registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither
ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the
accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or
change this data at any time without further notice.
Numerical distance relay with integrated automatic and control equipment (60 pages)
Summary of Contents for Alstom MiCOM P846
Page 1
GRID ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or...
Safety Section P846/EN SS/H11 (SS) - 1 CONTENTS INTRODUCTION HEALTH AND SAFETY SYMBOLS AND LABELS ON THE EQUIPMENT Symbols Labels INSTALLING, COMMISSIONING AND SERVICING DE-COMMISSIONING AND DISPOSAL TECHNICAL SPECIFICATIONS FOR SAFETY Protective fuse rating Protective class Installation category Environment...
However, the manuals cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Alstom Grid technical sales office and request the necessary information.
P846/EN SS/H11 Safety Section (SS) - 4 SYMBOLS AND LABELS ON THE EQUIPMENT For safety reasons the following symbols which may be used on the equipment or referred to in the equipment documentation, should be understood before it is installed or commissioned.
Page 11
(SS) - 5 Watchdog (self-monitoring) contacts are provided in numerical relays to indicate the health of the device. Alstom Grid strongly recommends that these contacts are hardwired into the substation's automation system, for alarm purposes. To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used.
Page 12
P846/EN SS/H11 Safety Section (SS) - 6 UL and CSA/CUL listed or recognized equipment To maintain UL and CSA/CUL Listing/Recognized status for North America the equipment should be installed using UL or CSA Listed or Recognized parts for the following items: connection cables, protective fuses/fuseholders or circuit breakers, insulation crimp terminals and replacement internal battery, as specified in the equipment documentation.
Safety Section P846/EN SS/H11 (SS) - 7 External test blocks and test plugs Great care should be taken when using external test blocks and test plugs such as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be accessible when using these. *CT shorting links must be in place before the insertion or removal of MMLB test plugs, to avoid potentially lethal voltages.
P846/EN SS/H11 Safety Section (SS) - 8 TECHNICAL SPECIFICATIONS FOR SAFETY Unless otherwise stated in the equipment technical manual, the following data is applicable. Protective fuse rating The recommended maximum rating of the external protective fuse for equipments is 16A, high rupture capacity (HRC) Red Spot type NIT, or TIA, or equivalent.
P846/EN MT Maintenance A general maintenance policy for the relay is outlined. P846/EN TS Troubleshooting Advice on how to recognize failure modes and the recommended course of action. Includes guidance on whom within Alstom Grid to contact for advice.
Page 20
P846/EN IT/D Introduction (IT) 1-4 MiCOM P846 P846/EN SC SCADA Communi cations This section provides an overview regarding the SCADA communication interfaces of the relay. Detailed protocol mappings, semantics, profiles and interoperability tables are not provided with in this manu al.
INTRODUCTION TO MICOM MiCOM is a comprehensive solution capable of meeting all electricity supply requirements. It comprises a range of components, systems and services from Alstom Grid. Central to the MiCOM concept is flexibility. MiCOM provides the ability to define an application solution and, through extensive communication capabilities, integrate it with your power supply control system.
P846/EN IT/D Introduction (IT) 1-6 MiCOM P846 PRODUCT SCOPE The P846 open line detector relay is designed for the protection of power systems in the event of a loss of critical power corridors or important tie lines, the loss of which can easily lead to stability problems.
Page 23
Introduction P846/EN IT/D MiCOM P846 (IT) 1-7 The P846 supports the following relay management functions in addition to the functions illustrated above. • Measurement of all instantaneous & integrated values • Circuit breaker control and status monitoring • Trip circuit and coil supervision •...
Page 27
Technical Data P846/EN TD/D MiCOM P846 (TD) 2-1 Technical Data Rear Communications Port EIA(RS)485 signal levels, two wire Mechanical Specifications Connections located on general purpose block, M4 screw. Design For screened twisted pair cable, multi-drop, 1000m max. Modular MiCOM Px40 platform relay, P846 For K-Bus or DNP3 protocol (ordering options).
Page 28
P846/EN TD/D Technical Data (TD) 2-2 MiCOM P846 Reset: approx. 64% of battery nominal set. Power Supply Recognition time: lter removed, <2ms with long fi Auxiliary Voltage (Vx) <12ms with half-cycle ac immun ity filter on. Three ordering options: (i) Vx: 24 to 48 Vdc...
Page 29
Technical Data P846/EN TD/D MiCOM P846 (TD) 2-3 Make, Carry: nvironmental Conditions 30A for 3 secs, dc resistive, 10,000 operations ( subject to the above limits of Ambient Temperature Range make / break capacity & rated voltag Per IEC 60255-6: 1988 Operating temperature range: Make, Carry &...
Page 30
P846/EN TD/D Technical Data (TD) 2-4 MiCOM P846 lectromagnetic Compatibility munity to Radiated Electromagnetic Energ (EMC) er IEC 60255-22-3: 2000, Class III: Test field strength, frequency band 80 to 1 1 MHz Bu rst High Frequency Disturbance MHz: Test 10 V/m,...
Page 31
Technical Data P846/EN TD/D MiCOM P846 (TD) 2-5 U Directives EMC Compliance Per 2004/108/EC: Compliance to the E uropean Commission Directive on EMC i claimed via the Technical File route. Product Specific Standards wer used to establish conformity: EN50263: 2000...
Page 32
P846/EN TD/D Technical Data (TD) 2-6 MiCOM P846 erformance Protection Functions Year 2000: Compliant Real time clock accura cy: <±2 seconds/day Open Line Detector Protection Modulation ratio: 1/3 or 1/6 Input signal peak-peak amplitude: 200mV…20V Performance Fast Operation: ≤35ms Input impedance at 1000Hz: Ω...
Page 33
Technical Data P846/EN TD/D MiCOM P846 (TD) 2-7 easure’t Setup: Invisible/Visible Settings, Measurements and Comms Settings: Invisible/Visible Records List Commission Tests Invisible/Visible Setting Values: Primary/Seconda Control Inputs: Invisible/Visible Settings List Ctrl I/P Config: Invisible/Visible Ctrl I/P Labels: Invisible/Visible Global Settings (System Data)
Page 34
P846/EN TD/D Technical Data (TD) 2-8 MiCOM P846 Input 1 Trigger: No Trigger/Trigger L/H/Trig RP2 InactivTimer: 1…30min RP2 Baud Rate: 9600 bits/s (up to): Input 32 Trigger: No Trigger/Trigger L/H/ 19200 bits/s Trigger H 38400 bits/s Measured Operating Data Commission...
Page 35
Technical Data P846/EN TD/D MiCOM P846 (TD) 2-9 ϕ Control Input User Labels Per phase ( = A, B, C) RMS current measurements (Ctrl. I/P Labels) Vϕ-ϕ Magnitude Control Input 1: Vϕ-ϕ Phase Angle (up to): Vϕ Magnitude Control Input 32: Vϕ...
