EASTRON SDM630-MT V2 User Manual
SDM630-MT V2
DIN Rail Smart Meter for Single and Three Phase Electrical Systems
Measures 4 Tariffs kWh/kvarh/time
and Kvarh, KW, Kvar, KVA, P, F, PF, dmd, V, A etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
USER MANUAL
2016 V1.1

Advertisement

loading

Summary of Contents for Eastron SDM630-MT V2

  • Page 1 EASTRON SDM630-MT V2 User Manual SDM630-MT V2 DIN Rail Smart Meter for Single and Three Phase Electrical Systems  Measures 4 Tariffs kWh/kvarh/time and Kvarh, KW, Kvar, KVA, P, F, PF, dmd, V, A etc.  Bi-directional measurement IMP & EXP ...
  • Page 2 EASTRON SDM630-MT V2 User Manual Introduction The SDM630-MT V2 is a multifunction meter that supports max 4 tariffs and 10 time segments, the tariffs and segments can be set via RS485 communication. The unit measures and displays the characteristics of single phase two wires (1p2w), three phase three wires (3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active and reactive energy, imported or exported.
  • Page 3 EASTRON SDM630-MT V2 User Manual Start-up Screens The first screen lights up all display segments and can be used as a display check second screen indicates firmware installed in the unit and its build number. The interface performs a self-test and indicates the result if the test passes.
  • Page 4 EASTRON SDM630-MT V2 User Manual Each successive pressing of the button selects a new range: Phase to neutral voltages(3p4w) Phase to neutral voltages(3p3w) Current on each phase Phase to neutral voltage THD%(3p4w) Phase to neutral voltage THD%(3p3w) Current THD% for each phase Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
  • Page 5 EASTRON SDM630-MT V2 User Manual Frequency and Power factor and Demand Each successive pressing of the button selects a new range: Frequency and Power Factor (total) Power Factor of each phase Maximum Power Demand Maximum Current Demand Power Each successive pressing of the...
  • Page 6 EASTRON SDM630-MT V2 User Manual Instantaneous Reactive Power in kVAr Instantaneous Volt-amps in KVA Total kW, kVArh, kVA Energy Measurements Each successive pressing of the button selects a new range: Imported active energy in kWh Exported active energy in kWh Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
  • Page 7 EASTRON SDM630-MT V2 User Manual Tariff 1 Active energy Tariff 2 Active energy Tariff 3 active energy Tariff 4 active energy Total active energy in kWh Imported reactive energy in kVArh Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. - 6 -...
  • Page 8 EASTRON SDM630-MT V2 User Manual Exported reactive energy in kVArh Tariff 1 reactive energy Tariff 2 reactive energy Tariff 3 reactive energy Tariff 4 reactive energy Total reactive energy in kVArh Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. - 7 -...
  • Page 9 EASTRON SDM630-MT V2 User Manual Date Year/month/day Example:1st.Jan.2000 Time Hour/minute/second Example:00:02:16 Set-up To enter set-up mode, pressing the button for 3 seconds, until the password screen appears. Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing.
  • Page 10 EASTRON SDM630-MT V2 User Manual 1) Use the buttons to select the required item from the menu. Selection does not roll over between bottom and top of list 2) Press to confirm your selection 3) If an item flashes, then it can be adjusted by the buttons.
  • Page 11 EASTRON SDM630-MT V2 User Manual Press the to enter the change password routine. The new password screen will appear with the first digit flashing to set the first digit and press to confirm your selection. The next digit will flash.
  • Page 12 EASTRON SDM630-MT V2 User Manual Press to enter the selection routine. The current time interval will flash buttons to select the time required. Press to confirm the selection. SET indicator will appear. Press to exit the DIT selection routine and return to the menu.
  • Page 13 EASTRON SDM630-MT V2 User Manual Press to enter the selection routine. The current time interval will flash The options can be: 0(always on),5,10,30,60,120minutes buttons to select the time required. Press to confirm the set-up, Supply System Use this section to set the type of power supply being monitored.
  • Page 14 EASTRON SDM630-MT V2 User Manual Pulse output This option allows you to configure the pulse output 1. The output can be set to provide a pulse for a defined amount of energy active or reactive. Use this section to set up the pulse output for:...
  • Page 15 EASTRON SDM630-MT V2 User Manual (It shows 1 impulse = 10kWh/kVArh) From the Set-up menu, use buttons to select the Pulse Rate option. Press to enter the selection routine. The current setting will flash. Note: When it’s dFt, it means 2.5Wh/VArh buttons to choose pulse rate.
  • Page 16 EASTRON SDM630-MT V2 User Manual From the Set-up menu, use buttons to select the Pulse width option. Press to enter the selection routine. The current setting will flash. buttons to choose pulse width. On Completion of the entry procedure, press...
  • Page 17 EASTRON SDM630-MT V2 User Manual Press button to enter the selection routine. The current setting will be flashing. buttons to choose Modbus Address(001 to 247) On completion of the entry procedure, press button to confirm the setting and press button to return the main set-up menu.
  • Page 18 EASTRON SDM630-MT V2 User Manual to return to the main set up menu. Parity From the Set-up menu, use buttons to select the Parity option. Press to enter the selection routine. The current setting will flash. buttons to choose Parity (EVEN / ODD / NONE)
  • Page 19 EASTRON SDM630-MT V2 User Manual Press to enter the selection routine. The current setting will flash. buttons to choose Stop Bit (2 or 1) On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.
  • Page 20 EASTRON SDM630-MT V2 User Manual Voltage and Current Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies) Voltages between phases 173 to 500V a.c. (3p supplies only) Basic current (Ib): 10A Max current : 100A Min. Current: 5% of Ib Starting current: 0.4% of Ib...
  • Page 21 EASTRON SDM630-MT V2 User Manual  Total harmonic distortion 1% up to 19st harmonic  Temperature co-efficient Voltage and current = 0.013%/°C typical Active energy = 0· 018%/°C, typical  Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
  • Page 22 EASTRON SDM630-MT V2 User Manual Environment  Operating temperature -25°C to +55°C*  Storage temperature -40°C to +70°C*  Relative humidity 0 to 90%, non-condensing  Altitude Up to 2000m  Warm up time  Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g Dimensions Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
  • Page 23 EASTRON SDM630-MT V2 User Manual Wiring diagram  Three Phase Three Wires: Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. - 22 - Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn...
  • Page 24 EASTRON SDM630-MT V2 User Manual  Three Phase Four Wires: Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. - 23 - Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn...
  • Page 25 EASTRON SDM630-MT V2 User Manual  Single Phase two Wires: Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. - 24 - Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn...