7.4.2. Low SoC alarm settings

When enabled, the alarm will activate when the state of charge (SoC) falls below the set value for more than 10 seconds. The
alarm will deactivate when the state of charge rises above the clear value
Setting
Set alarm value (setting 33)
Clear alarm value (setting 34)

7.4.3. Low voltage alarm

When enabled, the alarm will activate when the battery voltage falls below the set value for more than 10 seconds. The alarm will
deactivate when the battery voltage rises above the clear value.
Setting
Set alarm value (setting 35)
Set alarm value (setting 35)
Clear alarm value (setting 36)
Clear alarm value (setting 36)

7.4.4. High voltage alarm

When enabled, the alarm will activate when the battery voltage rises above the set value for more than 10 seconds. The alarm
will deactivate when the battery voltage drops below the clear value.
Setting
Set alarm value (setting 37)
Set alarm value (setting 37)
Clear alarm value (setting 38)
Clear alarm value (setting 38)

7.5. Display settings

7.5.1. Backlight intensity

The intensity of the backlight This setting ranges from 0 (always off) to 9 (maximum intensity).
Setting
Backlight intensity (setting 49)

7.5.2. Backlight always on

When set the backlight will not automatically turn off after 60 seconds of inactivity.
Page 29
Manual - BMV-700H
Default
1%
0 - 100%
1%
0 - 100%
Default
1.1V
0 - 95.0V
0V
1.0V
0 - 95.0V
0V
Default
1.1V
0 - 95.0V
0V
1.0V
0 - 95.0V
0V
Default
5
Range
Steps
1%
1%
Range
Steps
0.1V
0 - 384V
0.1V
0.1V
0 - 384V
0.1V
Range
Steps
0.1V
0 - 384V
0.1V
0.1V
0 - 384V
0.1V
Range
Step size
0 - 9
1