Page 36
P846/EN TD/D Technical Data (TD) 2-10 MiCOM P846 Measurements 3 Fault Record Proforma P -processor signals: PP_kAmax The following data is re corded for any PP_MW relevant elements that operated during a PP_MW3cy fault, and can be viewed in each fault record.
Page 37
Getting Started P846/EN GS/D MiCOM P846 GETTING STARTED Date: June 2011 Hardware Suffix: Software Version: Connection Diagrams: 10P846xx (xx = 01 to 07)
Page 38
P846/EN GS/D Getting Started MiCOM P846...
Page 39
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-1 CONTENTS (GS) 3- GETTING STARTED User interfaces and menu structure Introduction to the relay 1.2.1 Front panel 1.2.1.1 LED indications 1.2.2 Relay rear panel Relay connection and power-up Introduction to the user interfaces and settings options Menu structure 1.5.1...
Page 40
P846/EN GS/D Getting Started (GS) 3-2 MiCOM P846 FIGURES Figure 1: Relay front view Figure 2: Relay rear view Figure 3: Menu structure Figure 4: Front panel user interface Figure 5: Hotkey menu navigation Figure 6: Front port connection Figure 7: PC –...
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-3 GETTING STARTED User interfaces and menu structure The settings and functions of the MiCOM protection relay can be accessed both from the front panel keypad and LCD, and via the front and rear communication ports. Information on each of these methods is given in this section to describe how to start using the relay.
P846/EN GS/D Getting Started (GS) 3-4 MiCOM P846 − Hotkey functionality: − SCROLL Starts scrolling through the various default displays. − STOP Stops scrolling the default display. − For control of setting groups, control inputs and circuit breaker operation −...
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-5 IRIG-B and 2nd Rear Digital Input Connection Comms Board Digital Input Connection Power Supply Connection Rear Comms Port (EIA485) Digital Output Connection Current and Voltage Input Terminal Figure 2: Relay rear view Refer to the wiring diagram in the Installation section for complete connection details.
P846/EN GS/D Getting Started (GS) 3-6 MiCOM P846 The measurement information and relay settings that can be accessed from the three interfaces are summarized in Table 1. Keypad/ LCD Courier DNP3.0 Display & modification of all settings • • Digital I/O signal status •...
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-7 All of the settings in the menu fall into one of three categories; protection settings, disturbance recorder settings, or control and support (C&S) settings. One of two different methods is used to change a setting depending on which category the setting falls into.
If the passwords are lost an emergency password can be supplied - contact Alstom Grid with the relay’s serial number. The current level of access enabled for an interface can be determined by examining the 'Access level' cell in the 'System data' column, the access level for the front panel User Interface (UI), can also be found as one of the default display options.
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-9 System Other default displays 3-phase voltage frequency Alarm messages Date and time Column n Column 1 Column 2 Group 4 Sytem data View records Other column headings Overcurrent Data 1.1 Data 2.1 Data n.1...
P846/EN GS/D Getting Started (GS) 3-10 MiCOM P846 Entry to the menu structure of the rel ay is mad e from the default display and is not affected if the display is showing the ‘Ala ent’ message. rms/Faults pres 1.8.2...
Courier communication protocol only. Courier is the communication language developed by Alstom Grid to allow communication with its range of protection relays. The front port is particularly designed for use with the relay settings program MiCOM S1 that is a...
Page 51
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-13 Figure 6: Front port connection The relay is a Data Communication Equipment (DCE) device. Thus the pin connections of the relay’s 9-pin front port are as follows: Pin no. 2 Tx T ransmit data Pin no.
P846/EN GS/D Getting Started (GS) 3-14 MiCOM P846 Figure 7: PC – relay signal connection Having made the physical connection from the relay to the PC, the PC’s communication settings must be configured to match those of the relay. The relay’s communication settings...
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-15 1.10 MiCOM S1 relay communications basics The front port is particularly designed for use with the relay settings pr ogram MiCOM S1 that is a Windows 98, Windows NT4.0, Windows 2000 or Windows XP based software package.
P846/EN GS/D Getting Started (GS) 3-16 MiCOM P846 and click on the required Px40 series 1.10.3 Open communication link with relay To open the communications link from S1 to the P846 relay the following procedure must be followed: First the communication setup must be adjusted if necessary. In the "Device" menu, select "Communications Setup…"...
Page 55
Getting Started P846/EN GS/D MiCOM P846 (GS) 3-17 Figure 8: Communication set-up screen When the communications setup is correct the link with the relay can be initialized. In the "Device" me nu, select "Open Connection…" This brings up a prompt for the ad dress of the relay to be interrogated (for front port access, the relay address is always “1”...
P846/EN GS/D P846/EN GS/D Getting Started Getting Started (GS) 3-18 (GS) 3-18 MiCOM P846 MiCOM P846 1.10.4 1.10.4 Off-line use of MiCOM S1 Off-line use of MiCOM S1 As well as being used for the on-line editing of settings, MiCOM S1 can also be used as an As well as being used for the on-line editing of settings, MiCOM S1 can also be used as an off-line tool to prepare settings without access to the relay.
Page 58
P846/EN ST/D Getting Started MiCOM P846...
Page 59
Settings P846/EN ST/D MiCOM P846 (ST) 4-1 CONTENTS (ST) 4- SETTINGS Relay settings configuration 1.1.1 Default settings restore Protection application settings 1.2.1 CT/VT ratios 1.2.2 Supervision (VTS) Control and support settings 1.3.1 System data 1.3.2 Circuit breaker control 1.3.3 Date and time 1.3.4...
Settings P846/EN ST/D MiCOM P846 (ST) 4-3 SETTINGS The P846 must be configured to the system and application by means of appropriate settings. The sequence in which the settings are listed and described in this chapter will be the protection setting, control and configuration settings and the disturbance recorder settings (see chapter P846/EN GS for the detailed relay menu map).
Page 62
P846/EN ST/D Settings (ST) 4-4 MiCOM P846 Menu Text Default Setting Available Settings Setting Group 1 Enabled Enabled or Disabled If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting (paste).
Settings P846/EN ST/D MiCOM P846 (ST) 4-5 Menu Text Default Setting Available Settings Enabled/Disabled/Hotkey Direct Access Enabled only/CB Cntrl. only Defines what CB control direct access is allowed. Enabled implies control via menu, hotkeys etc. LCD Contrast 0…31 Sets the LCD contrast.
P846/EN ST/D Settings (ST) 4-6 MiCOM P846 Setting Range Menu Text Default Setting Step Size Min. Max. CVT Enabled Enabled Disabled/Enabled To enable (activate) or disable (turn off) the potential transformer alarm function. CVT Threshold 0.1% Sets a maximum threshold for the ratio of negative sequence voltage V2 over the sum of positive and negative sequence voltages (V1 +V2).
Page 65
Settings P846/EN ST/D MiCOM P846 (ST) 4-7 Setting Range Menu Text Default Setting Step Size Min. Max. VTS Ι2> Inhibit 100A 100A 1000A The setting is used to override a voltage supervision block in the event of a fault occurring on the system with negative sequence current above this setting which could trigger the voltage supervision logic.
