Heatilator RAVE32-IFT-B Installation Manual page 36

Hide thumbs Also See for RAVE32-IFT-B:
Table of Contents

Advertisement

Coaxial to Colinear Venting
WARNING! Risk of Fire! Coaxial to colinear venting con-
figuration may only be used in existing non-combustible
chimney. Installation in any other venting application
could cause fire.
The coaxial to colinear adapter (DV-46DVA-GCL) is ap-
proved for installations into solid fuel masonry or factory
built fireplaces that have been installed in accordance with
the National, Provincial, State and local building codes.
The coaxial to colinear vent components are shown in
Section 12.A. The DV-46DVA-GCL must be recessed
into existing masonry fireplace. See Table 1 and Figure
4.21.
INLET AIR VENT PIPE
Figure 4.21 Coaxial/Colinear Appliance Connector
Prior to installing the gas appliance:
• Have the chimney and adjacent structure inspected
and cleaned by qualified professionals. Hearth & Home
Technologies recommends that NFI or CSIA certified
professionals, or technicians under the direction of certi-
fied professionals, conduct a minimum of a NFPA 211
Level 2 inspection of the chimney.
• Replace component parts of the chimney and fireplace
as specified by the professionals.
• Ensure all joints are properly engaged and the chimney
is properly secured.
Stainless Steel Flex Requirement - RAVE32-IFT-B
ONLY:
The RAVE32-IFT-B model requires the use of a 3 ft. stain-
less steel flex liner (768-380A) to be installed directly to the
exhaust collar on the DV-46DVA-GCL connector.
WARNING! Risk of Fire! Risk of Asphyxiation! Failure
to install the stainless steel flex could cause excessive flex
vent temperatures.
• Aluminum material degradation could cause flex vent
system to fail.
• Installer MUST install the 3 ft. stainless steel flex on
RAVE32-IFT-B.
Heatilator • RAVE32-IFT-B, RAVE36-IFT-B, RAVE42-IFT-B Installation Manual • 2619-983 Rev. U • 9/22
36
EXHAUST VENT PIPE
OUTSIDE FACE OF
FIREPLACE
EXHAUST VENT PIPE
TOP OF FIREPLACE
OPENING
3 IN. MIN.
SHADED AREA DEFINED AS
"INSIDE EXISTING MASONRY
FIREPLACE"
Figure 4.22 Existing Fireplace DV-46DVA-GCL
Clearance Requirements
Table 1
CLEARANCE TO COMBUSTIBLES REQUIREMENTS
DV-46DVA-GCL
Exhaust Vent Pipe
Clearances to Combustibles:
Refer to Section 3 for clearances to the appliance, man-
tel, mantel legs and wall projection.
Refer to Section 5 for pipe clearances to combustibles.
Termination Cap
For installation of termination cap see minimum vent
heights for various pitched roofs. See Section 4.A.
Flue Damper
Fully lock the solid fuel fireplace's flue damper in the open
position, OR completely remove it.
Venting Components
The LINK-DV30B is approved for use with the coaxial/co-
linear venting application. The LINK-DV30B kit includes:
• Two 30 foot sections of flexible vent pipe (3 inches Ø).
One section is used to draw combustion air and the other
section is used to expel exhaust gases.
• One vertical termination cap.
CAUTION! DO NOT use any flue restrictor when vent-
ing with the DV-46DVA-GCL adapter and LINK-DV30B
kit. This could result in poor flame appearance, sooting,
pilot malfunction, or overheating.
5 IN. MIN.
3 IN.
5 IN.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rave36-ift-bRave42-ift-b

Table of Contents