Operation - Immergas NIKE Mini 24 Export Manual

Compact instantaneous wall-hung conventional flue boilers, compact wall-hung conventional flue boilers for central heating only
Table of Contents

Advertisement

Technical Documentation
Technical Documentation
Secondary circuit (domestic hot water circuit) for combi versions only.

Operation.

When domestic hot water is drawn cold water flows inside
the d.h.w. flow switch (1) which closes the electrical contact
coupled to it (see the electrical circuit).
As a result, the integrated board starts the d.h.w. priority phase
that ignites the burner and, if there's an ongoing central heating
request, switches the 3-way diverter valve (2) moving it into the
working position (see operation of the hydraulic 3-way valve).
This causes the delivery pipe (M) to close and simultaneously
the passage opens to the d.h.w. exchanger (3).
In this way circulation in the central heating system is pre-
vented while it is allowed in the plate exchanger, inside which
the domestic cold water absorbs the heat from the primary
circuit water (see d.h.w. exchanger).
So in this phase, central heating is off, domestic hot water
having priority.
The water/water heat exchange occurs inside the d.h.w. ex-
changer (3) which is secured to the d.h.w. inlet (1) and outlet
(2) body with screws.
Cold water
The top of the body on the left allows cold domestic water to
inlet
enter, while at the bottom it allows primary circuit return.
D.h.w. outlet
In the same way, the top part of the body on the right allows
the outlet of domestic hot water while at the bottom it allows
primary circuit delivery.
3
1
Primary
circuit return
Primary
circuit delivery
2
D.h.w. outlet
STNM ed 07/07
NIKE Mini Export
16