Page 66
P846/EN ST/D Settings (ST) 4-8 MiCOM P846 Setting Range Menu Text Default Setting Step Size Min. Max. Comms. Level 2 Displays the conformance of the relay to the Courier Level 2 comms. Relay Address 1 Sets the first rear port relay address.
Settings P846/EN ST/D MiCOM P846 (ST) 4-9 Setting Range Menu Text Default Setting Step Size Min. Max. Access Level Displays the current access level. Level 0 - Password 1 or 2 required - Read access to all settings, alarms, event records...
Page 68
P846/EN ST/D Settings (ST) 4-10 MiCOM P846 1.3.3 Date and time Displays the date and time as well as the battery condition. Setting Range Menu Text Default Setting Step Size Min. Max. Date/Time Data Displays the relay’s current date and time.
Settings P846/EN ST/D MiCOM P846 (ST) 4-11 Menu Text Default Setting Available Settings DDB 31 - 0 11111111111111111111111111111111 Allows the user to individually select whether DDB signals 0 to 31 create an event or not. Setting a ‘1’ will allow an event to be generated; setting a ’0’ will prevent an event being generated.
P846/EN ST/D Settings (ST) 4-12 MiCOM P846 Menu Text Default Settings Available settings MEASUREMENT SETUP Remote2 Values Primary Primary/Secondary The setting defines whether the values measured via the Second Rear Communication port are displayed in primary or secondary terms. 1.3.6...
Settings P846/EN ST/D MiCOM P846 (ST) 4-13 Setting Range Menu Text Default Setting Step Size Min. Max. COMMUNICATIONS 1200 bits/s, 2400 bits/s, 4800 bits/s, 9600 RP1 Baud Rate 19200 bits/s bits/s, 19200 bits/s or 38400 bits/s This cell controls the communication speed between relay and master station.
P846/EN ST/D Settings (ST) 4-14 MiCOM P846 1.3.7 Commissioning tests There are menu cells which allow the status of the opto-isolated inputs, output relay contacts, internal digital data bus (DDB) signals and user-programmable LEDs to be monitored. Additionally there are cells to test the operation of the output contacts, user- programmable LEDs and, where available, the auto-reclose cycles.
Settings P846/EN ST/D MiCOM P846 (ST) 4-15 Menu Text Default Setting Available Settings 0 = Not Operated Test Pattern 00000000000000000000000000000000 1 = Operated This cell is used to select the output relay contacts that will be tested when the ‘Contact Test’...
P846/EN ST/D Settings (ST) 4-16 MiCOM P846 Setting Range Menu Text Default Setting Step Size Min. Max. 24 - 27, 30 - 34, 48 - 54, 110 - 125, Opto Input 1 24 - 27 220 - 250 Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.
Settings P846/EN ST/D MiCOM P846 (ST) 4-17 1.3.10 Control input labels Menu Text Default Setting Setting Range Step Size CTRL I/P LABELS Control Input 1 Control Input 1 16 Character Text Setting to change the text associated with each individual control input. This text will be displayed when a control input is accessed by the hotkey menu, or it can be displayed in the programmable scheme logic.
Page 76
P846/EN ST/D Settings (ST) 4-18 MiCOM P846 Setting Range Menu Text Default Setting Step Size Min. Max. No Trigger except Dedicated Trip Inputs 1 to 32 Trigger Relay O/P’s which No Trigger, Trigger L/H, Trigger H/L are set to Trigger Any of the digital channels may be selected to trigger the disturbance recorder on either a low to high or a high to low transition.
Page 79
Operation P846/EN OP/D MiCOM P846 (OP) 5-1 CONTENTS (OP) 5- OPERATION OF INDIVIDUAL PROTECTION FUNCTIONS Requirements for fast topology detection The open-line detection problem Principles of operation 1.3.1 Data acquisition 1.3.2 Kalman filtering stage 1.3.3 Preprocessing stage 1.3.4 Fuzzy-logic engine stage 1.3.4.1...
Page 80
P846/EN OP/D Operation (OP) 5-2 MiCOM P846 IGURES Figure 1: Configuration of a line in a HV/EHV substation Figure 2: DLO processing logic Figure 3: Principle of the self-tuned Kalman-filter with p harmonics and q non-harmonics spectral lines 6 Figure 4:...
Operation P846/EN OP/D MiCOM P846 (OP) 5-3 OPERA TION OF INDIVIDUAL PROTECTION FUNCTIONS Requir ements for fast topology detection In the deregulated and market driven energy industry, modern power systems need to erate closer to their d esign limits. System topology is becoming more complex becaus w interconnections are being added to satisfy the deregulated flow of energy.
Page 82
P846/EN OP/D Operation (OP) 5-4 MiCOM P846 Figure 1 shows the typical configuration of a line in a HV/EHV substation with its capacitive voltage transformer CVT and current transformers (CT1, CT2 for breakers and CT3 for shunt reactor) that are connected to the DLO analog inputs (the shunt reactor current is needed to...
Operation P846/EN OP/D MiCOM P846 (OP) 5-5 Principles of operation The DLO algorithm is made up of five major building blocks as shown on figure 2: Line voltages Anti - alias Kalman Pre - Fuzzy - filtering Filter processor logic Engine &...
P846/EN OP/D Operation (OP) 5-6 MiCOM P846 1.3.2 Kalman filtering stage The advantage and superiority of this filtering technique in the present application i s its capability to provide signal components at spectral frequencies other than the fundamental and its harmonics. More specifically, its benefits are: It is possible to make the Kalman filter self-tuned to the fundamental frequency without any hardware modification.
Operation P846/EN OP/D MiCOM P846 (OP) 5-7 P4088ENa Figure 4: Frequency response of the Kalman-filter used in the DLO The fundamental positive and negative sequence voltage and current phasors and the DC components are the signals that are transferred from the Kalman filter to the next stage of the algorithm, the preprocessor.
P846/EN OP/D Operation (OP) 5-8 MiCOM P846 1.3.4 Fuzzy-logic engine stage Although fast and reliable relaying algorithms can be achieved by applying conventional Boolean logic, conflicts may arise in doubtful cases. For instance, during line energization at no-load, CVT (Capacitive Voltage Transformers) induced electro-magnetic transients may suggest that the active power is not zero (line closed) while the line is actually open.
Operation P846/EN OP/D MiCOM P846 (OP) 5-9 Figure 6: Fuzzification of two decision features 1.3.4.2 Fuzzy logic inference on the decision features, using sixteen rules or criteria The inference engine contains 16 rules unevenly divided into 11 rules for detecting the open- line status under various circumstances (’Open’...
Page 88
P846/EN OP/D Operation (OP) 5-10 MiCOM P846 Fortunately, even though this critical operating point is feasible, it is very sensitive for short lines (30 km), the typical sensitivities being 45% per degree of angle shift and 25% Mvar per unit of voltage ratio. The above considerations suggest therefore that even though the critical operating point is feasible, it is difficult to achieve and even more difficult to sustain in steady-state.
