduce to 2" diameter pipe
to accommodate the debris screen.
3.
Route piping to outside of structure. Continue with
installation following instructions given in general
guide lines for piping terminations and intake and
exhaust piping terminations for direct vent sections.
Refer to Table 10A through Table 10C for pipe sizes.
2"
2"
2"
3"
*2"
TRANSITION
*2"
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE − Intake pipe and exhaust pipe must be the same diameter.
Use the following steps when installing the unit in Non-
Direct Vent applications where combustion air is taken
from indoors or ventilated attic or crawlspace and flue
gases are discharged outdoors.
1. Use field-provided materials and the factory-provided
2.
Page 22
2"
2"
or
TRANSITION
*2"
3"
air intake screen to route the intake piping as shown
in Figure 17. Maintain a minimum clearance of 3"
(76mm) around the air intake opening. The air intake
opening (with the protective screen) should always be
directed forward, or sideways.
Use cement to secure the intake pipe to the connector,
if desired.
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by an
exhaust fan, power exhaust fan, or other device which
may create a negative pressure in the space, take care
when sizing the inlet air opening. The inlet air opening
must be sized to accommodate the maximum volume
of exhausted air as well as the maximum volume of
combustion air required for all gas appliances serviced
by this space.
INTAKE
EXHAUST
TOP VIEW
31-5000727 Rev. 0