Low Voltage Relay; High Voltage Relay; Alarm Settings; Alarm Buzzer - Victron energy BMV-700H Manual

Battery monitor
Hide thumbs Also See for BMV-700H:
Table of Contents

Advertisement

The "clear relay" value needs to be greater than the "set relay" value.
Setting
Set relay value (setting 16)
Clear relay value (setting 17)
When the "set relay" and "clear relay" values are equal, the state of charge condition will be unable to drive
the relay.
Note that this setting is also known as the discharge floor. The time-to-go reading displayed by the battery
monitor relates to this setting. The time to go is the time left until this setting (the discharge floor) has been
reached.

7.3.7. Low voltage relay

When the battery voltage falls below the "set relay" value for more than 10 seconds the relay will close.
When the battery voltage rises above the "clear relay" value, the relay will open (after a delay, depending on the
closed time [27]
and/or the
Relay off delay [27]
The "clear relay" value needs to be greater than the "set relay" value.
Setting
Set relay value (setting 18)
Clear relay value (setting 19)

7.3.8. High voltage relay

When the battery voltage rises above the "set relay" value for more than 10 seconds the relay will close.
When the battery voltage falls below the "clear relay" value, the relay will open (after a delay, depending on the
closed time [27]
and/or the
Relay off delay [27]
The "clear relay" value needs to be greater than the "set relay" value.
Setting
Set relay value (setting 20)
Clear relay value (setting 21)

7.4. Alarm settings

The BMV battery monitor is equipped with an alarm relay and a buzzer. Alarms are also visible on the VictronConnect app while
connected to the battery monitor or are used to send an alarm signal to a GX device.
Alarms are disabled by default. To enable do the following:
• In the VictronConnect app, enable the alarm by sliding the slider button to the right.
• Via the head unit, enable the alarm by changing the "set" and "clear" value in the alarm settings to any value above zero.

7.4.1. Alarm buzzer

When enabled (set to ON), the buzzer will sound an alarm as soon as an alarm condition occurs. After a button is pressed, the
buzzer will stop sounding.
When disabled (set to OFF) the buzzer will not sound an alarm.
Setting
Alarm buzzer (setting 32)
Page 28
Manual - BMV-700H
Default
50%
90%
settings).
Default
0V
0V
settings).
Default
0V
0V
Default
ON
Range
Step size
0 - 99%
1%
0 - 99%
1%
Relay minimum
Range
Step size
0 - 384V
0.1V
0 - 384V
0.1V
Relay minimum
Range
Step size
0 - 384V
0.1V
0 - 384V
0.1V
Modes
ON
OFF
All features and settings