Operation P846/EN OP/D MiCOM P846 (OP) 5-11 The fuzzy rules operate according to physical principles. For example, we may define with fuzzy variables "Active power" and "DeltaP" presented in figure 6 the following rules: A steady state rule for security:...
P846/EN OP/D Operation (OP) 5-12 MiCOM P846 OPERATION OF NON PROTECTION FUNCTIONS Trip LED logic As previously mentioned in section 1.1, the DLO is made for monitoring the status of a transmission line. Upon detection of an open line, the DLO will close its Output contact R3 and will keep it open when the line is closed.
Operation P846/EN OP/D MiCOM P846 (OP) 5-13 2.2.1 Loss of one or two phase voltages The VTS feature within the relay rates on detection of negative phase sequence (nps voltage without the presence of nega tive phase sequence current. This gives operation fo the loss of one or two phase voltages.
P846/EN OP/D Operation (OP) 5-14 MiCOM P846 • VA>, VB>, VC> level detectors are operating on phase volta ges and have fixed setting: • Pickup level 30V (Vn 100/120V) or 120V (380/440V) • Drop off level 10V (Vn 100/120V) or 40V (Vn 380/440V) •...
Operation P846/EN OP/D MiCOM P846 (OP) 5-15 The DLO provides a mean to detec t asymmetry of the CVT measurements and to output an alarm when a settable threshold is exceeded. The asymmetry is detected with the following index: Asymmetry index: based on the positive and negative sequence voltages.
P846/EN OP/D Operation (OP) 5-16 MiCOM P846 INTSIG Phase A Undercurrent Operation 20ms INTSIG Phase A Undervoltage Operation & DDB Pole Dead A (355) DDB CB Open A ph (775) INTSIG Phase B Undercurrent Operation 20ms INTSIG Phase B Undervoltage Operation &...
Page 95
Operation P846/EN OP/D MiCOM P846 (OP) 5-17 Should both sets of contacts be closed, only one of the following two conditions would apply: − Auxiliary contacts / wiring defective − Circuit Breaker (CB) is defective If any of the above conditions exist, an alarm will be issued after a 5s time delay. A n...
Operation P846/EN OP/D MiCOM P846 (OP) 5-19 Circuit breaker control The relay includes the following options fo r control of a single circuit breaker: • Local tripping and closing, via the relay menu or hotkeys • Local tripping and closing, via relay opto-isolated inputs •...
Page 98
P846/EN OP/D Operation (OP) 5-20 MiCOM P846 For a manual reclosure there is a CB Healthy check if required. This facility accepts an input to one of the relays opto-isolators to indicate that the breaker is capable of closing (circuit breaker energy for example).
Page 99
Operation P846/EN OP/D MiCOM P846 (OP) 5-21 Disable SET: CB Control by Local Remote Local & remote Opto Local & Opto Remote & Opto Enable opto initiated CB trip and close Local & Remote & Opto DDB Control Trip (698)
P846/EN OP/D Operation (OP) 5-22 MiCOM P846 2.7.1 CB control using hotkeys The hotkeys allow direct access to the manual trip and close commands, bypassing the SYSTEM DATA menu. Select TRIP or CLOSE, then confirm. If a trip is executed a screen with the CB status appears once the command has been completed.
Page 101
Operation P846/EN OP/D MiCOM P846 (OP) 5-23 The Control Input commands can be found in the ‘Control Input’ menu. In the ‘Ctrl. Ι/P status’ menu cell there is a 32 bit word which represent the 32 control input commands. The status of the 32 control inputs can be read from this 32-bit word.
P846/EN OP/D Operation (OP) 5-24 MiCOM P846 Changing setting groups The setting groups can be changed either via opto inputs or via a menu selection. In the Configuration column if ‘Setting Group – select via optos’ is selected then optos 1 and 2, which are dedicated for setting group selection, can be used to select the setting group as shown in the table below.
Page 103
Operation P846/EN OP/D MiCOM P846 (OP) 5-25 To avoid the event buffer from being filled with unnecessary time sync. events, it is possible to ignore any event that is generated by the time sync. opto input. This can be done by...
Page 107
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-1 CONTENTS (AP) 6- INTRODUCTION Protection of power systems APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS Open line detector function Application Setting guidelines DLO simulator and some test cases 2.4.1 Typical test cases AUXILIARY SUPPLY FUSE RATING...
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-3 INTRODUCTION Protection of power systems Modern power systems are operating nearer to their stability limits, in order to meet the increased demands from a deregulated market. In order to operate closer to these limits, fast discriminatory protection is required to detect and react quickly to changes in the power system.
P846/EN AP/D Application Notes (AP) 6-4 MiCOM P846 APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS The following sections detail the individual protection functions in addition to where and how they may be applied. Open line detector function Traditional methods for detecting an open line condition are the following: Trip signals coming from line protection relays: It consists in monitoring all protection signals likely to order the opening of the line.
Page 111
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-5 Vbase Base Power Line Charging Line Charging Line Charging (kV) (MW) (MVar/km) (p.u./km) (km/p.u.) 0.047 0.00131 0.062 0.00129 0.081 0.00125 0.160 0.00125 0.178 0.00128 0.532 0.00127 1.12 0.00129 2081 2.67 0.00128 2276 2.92...
P846/EN AP/D Application Notes (AP) 6-6 MiCOM P846 The DLO must detect the open-close status of a line at both ends for the Reliability: following categories of phenomena: − Line closing or opening at local end (with or without a shunt reactor connected) −...
DLO simulator and some test cases The DLOSimulator is a program that s imulates and reproduces the exact behavior of the MiCOM P846 relay. It is running on Windows and either processes Comtrade and Matlab data files. The user si mulates test cases with the graphical interface GUI shown on figure 2.
Page 114
P846/EN AP/D Application Notes (AP) 6-8 MiCOM P846 Figure 2: DLOSimulator graphical user interface 1 – Input data file A – Format Two types of data files are possible Matlab: extension .mat Comtrade (ASCII or binary): extensions .cfg and .dat B –...
Page 115
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-9 Matlab files default names: Variable name for time: t Seconds Variable name for vabc: vabc (matrix) or [va vb vc] (3 vectors) Volts Variable name for iabc: iabc (matrix) or [ia ib ic] (3 vectors)
P846/EN AP/D Application Notes (AP) 6-10 MiCOM P846 2.4.1 Typical test cases Test cases 1 to 5 show the performance of the DLO for five different situations. For each of these, the line voltages, the feeder breaker currents and the shunt reactor currents are plotted as the relay analog inputs while the fault detector signal and open line decision are the two digital outputs.
Page 117
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-11 A long line being closed and opened at the local end while remote end is kept Case 2: open. Line parameters: Nominal frequency (Hz): 60.0 Nominal line voltage (kV): Line charging (MVar):...
