HEAT PUMP UNIT (BAC-19XX63)

Inputs and Outputs List

Inputs
(AI1)
INTERNAL Space Temperature Sensor*
AI2/IN2
Remote Room Temp. Sensor
AI3/IN3
Discharge Air Temperature
AI4/IN4
Outside Air Temperature
BI5/IN5
BI6/IN6
Fan Status
AI7/IN7
Analog Input #7
(AI8)
INTERNAL Humidity Sensor*
(BI9)
INTERNAL Motion Sensor*
(AI10)
INTERNAL CO2 Sensor*
*Internal temperature sensor is on all models. Option-
al internal humidity, motion, and CO2 sensors are on
applicable models.
Outputs
BO1/RLY1
Fan Start - Stop
BO2/RLY2
Stage 1 Compressor
BO3/RLY3
Stage 2 Compressor
BO4/RLY4
Reversing Valve
BO5/RLY5
Auxiliary Heat
BO6/RLY6
Binary Output #6
AO7/OUT7
Analog Output #7
AO8/OUT8
Analog Output #8
AO9/OUT9
Economizer Output
BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide
HPU
NOTE: Binary Output (BO1—BO6) terminals
are relays and are used with SC
terminals instead of GND terminals.
NOTE: Universal (analog) inputs (AIx/INx) and
outputs (AOx/OUTx) are used with GND
terminals. They can be configured to
emulate binary (on/off or voltage/no-
voltage) objects.
NOTE: Universal Input (INx) terminal = Analog
Input (AIx) object or Binary Input (BIx).
Universal Output (OUTx) terminal =
Analog Output (AOx) object. Relay
output (RLYx) = Binary Output (BOx)
object.
NOTE: Unused inputs and outputs are
available for use with custom
configuration and programming in
KMC software.
15