The G/Y1 signal to the furnace is energized to turn on the furnace blower. If kumo cloud
and configured to operate a second stage blower speed, the Y/Y2 signal is also energized.
The furnace blower continues to run for 30 seconds after the humidifier stops.
NOTE
• Humidifier output will only run when in heating mode.
• Mode 25 set to 1 = furnace fan on, when thermo OFF. Mode 25 set to 2 = furnace fan
off, when thermo OFF.
Specifications are subject to change without notice.
PAA-A18, 24, 30, 36, 42AA1/BA1/CA1
Condition
(No Defrost/No Error)
Heat operation &
Thermo OFF
Heat operation &
Thermo ON
Heat operation &
Thermo OFF
ON
Heat operation &
Thermo ON
Heat operation &
Thermo OFF
Heat operation &
Thermo ON
Heat operation &
Thermo OFF
ON
Heat operation &
Thermo ON
97
CN25 Output
Furnace
Blower
OFF
OFF²
OFF
OFF²
ON
ON²
OFF
OFF²
ON
ON²
®
app is used