Page 118
P846/EN AP/D Application Notes (AP) 6-12 MiCOM P846 Short line with low transit being opened (no fault) at remote end Case 3: Line parameters: Nominal frequency (Hz): 60.0 Nominal line voltage (kV): Line charging (MVar): Line base power (MVA): 2081...
Page 119
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-13 Long line with normal transit being opened at both ends to clear a fault Case 4: Line parameters: Nominal frequency (Hz): 60.0 Nominal line voltage (kV): Line charging (MVar): Line base power (MVA):...
Page 120
P846/EN AP/D Application Notes (AP) 6-14 MiCOM P846 Case 5: 100% shunt compensated line with normal transit being opened at both ends Line parameters: Nominal frequency (Hz): 60.0 Nominal line voltage (kV): Line charging (MVar): Line base power (MVA): 2081...
Application Notes P846/EN AP/D MiCOM P846 (AP) 6-15 AUXILIARY SUPPLY FUSE RATING In the Safety section of this manual, the maximum allowable fuse rating of 16A is quoted. To allow time grading with fuses upstream, a lower fuselink current rating is often preferable.
To access the Px40 PSL Editor menu click on The PSL Editor module enables you to connect to any MiCOM ALSTOM device front port, retrieve and edit its Programmable Scheme Logic files and send the modified file back to a...
Page 128
P846/EN PL/D Programmable Logic (PL) 7-4 MiCOM P846 How to use MiCOM ALSTOM Px40 PSL editor With the Px40 PSL Module you can: • Start a new PSL diagram • Extract a PSL file from a Px40 IED • Open a diagram from a PSL file •...
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-5 1.5.1 Standard tools • For file management and printing. 1.5.2 Alignment tools • To snap logic elements into horizontally or vertically aligned groupings. 1.5.3 Drawing tools • To add text comments and other annotations, for easier reading of PSL schemes.
Page 130
P846/EN PL/D Programmable Logic (PL) 7-6 MiCOM P846 Output Use an output from PSL to drive a fixed logic scheme. Control In Create an input signal to logic that can be operated from an external command. Fault Record Trigger Create a fault record trigger.
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-7 Rules for Linking Symbols Links can only be started from the output of a signal, gate, or conditioner, and can only be ended on an input to any element. Since signals can only be either an input or an output then the concept is somewhat different.
P846/EN PL/D Programmable Logic (PL) 7-8 MiCOM P846 1.6.5 Control in signal properties Control In There are 32 control inputs which can be activated via the relay menu or rear communications. When the control input is activated an associated DDB within the PSL will be asserted high.
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-9 1.6.9 LED conditioner properties Each LED can be conditioned to be latching or non-latching. 1. Select the LED name from the LED Name list (only shown when inserting a new symbol). 2. Select if the LED should be latching using the Latching check box.
P846/EN PL/D Programmable Logic (PL) 7-10 MiCOM P846 1. Select the contact name from the Contact Name list (only shown when inserting a new symbol). 2. Choose the conditioner type required in the Mode tick list. 3. Set the Pickup Time (in milliseconds), if required.
Page 135
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-11 1. Select the Gate type AND, OR, or Programmable. 2. Set the number of inputs to trigger when Programmable is selected. 3. Select if the output of the gate should be inverted using the Invert Output check box. An...
P846/EN PL/D Programmable Logic (PL) 7-12 MiCOM P846 Description of logic nodes DDB No. English Text Source Description Signal which shows the state of output relay 1 Output Label 1 (settable) Output Conditioner (0 = de-energized, 1 = energized) Signal which shows the state of output relay 2 to 32 Output Label 2 …...
Page 137
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-13 DDB No. English Text Source Description 273 - 283 Reserved F out of range Frequency Tracking Frequency Not Found by the frequency tracking 285 - 301 Reserved Triggers User Alarm 1 message to be alarmed on LCD...
Page 138
P846/EN PL/D Programmable Logic (PL) 7-14 MiCOM P846 DDB No. English Text Source Description Commissioning Tests - automatically places relay in Test Mode Test Mode For IEC-870-5-103 protocol only, used for "Command Command Blocking Blocking" (relay ignores SCADA commands) For IEC-870-5-103 protocol only, used for "Monitor Monitor Blocking Blocking"...
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-15 DDB No. English Text Source Description tBF2 Trip 3Ph - three phase output from circuit Bfail2 Trip 3ph CB Fail breaker failure logic, stage 2 timer 696 - 697 reserved Control Trip – operator trip instruction to the circuit...
Page 140
P846/EN PL/D Programmable Logic (PL) 7-16 MiCOM P846 1.8.1 Relay output contact mapping The default mappings for each of the relay output contacts are as shown in the following table: Relay Contact P846 Relay Text Function Number Output R1 CVT Alarm output...
Page 141
Programmable Logic P846/EN PL/D MiCOM P846 (PL) 7-17 PSL DATA column The P846 relay contains information to assist in the tracking of changes to the application specific PSL. In conjunction with the password control of the relay, it will provide security against changes to protection scheme operation caused by PSL modification by unauthorized personnel.
Page 143
Measurements and Recording P846/EN MR/D MiCOM P846 MEASUREMENTS AND RECORDING Date: June 2011 Hardware Suffix: Software Version: Connection Diagrams: 10P846xx (xx = 01 to 07)
Page 144
P846/EN MR/D Measurements and Recording MiCOM P846...
Page 145
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-1 CONTENTS (MR) 8- MEASUREMENTS AND RECORDING Introduction Event & fault records 1.2.1 Types of event 1.2.1.1 Change of state of opto-isolated inputs 1.2.1.2 Change of state of one or more output relay contacts 1.2.1.3...
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-3 MEASUREMENTS AND RECORDING Introduction The P846 is equipped with integral measurements, event, fault and disturbance recording facilities suitable for analysis of complex system disturbances. The relay is flexible enough to allow for the programming of these facilities to specific user application requirements and are discussed below.
P846/EN MR/D Measurements and Recording MiCOM P846 (MR) 8-4 For extraction from a remote source via communications, refer to the SCADA Communications chapter (P846/EN SC), where the procedure is fully explained. 1.2.1 Types of event An event may be a change of state of a control input or output relay, an alarm condition, setting change etc.
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-5 Alarm Condition Event Text Event Value Battery Fail Battery Fail ON/OFF Bit position 0 in 32 bit field Field Voltage Fail Field Volt Fail ON/OFF Bit position 1 in 32 bit field Setting Group via Opto Setting Grp.
LCD. The following shows an example of how various events appear when displayed using MiCOM S1: - Monday 03 January 2006 15:32:4 9 GMT Open Line Detect ON ALSTOM: MiCOM P846 Model Number: P846318 B4M0310J Address: 001 Column: 0F Row: 2B...
Page 151
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-7 - Monday 03 January 2005 15:33:11 GMT Logic Inputs ALSTOM: MiCOM P846 Model Number: P846318B4M0300J Address: 001 Column: 00 Row: 20 Event Type: Logic input changed state Event Value: 0000111000001010 - Monday 03 January 2005 15:34:54 GMT Output Contacts...
