Siemens SINOVA Manual page 65

3wj air circuit breakers
Table of Contents

Advertisement

Accessories
3.3 Control and signaling accessories
Shunt trip (ST)
Rated control supply voltage U
Operating range (acc. to IEC 60947-1)
Extended operating range for battery operation
Switch-on power
AC / DC
Continuous power AC / DC
Minimum command duration at 100% U
Maximum command time at 100% U
Opening time of the circuit breaker at 100% U
Fuse protection of the control circuit
Smallest permissible
DIAZED fuse, gL, slow-
response
Miniature circuit break-
er with C characteristic
64
S
24 V DC
110 ... 127 V AC /
110 ... 125 V DC
220 ... 240 V AC /
220 ... 250 V DC
S
S
S
24 V DC
110 ... 127 V AC /
110 ... 125 V DC
220 ... 240 V AC /
220 ... 250 V DC
24 V DC
110 ... 127 V AC /
110 ... 125 V DC
220 ... 240 V AC /
220 ... 250 V DC
24 V DC
110 ... 127 V AC / 110 ... 125 V DC
220 ... 240 V AC / 220 ... 250 V DC
85 ... 110% U
S
85 ... 126% U
S
100% OP
40 VA / 40 W
8 VA / 8 W
60 ms
--
80 ms
2 A
1 A
1 A
2 A
1 A
1 A
Operating Instructions, 12/2022, L1V30828903001-01