9-2 ELECTRICAL CHARACTERISTICS
Table 4
Units
Voltage
Model
Hz
Volts
range
FXMQ15TBVJU
FXMQ18TBVJU
FXMQ24TBVJU
208/
MAX. 253V
FXMQ30TBVJU
60
230
MIN. 187V
FXMQ36TBVJU
FXMQ48TBVJU
FXMQ54TBVJU
MCA: Minimum Circuit Ampacity (A) ;
MOP: Maximum Overcurrent Protective Device (A)
HP: Fan Motor Rated Output (Hp (W)) ; FLA: Full Load Ampere (A)
9-3 SPECIFICATION FOR FIELD SUPPLY FUSES
AND WIRING
Table 5
Power supply wiring
Model
MOP
Size
FXMQ15TBVJU
FXMQ18TBVJU
Wiring size
FXMQ24TBVJU
and length
FXMQ30TBVJU
15A
must comply
with local
FXMQ36TBVJU
codes.
FXMQ48TBVJU
FXMQ54TBVJU
The lengths of remote controller wiring and transmission wir-
ing are as follows:
(1) Remote controller wiring (indoor unit - remote controller)
..............................................................Max. 1,640 ft. (500 m)
(2) Transmission wirings ... Total wiring length 6,560 ft. (2,000 m)
• Outdoor unit - Indoor unit ........ Max. 3,280 ft. (1,000 m)
• Outdoor unit - Branch Selector unit ... Max. 3,280 ft. (1,000 m)
• Branch Selector unit - Indoor unit ..... Max. 3,280 ft. (1,000 m)
• Indoor unit - Indoor unit .......... Max. 3,280 ft. (1,000 m)
NOTE
1. Vinyl cord with sheath or cable (Insulated thickness :
1/16 in. (1 mm) or more)
English
Power
Fan motor
supply
MCA MOP
HP
FLA
0.31
1.8
15
1.4
(230)
0.31
1.9
15
1.5
(230)
0.31
1.9
15
1.5
(230)
0.49
3.0
15
2.4
(364)
0.49
3.1
15
2.5
(364)
0.49
3.6
15
2.9
(364)
0.47
3.6
15
2.9
(350)
Remote controller wiring
Transmission wiring
Wiring
Size
2-conductor,
stranded
nonshielded
AWG18-16
copper cable
(0.75-
PVC/vinyl
1.25 mm
)
2
jacket
(NOTE 2)
9-4 WIRING CONNECTION METHOD
CAUTION FOR WIRING
• For connection to the terminal block, use ring type crimp
style terminals with insulation sleeve or insulate the wirings
properly.
Insulation sleeve
Ring type crimp
style terminals
Fig. 21
• Connect the terminal as shown in Fig. 22.
• Do not carry out soldering finish when stranded wires are
used. (Otherwise, the loosening of wires may result in
abnormal heat radiation.)
Use wires the same in size
(If the air conditioner is
in simultaneous multi operation)
Fig. 22
(Abnormal heating may occur if the wirings are not tight-
ened securely.)
• Use the required wirings, connect them securely and fix
these wirings securely so that external force may not apply
to the terminals.
• Use a proper screw driver for tightening the terminal
screws.
If an improper screw driver is used, it may damage the
screw head and a proper tightening cannot be car ried out.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
terminals.
Table 6
Terminal for remote controller and
transmission wirings
Terminal for power supply
Ground terminal
• Do not carry out soldering finish when stranded wirings
are used.
Wiring
Tightening torque
[lbf·ft. (N·m)]
0.65 ± 0.07
(0.88 ± 0.08)
1.08 ± 0.10
(1.47 ± 0.14)
14