P846/EN MR/D Measurements and Recording MiCOM P846 (MR) 8-8 Disturbance recorder The integral disturbance record er has an area of memory specifically set aside for record torag e. The number of records that may be stored by the relay is dependent upon the selected recording duration.
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-9 Setting Range Menu Text Default Setting Step Size Min. Max. No Trigger except Dedicated Trip Inputs 1 to 32 Trigger Relay O/P’s which No Trigger, Trigger L/H, Trigger H/L are set to Trigger Any of the digital channels may be selected to trigger the disturbance recorder on either a low to high or a high to low transition.
Page 154
P846/EN MR/D Measurements and Recording MiCOM P846 (MR) 8-10 1.4.1 Measured voltages and currents The relay produces both phase to ground and phase to phase voltage and current values. They are produced direc tly from the DFT ( Discrete Fourier Transform) used by the relay...
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-11 1.4.5 Demand values The relay produces fixed, rolling and peak demand values, using the reset demand menu cell. It is possible to reset these quantities via the user interface or the remote communications.
P846/EN MR/D Measurements and Recording MiCOM P846 (MR) 8-12 Menu Te Default Settings Available settings MEASUREMENT SETUP Roll Sub Period 30 minutes 1 to 99 minutes step 1 minute These two settings ar e used to set the length of the window used for the calculation of rolling demand quantitie Num.
Page 157
Measurements and Recording P846/EN MR/D MiCOM P846 (MR) 8-13 MEASUREMENTS 1 MEASUREMENTS 2 VAN Phase Angle 0 deg. 3 Phase VA Line 0 VAr VBN Magnitude 3Ph PF Li VBN Phase Angle 0 deg. APh PF Line VCN Magnitude BPh PF Line VCN Phase Angle 0 deg.
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-3 FIRMWARE DESIGN Hardware overview The relay hardware is based on a modular design whereby the relay is made up of an assemblage of several modules that are drawn from a standard range. Some modules are essential while others are optional depending on the user’s requirements.
P846/EN FD/D Firmware Design (FD) 9-4 MiCOM P846 1.2.1 Real-time operating system The real time operating system is used to provide a framework for the different parts of the relay’s software to operate within. To this end the software is split into tasks.
Page 165
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-5 1.2.2 System services software The system services software provides the low-level control of the relay hardware. For example, the system services software controls the boot of the relay’s software from the non-volatile flash EPROM memory at power-on, and provides driver software for the user interface via the LCD and keypad, and via the serial communication ports.
Page 166
P846/EN FD/D Firmware Design (FD) 9-6 MiCOM P846 1.3.2 Co-processor board The processor used on the second board is the same as that used on the main processor board. The second processor board has provision for fast access (zero wait state) SRAM for use with both program and data memory storage.
P846/EN FD/D Firmware Design (FD) 9-8 MiCOM P846 In the Opto Config. menu the nominal battery voltage can be selected for all opto inputs by selecting one of the five standard ratings in the Global Nominal V settings. If Custom is selected then each opto input can individually be set to a nominal voltage value.
Page 169
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-9 The power supply board incorporates inrush current limiting. This limits the peak inrush current, during energization, to approximately 10A. 1.3.5.2 Output relay board The output relay board holds eight relays, six wit h normally open contacts and two with changeover contacts.
Page 171
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-11 1.3.6 Mechanical layout The case materials of the relay are constructed from pre-finished steel that has a conductive covering of aluminum and zinc. This provides good earthing at all joints giving a low impedance path to earth that is essential for performance in the presence of external noise.
P846/EN FD/D Firmware Design (FD) 9-12 MiCOM P846 Protection & Control Measurements and event, fault Software & disturbance records Disturbance recorder task Protection Programable & task fixed scheme logic Platform Software Fourier signal Protection Event, fault, Remote processing algorithms communications...
Page 173
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-13 1.4.3.1 Record logging The logging function is provided to store all alarms, events, faults and maintenance records. The records for all of these incidents are logged in battery backed-up SRAM in order to provide a non-volatile log of what has happened.
P846/EN FD/D Firmware Design (FD) 9-14 MiCOM P846 P4091ENa Figure 5: Frequency response of the DLO Kalman filter 1.4.6 Fourier filtering All backup protection and measurement functions use one cycle fourier digital filtering to extract the power frequency component. This filtering is performed on the main processor board.
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-15 1.4.6.2 Event and fault recording A change in any digital input signal or protection element output signal causes an event record to be created. When this happens, the protection and control task sends a message to the supervisor task to indicate that an event is available to be processed and writes the event data to a fast buffer in SRAM which is controlled by the supervisor task.
P846/EN FD/D Firmware Design (FD) 9-16 MiCOM P846 (1m)Z P0124ENa Figure 6: Two machine equivalent circuit From this diagram: Vp = mΙpZr + ΙfRf …(equation 1) The fault location, m, can be found if Ιf can be estimated allowing equation 1 to be solved.
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-17 1.5.4.1 Obtaining the vectors Different sets of vectors are chosen depending on the type of fault identified by the phase selection algorithm. The calculation using equation 1 is applied for either a phase to ground fault or a phase to phase fault.
Page 179
Firmware Design P846/EN FD/D MiCOM P846 (FD) 9-19 1.6.1 Start-up self-testing The self-testing which is carried out when the relay is started takes a few seconds to complete, during which time the relay’s protection is unavailable. This is signaled by the ‘Healthy’...
Page 180
P846/EN FD/D Firmware Design (FD) 9-20 MiCOM P846 • The battery status • The level of the field voltage • The integrity of the digital signal I/O dat a from the opto-isolated inputs and the relay contacts is checked by the data acquisition function every time it is executed.
Page 183
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-1 CONTENTS (CM) 10- INTRODUCTION RELAY COMMISSIONING TOOLS Opto I/P status Relay O/P status Test port status LED status Monitor bits 1 to 8 Test mode Test pattern Contact test Test LEDs 2.10 Using a monitor/download port test box...
Page 184
P846/EN CM/D Commissioning (CM) 10-2 MiCOM P846 5.2.8 Rear communi cations port 5.2.8.1 Courier communications 5.2.8.2 DNP 3.0 interface 5.2.9 Second rear comm unications port 5.2.9.1 K-Bus configuration 5.2.9.2 EIA(RS)485 configura tion 5.2.9.3 EIA(RS)232 configuration 5.2.10 Current inputs 5.2.11 Voltage inputs...
(CM) 10-3 INTRODUCTION The MICOM P846 open line detecting relays are fully numerical in their design, implementing all protection and non-protection functions in software. The relays employ a high degree of self-checking and, in the unlikely event of a failure, will give an alarm. As a result of this, the commissioning tests do not need to be as extensive as with non-numeric electronic or electro-mechanical relays.
