Lennox LGT036 Installation Instructions Manual page 15

Table of Contents

Advertisement

Parameter
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OP­
TIONS > EDIT PARAMETERS = 12 for EBM, 6 for ECM
BLOWER SMOKE CFM
SETUP > TEST & BALANCE > BLOWER
BLOWER HEATING HIGH CFM
BLOWER HEATING LOW CFM
BLOWER COOLING HIGH CFM
BLOWER COOLING LOW CFM
BLOWER VENTILATION CFM
SETUP > TEST & BALANCE > DAMPER
BLOWER HIGH CFM DAMPER POS %
BLOWER LOW CFM DAMPER POS %
POWER EXHAUST DAMPER POS %
SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 216
POWER EXHAUST DEADBAND %
SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 10 (Applies to Thermostat Mode ONLY)
FREE COOLING STAGE-UP DELAY
Installer: Record any parameter changes under "Field Setting" column. Settings need to be recorded by installer for use when Unit
Controller is replaced or reprogrammed.
LGT/LCT036, 048, 060, 072
TABLE 4
BLOWER PARAMETER SETTINGS - 581102-01
Field
Setting
% Percentage of torque for blower smoke speed.
% Percentage of torque for blower heating high speed.
Percentage of torque for blower heating low speed (P volt gas heat
%
only).
% Percentage of torque for blower cooling high speed.
Percentage of torque for blower cooling low speed and vent speed for
%
standard static blowers.
% Percentage of torque for high static blower ventilation speed.
% Minimum damper position for high speed blower operation. Default 0%.
% Minimum damper position for low speed blower operation. Default 0%.
Minimum damper position for low power exhaust operation. Default
%
50%.
% Deadband % for power exhaust operation. Default 10%.
Number of seconds to hold blower at low speed before switching to
sec
blower at high speed. Default 300 seconds.
Page 15
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lgt048Lgt060Lgt072Lct036Lct048Lct060 ... Show all

Table of Contents