Air Handling Unit (Bac-19Xx36); Inputs And Outputs List - KMC Controls KMCConquest FlexStat BAC-19 Series Sequence Of Operation

Hide thumbs Also See for KMCConquest FlexStat BAC-19 Series:
Table of Contents

Advertisement

AIR HANDLING UNIT (BAC-19XX36)

Inputs and Outputs List

Inputs
(AI1)
INTERNAL Space Temperature Sensor*
AI2/IN2
Remote Room Temp. Sensor
AI3/IN3
Discharge Air Temperature
AI4/IN4
Outside Air Temperature
AI5/IN5
Analog Input #5
BI6/IN6
Fan Status
BI7/IN7
Low Limit Status
(AI8)
INTERNAL Humidity Sensor*
(BI9)
INTERNAL Motion Sensor*
(AI10)
INTERNAL CO2 Sensor*
*Internal temperature sensor is on all models. Option-
al internal humidity, motion, and CO2 sensors are on
applicable models.
Outputs
BO1/RLY1
(Modulating) Fan Start/Stop
BO2/RLY2
On/Off Cooling*
BO3/RLY3
On/Off Heating*
AO4/OUT4
Analog Output #4
AO5/OUT5
Analog Output #5
AO6/OUT6
Modulating Fan Speed Control
AO7/OUT7
Modulating Cooling Valve
AO8/OUT8
Modulating Heating Valve
AO9/OUT9
Economizer Output
*AO7 and BO2 are controlled simultaneously.
**AO8 and BO3 are controlled simultaneously.
BAC-19xxxx FlexStat Sequence of Operation and Wiring Guide
AHU
NOTE: See also
Ventilation) on page
NOTE: Binary Output (BO1—BO3) terminals
are relays and are used with SC
terminals instead of GND terminals.
NOTE: Universal (analog) inputs (AIx/INx) and
outputs (AOx/OUTx) are used with GND
terminals. They can be configured to
emulate binary (on/off or voltage/no-
voltage) objects.
NOTE: Universal Input (INx) terminal = Analog
Input (AIx) object or Binary Input (BIx).
Universal Output (OUTx) terminal =
Analog Output (AOx) object. Relay
output (RLYx) = Binary Output (BOx)
object.
NOTE: Unused inputs and outputs are
available for use with custom
configuration and programming in
KMC software.
4
DCV (Demand Control
3.
AG200123C