P846/EN CM/D Commissioning (CM) 10-4 MiCOM P846 RELAY COMMISSIONING TOOLS To help minimize the time required to test MiCOM relays the relay provides several test facilities under the ‘COMMISSION TESTS’ menu heading. There are menu cells which allow the status of the opto-isolated inputs, output relay contacts, internal digital data bus (DDB) signals and user-programmable LEDs to be monitored.
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-5 Relay O/P status This menu cell displays the status of the digital data bus (DDB) signals that result in energization of the output relays as a binary string, a ‘1’ indicating an operated state and ‘0’...
A monitor/download port test box containing 8 LEDs and a switchable audible indicator is available from Alstom Grid, or one of their regional sales offices. It is housed in a small plastic box with a 25-pin male D-connector that plugs directly into the relay’s monitor/download port.
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-7 SETTING FAMILIARIZATION When commissioning a P846 relay for the first time, sufficient time should be allowed to become familiar with the method by which the settings are applied. The Getting Started section (P846/EN GS) contains a detailed description of the menu structure of P846 relays.
P846/EN CM/D Commissioning (CM) 10-8 MiCOM P846 EQUIPMENT REQUIRED FOR COMMISSIONING Minimum equipment required Multifunctional dynamic current and voltage injection test set. Multimeter with suitable ac current range, and ac and dc voltage ranges of 0 – 440V and 0 – 250V respectively.
Note: In the event that the password has been lost, a recovery password can be obtained from Alstom Grid by quoting the serial number of the relay. The recovery password is unique to that relay and is unlikely to work on any other relay.
P846/EN CM/D Commissioning (CM) 10-10 MiCOM P846 Carefully examine the relay to see that no physical damage has occurred since installation. Ensure that the case earthing connections, bottom left-hand corner at the rear of the relay case, are used to connect the relay to a local earth bar using an adequate conductor.
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-11 Heavy duty terminal block P1042ENa Figure 2: Location of securing screws for heavy duty terminal blocks 5.1.3 Insulation Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation.
P846/EN CM/D Commissioning (CM) 10-12 MiCOM P846 5.1.4 External wiring Check that the external wiring is correct to the relevant relay diagram and scheme diagram. Ensure as far as practical that phasing/phase rotation appears to be as expected. The relay diagram number appears on the rating label under the top access cover on the front of the relay.
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-13 5.2.1 Watchdog contacts Using a continuity tester, check the watchdog contacts are in the states given in Table 2 for an energized relay. 5.2.2 LCD front panel display The liquid crystal display is designed to operate in a wide range of substation ambient temperatures.
Page 196
P846/EN CM/D Commissioning (CM) 10-14 MiCOM P846 5.2.3.2 Without an IRIG-B signal If the time and date is not being maintained by an IRIG-B signal, ensure that cell [0804: IRIG-B Sync.] is set to ‘Disabled’. Set the date and time to the correct local time and date using cell [0801: DATE and TIME, Date/Time].
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-15 Terminals Supply Rail P846 +ve (positive) M7 & M8 –ve (positive) M9 & M10 Table 4: Field voltage terminals 5.2.6 Input opto-isolators This test checks that all the opto-isolated inputs on the relay are functioning correctly.
P846/EN CM/D Commissioning (CM) 10-16 MiCOM P846 5.2.8 Rear communications port This test shou ld only be performed where the relay is to be accessed from a remote location and will vary depending on the commu nications standard being adopted.
Check that communications can be established with this relay using the portable PC. 5.2.9.2 EIA(RS)485 configuration If an EIA(RS)485 to EIA(RS)232 convertor (Alstom Grid CK222) is installed, con nect a portable PC running the appropriate software (e.g. MiCOM S1) to the EIA(RS)232 side of the...
P846/EN CM/D Commissioning (CM) 10-18 MiCOM P846 Connections to the second rear port configured for EIA(RS)232 operation can be made using a screened multi-core communication cable up to 15m long, or a total capacitance of 2500pF. The cable should be terminated at the relay end with a 9-way, metal shelled, D- type male plug.
Page 201
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-19 Cell in MEASUREMENTS 1 column Voltage applied to [021A: VAN Magnitude] D19 – D22 [021C: VBN Magnitude] D20 - D22 [021E: VCN Magnitude] D21 – D22 Table 9: Voltage input terminals The measured voltage values on the relay LCD or a portable PC connected to the front communication port will either be in primary or secondary volts.
P846/EN CM/D Commissioning (CM) 10-20 MiCOM P846 SETTING CHECKS The setting checks ensure that all of the application-specific relay settings (i.e. both the relay’s function and programmable scheme logic settings), for the particular installation, have been correctly applied to the relay.
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-21 When the relay is energized with no input volts or currents applied, the ‘Open Line Detect’ trip will be active. Connect the three voltage outputs of the test set to the three phase voltage transformer inputs of the relay and apply rated voltage to terminals C19, C20 and C21.
Page 204
P846/EN CM/D Commissioning (CM) 10-22 MiCOM P846 − Step through the settings using the relay’s operator interface and compare them with the original application-specific setting record. Ensure that all protection elements required have been ENABLED in the CONFIGURATION column. Unless previously agreed to the contrary, the application-specific programmable scheme...
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-23 ON-LOAD CHECKS The objectives of the on-load checks are to: − Confirm the external wiring to the current and voltage inputs is correct. − Check the polarity of the line current transformers at each end is consistent.
P846/EN CM/D Commissioning (CM) 10-24 MiCOM P846 7.1.2 Current connections Measure the current transformer secondary values for each input using a multimeter connected in series with the corresponding relay current input. Check that the current transformer polarities are correct by measuring the phase angle...
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-25 FINAL CHECKS The tests are now complete. Remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the relay in order to perform the wiring verification tests, it should be ensured that all connections (wiring, fuses and links) are replaced in accordance with the relevant external connection or scheme diagram.
P846/EN CM/D Commissioning (CM) 10-26 MiCOM P846 COMMISSIONING TEST RECORD Date: Engineer: Station: Circuit: System Frequency: VT Ratio: CT Ratio (tap in use): Front Plate Information Open Line Detector Relay P846 Model number Serial number Rated current In Rated voltage Vn...
Page 209
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-27 *Delete as appropriate Have all relevant safety instructions been Yes* followed? Product Checks With the relay de-energized 5.1.1 Visual inspection Relay damaged? Yes* Rating information correct for installation? Yes* Case earth installed? Yes* Yes* 5.1.2...
Page 210
P846/EN CM/D Commissioning (CM) 10-28 MiCOM P846 5.2.4 Light emitting diodes Alarm (yellow) LED working? Yes* Out of service (yellow) LED working? Yes* 5.2.4.3 All 18 programmable LEDs working? Yes* 5.2.5 Field supply voltage Value measured between terminals 8 and 9 V dc 5.2.6...
Page 213
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-31 5.2.10 Voltage inputs Displayed voltage Primary* Secondary* Main VT ratio N/A* Input VT Applied Value isp yed val Setting Checks Application-spec ific function settings applied? Yes* Yes* Application-specific programmable scheme logic settings applied?
