Vertical Sidewall Installation - Vermont Castings VWDVP70NTSC Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

VWDV70 Series Gas Fireplace

VERTICAL SIDEWALL INSTALLATION

Step 1
Locate vent opening on the wall. It may be necessary to
fi rst position the fi replace and measure to obtain hole lo-
cation. Depending on whether the wall is combustible or
noncombustible, cut opening to size. Figure 15 (For com-
bustible walls fi rst frame in opening.)
Combustible Walls: Cut a 10
mm) hole through the exterior wall and frame as shown.
Figure 15
Noncombustible Walls: Hole opening must be 8
mm) in diameter.
Vent Opening for Combustible Walls
10
"
1
2
(267 mm) Min.
10
"
1
2
(267 mm)
Min.
Fireplace Hearth
Opening for Noncombustible Wall
8
"
1
2
(216 mm)
Fireplace Hearth
Figure 15 -
Locate vent opening on wall
Step 2
Secure fi restop to the inside frame, center in the 10
10
" vent opening.
1
2
Step 3
Place fi replace into position. Measure the vertical height
(X) required from the base of the fl ue collars to the center
of the wall opening. Figure 16
Step 4
Using appropriate length of pipe section(s) attach to fi re-
place with three (3) screws. Follow with the installation of
the elbow.
Step 5
Measure the horizontal length requirement fi guring a 1
(32 mm) overlap, i.e. from the elbow to the outside wall
cap. Figure 17
Always install horizontal venting on a level
plane.
16
"H x 10
"W (267 x 267
1
1
2
2
" (216
1
2
Framing Detail
FP2293
" x
1
2
1
Figure 16 -
Vertical Height Requirement
Figure 17 -
Horizontal Length Requirement
Step 6
Use appropriate length of pipe sections — telescopic or
fi xed — and install.
Sealing vent pipe and fi restop gaps with high tem-
perature sealant will restrict cold air being drawn in
around fi replace.
Step 7
Guide the vent terminations 5" and 8" collard into their
respective vent pipes. Double check that the vent pipes
overlap the collars by a minimum 1
the termination to the wall with screws provided and caulk
around the wall plate to weatherproof. As an alternative to
screwing the termination directly to the wall, you may also
"
4
use expanding plugs or an approved exterior construction
adhesive.
Support horizontal pipes every 36" (914 mm)
with metal pipe straps.
VENTING INSTALLATION
X
X
" (32 mm). Secure
1
4
20306745
FP1181