User Guide | Danfoss Gas sensor, type DGS
5.10.3 Zero point calibration of
analogue output
5.11 Addressing
© Danfoss | Climate Solutions | 2022.01
With this menu item you can adjust the zero point of the analogue output (4mA). The zero point
correction is only possible when the minimum output is 2 V or 4 mA, i.e. not possible when minimum
output is 0 V or 0 mA.
The error message of the output monitoring is suppressed as long as the menu Calibration AO is open.
Therefore, connect the ampere meter (measuring range 20 mA DC) to the analogue output only after
having opened the menu.
Calibration AO 1
Connect ampere meter to the analogue output.
Calibration
320
Calibration
320
Calibration
SAVE
Calibration
323
Addressing
Assignment of the MODBUS address of the device for system integration, e.g. with
Danfoss front end type AK-SM 800.
Set Address
4
Symbol
Description
4
MODBUS Address
Display of the current zero offset on the left.
AO 1
0
Adjust the zero offset on the right by changing the offset value
AO 1
slowly, until the ampere meter shows the desired value.
323
Save the adjusted zero offset.
AO 1
Return to the display of the current zero offset.
AO 1
323
Define the MODBUS address.
Default
Function
0
0 = Device is not addressed, BUS not used. Max. value is 240.