Location; Ductwork; Acoustic Insulation - Carrier WeatherMaker 50A020 Installation Instructions Manual

Single package electric cooling rooftop units with electric heat option, comfortlink controls and puron refrigerant (r-410a)
Hide thumbs Also See for WeatherMaker 50A020:
Table of Contents

Advertisement

WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
R-410A refrigerant systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on R-410A refrigerant equipment.
CAUTION
DO NOT re-use compressor oil or any oil that has been ex-
posed to the atmosphere. Dispose of oil per local codes and
regulations. DO NOT leave refrigerant system open to air any
longer than the actual time required to service the equipment.
Seal circuits being serviced and charge with dry nitrogen to
prevent oil contamination when timely repairs cannot be com-
pleted. Failure to follow these procedures may result in dam-
age to equipment.
ACOUSTICAL CONSIDERATIONS
In order to minimize sound transmitted to the space, please con-
form to the following recommendations (Fig. 1):

Location

Avoid locating the unit above sound-sensitive areas. In-
stead, locate the unit above restrooms, storage areas, corri-
dors, or other noise-tolerant areas.
Avoid mounting the unit in the middle of large roof ex-
panses between vertical supports. This will minimize the
phenomenon known as roof bounce.
Install the units close to vertical roof supports (columns or
load bearing walls).
Locate the units at least 25 ft away from critical areas. If
this is not possible, the ductwork and ceiling structure
should be acoustically treated.
Consider the use of vibration isolators or an acoustic curb.
FLEXIBLE
CONNECTORS
SUPPLY AND
RETURN
VIBRATION
ISOLATORS
IN ROOF
CURB

Ductwork

Acoustic Insulation

INTAKE
SUPPLY
PLENUM
FAN
SUPPLY AND RETURN
DUCTS LINED WITH
ACOUSTICAL DUCT LINER
Fig. 1 — Acoustical Considerations
2
Utilize flexible connectors between the unit and the supply
and return ducts.
Supply and return air main trunk ducts should be located
over hallways and/or public areas.
Provide trailing edge turning vanes in ductwork elbows
and tees to reduce air turbulence.
Make the ductwork as stiff as possible.
Use round duct wherever possible because it is less noisy.
Seal all penetrations around ductwork entering the space.
Make sure that ceiling and wall contractors do not attach
hangers or supports to ductwork.
Provide as smooth and gradual transition as possible when
connecting the rooftop unit discharge to the supply duct.
If a ceiling plenum return is utilized, provide a return elbow
or tee to eliminate line-of-sight noise to the space. Face the
entrance of the return duct away from other adjacent units.
Provide acoustic interior lining for first 20 ft of supply and
return duct or until the first elbow is encountered. The el-
bow prevents line-of-sight transmission in the supply and
return ducts.
Install a double layer of 2-in. low density quilted fiberglass
acoustical pad with a
/
-in. barium-loaded vinyl facing on
1
8
top of the roof deck before building insulation and roofing
installation occur. Place the material inside the curb and
for 4 to 8 ft beyond the unit perimeter, dependent upon unit
size (larger units require a wider apron outside the curb).
Openings in the pad should only be large enough for the
supply and return ducts. An alternate approach is to use
two layers of gypsum board with staggered seams in addi-
tion to the acoustical pad.
DISCHARGE
PLENUM
COMPRESSOR/
CONDENSING
SECTION
ROUND DUCT CONTROLS
RUMBLE BEST
ALL ROOF
PENETRATIONS
SHOULD BE
SEALED
AIR TIGHT

Advertisement

Table of Contents
loading

Table of Contents