ROOF TOP UNIT (BAC-19XX63)

Inputs and Outputs List

Inputs
(AI1)
INTERNAL Space Temperature Sensor*
AI2/IN2
Remote Room Temp. Sensor
AI3/IN3
Discharge Air Temperature
AI4/IN4
Outside Air Temperature
AI5/IN5
Analog Input #5
BI6/IN6
Fan Status
AI7/IN7
Analog Input #7
(AI8)
INTERNAL Humidity Sensor*
(BI9)
INTERNAL Motion Sensor*
(AI10)
INTERNAL CO2 Sensor*
*Internal temperature sensor is on all models. Option-
al internal humidity, motion, and CO2 sensors are on
applicable models.
Outputs
BO1/RLY1
Fan Start - Stop
BO2/RLY2
Stage 1 Cooling*
BO3/RLY3
Stage 2 Cooling
BO4/RLY4
Binary Output #4
BO5/RLY5
Stage 1 Heating*
BO6/RLY6
Stage 2 Heating
AO7/OUT7
Analog Cooling Output*
AO8/OUT8
Analog Heating Output*
AO9/OUT9
Economizer Output
*AO7 and BO2 are controlled simultaneously.
**AO8 and BO5 are controlled simultaneously.
BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide
RTU
NOTE: See also
Ventilation) on page
NOTE: Binary Output (BO1—BO6) terminals
are relays and are used with SC
terminals instead of GND terminals.
NOTE: Universal (analog) inputs (AIx/INx) and
outputs (AOx/OUTx) are used with GND
terminals. They can be configured to
emulate binary (on/off or voltage/no-
voltage) objects.
NOTE: Universal Input (INx) terminal = Analog
Input (AIx) object or Binary Input (BIx).
Universal Output (OUTx) terminal =
Analog Output (AOx) object. Relay
output (RLYx) = Binary Output (BOx)
object.
NOTE: Unused inputs and outputs are
available for use with custom
configuration and programming in
KMC software.