PRODUCT DESIGN
WARNING
In 90% furnace upright upflow installations, the drain
trap must be mounted on the opposite side of the unit
from the junction box. This will reduce the risk of wa-
ter reaching the junction box in the event of a blocked
drain condition.
Connect hot, neutral, and ground wires as shown in the
wiring diagram located on the unit's blower door. Line po-
larity must be observed when making field connections. Line
voltage connections can be made through either the right
or left side panel.
The 80% and 90% furnaces are shipped configured for a
left side electrical connection with the junction box located
inside the burner compartment on 80% furnaces and in-
side the blower compartment on 90% furnaces. To make
electrical connections through the opposite side of the fur-
nace, the junction box must be relocated to the other side
of the burner compartment on 80% furnaces and to the
other side of the blower compartment on 90% furnaces prior
to making electrical connections, refer to the following fig-
ures.
CAUTION
Edges of sheet metal holes may be sharp. Use gloves
as a precaution when removing hole plugs.
STANDARD
JUNCTION BOX
LOCATION
80% Furnace Junction Box Relocation
STANDARD
JUNCTION BOX
LOCATION
90% Furnace Junction Box Relocation
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.
To avoid the risk of electrical shock, injury, or death,
the furnace must be electrically grounded in accor-
dance with local codes or, in their absence, with the
latest edition of the National Electric Code.
115 VOLT LINE CONNECTION OF ACCESSORIES
(HUMIDIFIER AND ELECTRONIC AIR CLEANER)
To avoid electrical shock, injury or death, disconnect
electrical power before servicing, or changing any elec-
trical wiring.
All 80% & 90% furnaces, except the 80% GUIB & GCIB
model furnaces, have an integrated ignition control that is
equipped with line voltage accessory terminals for control-
ling power to an optional field-supplied humidifier and/or elec-
tronic air cleaner.
Electronic Air Cleaner
Turn OFF power to the furnace before installing any acces-
sories. Follow the humidifier or air cleaner manufacturers'
instructions for locating, mounting, grounding, and control-
ling these accessories.
Refer to the following two figures for installation of either an
Electronic Air Cleaner or Humidifier on GUIB or GCIB model
ALTERNATE
JUNCTION BOX
furnaces that have a WR50A52 ignition control.
LOCATION
L 1
N
(GUIB/GCIB with WR50A52 Ignition Control)
ALTERNATE
JUNCTION BOX
LOCATION
(GUIB/GCIB with WR50A52 Ignition Control)
WARNING
WARNING
Accessory Load Specifications
Humidifier
1.0 Amp maximum at 120 VAC
1.0 Amp maximum at 120 VAC
F L O W A C T U A T E D
S W IT C H
Electronic Air Cleaner Wiring
INTEGRATED CONTROL MODULE
HOT 120 VAC
NEUTRAL 120 VAC
H
L
E
I
A
N
T
E
1 2 0 V
R E L A Y
T O IN D O O R B L O W E R
H E A T IN G S P E E D
Humidifier Wiring
E L E C T R O N IC
A IR C L E A N E R
L
I
N
E
H U M ID IF IE R
61
Rev. 1