Before Commissioning; Flushing - Vexve BFS400W1 Installation, Operation And Maintenance Manual

Butterfly valves
Table of Contents

Advertisement

4.7 Before commissioning

It is recommended to fill the pipeline via by-pass valves in order to avoid pressure shocks and to reduce
forces caused by opening the butterfly valve under pressure (see Figure 23.).
NOTE:
· It is recommended to fill the pipeline via by-pass valves.
· The pipeline must be flushed carefully, see chapter 4.8 for instructions

4.8 Flushing

Pipeline needs to be flushed carefully after the
valve installation.
Before starting the flushing, turn the valve disc
so that the opening angle is 30–40°.
Close the valve gradually during the flushing until
the opening angle is approximately 5-10°.
Decreasing the opening angle increases the
velocity of the flow through the valve. This
produces efficient removing of impurities from
sealing surfaces of the valve.
18
To avoid pressure shocks and to reduce the
forces caused by opening the valve under pres-
sure, a by-pass valve must be used in
connection with butterfly valves
(see Figure 23.).
Figure 23. By-pass valve.
Figure 24. Pipeline needs to be flushed after
valve installation
www.vexve.com