Honeywell ExiLED Manual page 3

Surface mounted

Advertisement

Technical description
Part no.:
Operation Voltage:
Maximum Power Consumption:
Battery (LiFePO ):
4
Battery Protection:
Min. - Max. Charge Current:
Charge Voltage Range:
Charging Time:
Emergency Mode Duration:
Lumen output, normal:
Lumen output, emergency (1h/3h/8h):
Produced in accordance with:
Ambient Temperature Range:
Relative Humidity:
Degress of cover protection:
Technical lifetime (light source):
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
The ExiLED is a self-contained LED exit sign with selftest function.
It can be configured as maintained or non-maintained.
Selftest functions
Every 15 days the luminaire will perform an emergency operation test. This will light the exit sign for approximately 3
seconds. The red indicator LED will flash during this test sequence.
Every 6 months the luminaire will perform a battery condition test. The test will last for the stated duration. The exit sign will
be lit and the yellow indicator LED will flash during this test sequence.
Note: When using DALI or Wireless communication, the frequencies and schedules for tests will instead be determined by
the connected PC software.
Manual test functions
Manual tests can only be performed if both mains and battery are connected.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed. The exit sign will be lit for
approximately 3 seconds, the red indicator LED will flash during this test sequence.
By pressing the test button for a time space between 5 and 10 seconds, a battery condition test is performed. This test will
last for the stated duration and can only be performed when the battery is fully charged (steady green indicator LED). The
exit sign will be lit and the yellow indicator LED will flash during this test sequence.
Resetting errors
Push the test button for a time space between 10 and 15 seconds to delete all indicated errors. Then the luminaire enters
regular operation mode.
Dimming
By pressing the test button continuously for 15 seconds, when luminaire is connected to mains, the luminosity will be
reduced to 10% of its total luminance. In emergency mode the light output will remain unchanged.
To restore the original settings, repeat the above procedure.
The dimming setting remains stored in the luminaire even when both mains and battery voltages are disconnected.
Honeywell Life Safety AS, Postboks 236, 1372 Asker
ExiLED M ST LED 25m 10Y 138h ExiLED M ST LED 40m 10Y 138h
138087.10
220-240V AC, 50-60 Hz
3.8W / 4.1VA
Overcharge protection / Deep discharge protection
1h / 3h / 8h manually selected (default 1h)
155lm
200/90/40lm
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
900 gr
138126.10
4.1W / 4.4VA
6.4V / 0.6Ah
25 - 125mA
5.6 - 7.3V
8hours
180lm
210/90/40lm
o
5 to 40 C
Up to 95%
IP40
> 100000 hours
1400 gr
10 years
http://www.hls-nordic.com