System Trouble Shooting - Reo-Pure LP3 Series User Manual

Hide thumbs Also See for LP3 Series:
Table of Contents

Advertisement

REO-PURE LP3-350 SYSTEM TROUBLESHOOTING
PROBLEM  
RO  SYSTEM  
WILL  NOT  
START  
Pressure  or  float  switch  defective  
LOW  FEED  
PRESSURE  
Inadequate  upstream  pretreatment  
Pressure  regulator  needs  adjustment  
Operating  pressure  gauge  broken  
LOW  
OPERATING  
PRESSURE  
Membrane  element  brine  seal  is  folded  or  not  
THE  PUMP  
DOES  
NOT  RUN  
LOW  OR  NO  
REJECT  
WATER  /  
HIGH  PUMP  
Membrane  element  clogged  or  fouled  
PRESSURE  
Membrane  element  clogged  or  fouled  
LOW  OR  NO  
PRODUCT  
WATER  
Membrane  element  installed  backward  or  brine  
POSSIBLE  CAUSE  
No  electrical  power  
Storage  tank  full  
Low  feed  water  pressure  
Pump/motor  malfunction  
Feed  water  valve  OFF  
Low  inlet  water  pressure  
Filters  clogged  
Obstructed  feed  line  
Pump  impellers  worn  
Pump/motor  coupling  broken  
Low  water  volume  to  pump  
Malfunctioning  pump  
sealed  against  housing  wall  
Inlet  solenoid  valve  not  opening  
Membrane  element  fouled  
Manual  flush  valve  open  
Pump  is  bound  
Pump/Motor  coupling  damaged  
Restricted  orifice  
Clogged  drain  line  
Operating  pressure  low  
Water  temperature  too  low  
Product  check  valve  damaged  
Tank  over  -­  pressurized  
seal  damaged/rolled  
SOLUTION  
Check  power  supply  
Drain  portion  of  water  out  of  tank  
Must  be  minimum  of  35  psi  
Check,  replace  if  necessary  
Check,  replace  if  necessary  
Check,  open  feed  water  shut-­off  valve  
Check,  install  booster  pump  if  necessary  
Check  pressure  on  inlet  and  outlet  filter  pressure  
gauges  
Check  inlet  tubing  
Check  if  sized  correctly  or  fouled  
Check  and  adjust  if  necessary.  
Check,  replace  if  necessary  
Check,  replace  if  necessary  
Check,  replace  if  necessary  
Check,  install  booster  pump  if  necessary  
Check,  replace  if  necessary  
Check  brine  seal,  use  care  when  reinstalling  the  
membrane  into  the  vessel  
Clean  solenoid  valve  or  replace  
Check,  clean  or  replace  
Close  manual  flush  valve  
Manually  check  pump  rotation,  replace  if  necessary.  
Remove  pump  from  motor.    Check,  replace  if  
necessary.  
Check  and  clean  
Check  and  clean  
Check,  clean  or  replace  
Check  and  adjust  
Check,  clean  or  replace  
Check,  consult  dealer  if  necessary  
Check,  replace  if  necessary  
Check  tank  air  pressure.    Relieve  to  10  PSI  if  
necessary  
Check,  use  care  when  reinstalling  the  element  into  the  
housing.  
(system troubleshooting continued on next page)
LP3-­‐‑ 3 50   O wner's   M anual   |     1 9  

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lp3-350Lp3-200

Table of Contents