(2-PIPE AND 4-PIPE) FAN COIL UNIT (BAC-19XX63)

Inputs and Outputs List

FCU (2-PIPE)
Inputs
(AI1)
INTERNAL Space Temperature Sensor*
AI2/IN2
Remote Room Temp. Sensor
AI3/IN3
Discharge Air Temperature
AI4/IN4
Analog Input #4
BI5/IN5
Condensate Overflow (Float Switch)
BI6/IN6
Fan Status
AI7/IN7
Supply Water Temperature
(AI8)
INTERNAL Humidity Sensor*
(BI9)
INTERNAL Motion Sensor*
(AI10)
INTERNAL CO2 Sensor*
*Internal temperature sensor is on all models. Option-
al internal humidity, motion, and CO
applicable models.
Outputs
BO1/RLY1
3-Speed Fan Low Speed; Mod. Fan Start
BO2/RLY2
3-Speed Fan Medium Speed
BO3/RLY3
3-Speed Fan High Speed
BO4/RLY4
On/Off Heat/Cool Valve*
BO5/RLY5
On/Off Auxiliary Heat**
BO6/RLY6
Binary Output #6
AO7/OUT7
Modulating Heat/Cool Valve*
AO8/OUT8
Modulating Auxiliary Heat**
AO9/OUT9
Modulating Fan Speed Control
*AO7 and BO4 are controlled simultaneously.
**AO8 and BO5 are controlled simultaneously.
NOTE: For unit ventilator (with outside air
damper) applications, see
Unit Ventilator (BAC-19xx36) on page
12.
NOTE: Binary Output (BO1—BO6) terminals
are relays and are used with SC
terminals instead of GND terminals.
NOTE: Universal (analog) inputs (AIx/INx) and
outputs (AOx/OUTx) are used with GND
terminals. They can be configured to
emulate binary (on/off or voltage/no-
voltage) objects.
BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide
sensors are on
2
(4-Pipe)
(AI1)
INTERNAL Space Temperature Sensor*
AI2/IN2
Remote Room Temp. Sensor
AI3/IN3
Discharge Air Temperature
AI4/IN4
Analog Input #4
BI5/IN5
Condensate Overflow (Float Switch)
BI6/IN6
Fan Status
AI7/IN7
Analog Input #7
(AI8)
INTERNAL Humidity Sensor*
(BI9)
INTERNAL Motion Sensor*
(AI10)
INTERNAL CO2 Sensor*
*Internal temperature sensor is on all models. Option-
al internal humidity, motion, and CO2 sensors are on
applicable models.
BO1/RLY1
3-Speed Fan Low Speed; Mod. Fan Start
BO2/RLY2
3-Speed Fan Medium Speed
BO3/RLY3
3-Speed Fan High Speed
BO4/RLY4
On/Off Cooling Valve*
BO5/RLY5
On/Off Heating Valve**
BO6/RLY6
Binary Output #6
AO7/OUT7
Modulating Heat/Cool Valve*
AO8/OUT8
Modulating Auxiliary Heat**
AO9/OUT9
Modulating Fan Speed Control
*AO7 and BO4 are controlled simultaneously.
**AO8 and BO5 are controlled simultaneously.
NOTE: Universal Input (INx) terminal = Analog
Input (AIx) object or Binary Input (BIx).
Universal Output (OUTx) terminal =
Analog Output (AOx) object. Relay
output (RLYx) = Binary Output (BOx)
object.
NOTE: Unused inputs and outputs are
available for use with custom
configuration and programming in
KMC software.
7
FCU (4-PIPE)
Inputs
Outputs
AG200123C