Page 214
P846/EN CM/D Commissioning (CM) 10-32 MiCOM P846 Yes* Circuit breaker operations counter reset? N/A* Yes* Current counters reset? N/A* Event records reset? Yes* Fault records reset? Yes* Disturbance records reset? Yes* Alarms reset? Yes* LEDs reset? Yes* Yes* Secondary front cover replaced?
Page 215
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-33 COMMENTS # (# Optional, for site observations or utility-specific notes). Commissioning Engineer Customer Witness Date: Date:...
Page 216
P846/EN CM/D Commissioning (CM) 10-34 MiCOM P846 SETTING RECORD Date: Engineer: Station: Circuit: System Frequency: VT Ratio: CT Ratio (tap in use): Front Plate Information Open line detection relay P846 Model number Serial number Rated current In Rated voltage Vn...
Page 217
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-35 0700 CONTROL Disabled* Local* Remote* 0701 CB Control by Local + Remote* Opto* Opto + Remote* Opto + Rem. + Local 0702 Close Pulse Time 0703 Trip Pulse Time 0705 Man Close Delay...
Page 218
P846/EN CM/D Commissioning (CM) 10-36 MiCOM P846 0A00 CT AND VT R ATIOS 0A01 Main VT Prim 0A02 Main VT Sec' 0A07 Phase Primary 0A08 Phase Sec'y. 0A10 Phase CT2 Prim’y 0A11 Phase CT2 Sec'y. 0AF0 CVT Enable Disabled* Enabled*...
Page 219
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-37 0C00 DISTURB. REC ORDER 0C10 Digital Input 3 No Trigger* Trigger L – H* 0C11 Input 3 Trigger Trigger H – L* 0C12 Digital Input 4 No Trigger* Trigger L – H* 0C13...
Page 220
P846/EN CM/D Commissioning (CM) 10-38 MiCOM P846 0C00 DISTURB. RECORDER 0C2A Digital Input 16 No Trigger* Trigger L – H* 0C2B Input 16 Trigger Trigger H – L* 0C2C Digital Input 17 No Trigg Trigger L – H* 0C2D Input 17 Trigger Trigger H –...
Page 225
Commissioning P846/EN CM/D MiCOM P846 (CM) 10-43 2900 CNTRL. I/P LABELS 2920 Control Input 3000 LINE PARAM ETERS Group 1 Group 2 Group 3 Group 4 Group 1 Se ttings Settin Settings Settings Settings 4702 Line Length 4703 Line Impedance...
Page 233
In view of the critical nature of protective relays and their infrequent operation, it is desirable to confirm that they are operating correctly at regular intervals. Alstom Grid protective relays are designed for a life in excess of 20 years. MiCOM relays are self-supervizing and so require less maintenance than earlier designs of relay.
Page 234
Method of repair 1.3.1 MiCOM P846 relay If the relay should develop a fault whilst in service, depending on the nature of the fault, the watchdog contacts will change state and an alarm condition will be flagged. Due to the extensive use of surface-mount components faulty PCBs should be replaced, as it is not possible to perform repairs on damaged circuits.
Page 235
Service Centers approved by Alstom Grid. Failure to obtain the authorization of Alstom Grid After Sales Engineers prior to commencing work may invalidate the product warranty. Before removing the front panel to replace a PCB the auxiliary supply must be removed, and wait 5 s for capacitors to discharge.
Page 236
P846/EN MT/D Maintenance (MT) 11-6 MiCOM P846 Ensure that the batte ry is securely held in its socket and that the battery terminals are making good contact w ith the metal termina ls of the socket. Close the bottom access cover.
Page 239
Troubleshooting P846/EN TS/D MiCOM P846 (TS) 12-1 CONTENTS (TS) 12- INTRODUCTION INITIAL PROBLEM IDENTIFICATION POWER UP ERRORS ERROR MESSAGE/CODE ON POWER-UP OUT OF SERVICE LED ILLUMINATED ON POWER UP ERROR CODE DURING OPERATION MAL-OPERATION OF THE RELAY DURING TESTING Failure of output contacts...
Troubleshooting P846/EN TS/D MiCOM P846 (TS) 12-3 INTRODUCTION Before carrying out any work on the equipment, the user should be familiar with the contents of the safety and technical data sections and the ratings on the equipment’s rating label The purpose of this section of the service manual is to allow an error condition on the r elay to be identified so that appropriate corrective action can be taken.
Other error codes relate to problems within actual error. the main processor board hardware or software. It will be necessary to contact Alstom Grid with details of the problem for a full analysis. Relay displays message The power up tests have detected corrupted...
Page 243
Troubleshooting P846/EN TS/D MiCOM P846 (TS) 12-5 Test Check Action Relay resets on completion of Error 0x0E080000, programmable scheme power up - record error code logic error due to excessive execution time. displayed Restore default settings by performing a power up with ⇐ and ⇒ keys depressed, confirm restoration of defaults at prompt using ↵...
P846/EN TS/D Troubleshooting (TS) 12-6 MiCOM P846 OUT OF SERVICE LED ILLUMINATED ON POWER UP Test Check Action Using the relay menu confirm If the setting is Enabled then disable the test whether the Commission Test/Test mode and, verify that the Out of Service LED Mode setting is Enabled.
Troubleshooting P846/EN TS/D MiCOM P846 (TS) 12-7 ERROR CODE DURING OPERATION The relay performs continuous self-checking. If an error is detected then an error message will be displayed, a maintenance record will be logged and the relay will reset (after a 1.6 second delay).
P846/EN TS/D Troubleshooting (TS) 12-8 MiCOM P846 MAL-OPERATION OF THE RELAY DURING TESTING Failure of output contacts An apparent failure of the relay output contacts may be caused by the relay configuration; the following tests should be performed to identify the real cause of the failure. Note that the relay self-tests verify that the coil of the contact has been energized, an error will be displayed if there is a fault in the output relay board.
Page 247
Troubleshooting P846/EN TS/D MiCOM P846 (TS) 12-9 Incorrect analog signals The measurements may be configured in primary or secondary to assist. If it is suspected that the analog quantities being measured by the relay are not correct then the measurement function of the relay can be used to verify the nature of the problem.
P846/EN TS/D Troubleshooting (TS) 12-10 MiCOM P846 REPAIR AND MODIFICATION PROCEDURE Please follow these 5 steps to return an Automation product to us: 1. Get the Repair and Modification Authorization Form (RMA) To obtain an electronic version of the RMA form, please visit the following URL: www.alstom.com/grid/productrepair...
Page 249
Repair/Modification Return Authorization Form FIELDS IN GREY TO BE FILLED IN BY Alstom Grid PERSONNEL ONLY Reference RMA: Date: Repair Center Address (for shipping) Service Type LSC PO No.: Retrofit Warranty Paid service Under repair contract Wrong supply Alstom Grid...
Page 250
Please fax/e-mail a copy of the appropriate documentation (M). Please ensure the Purchase Order is released, for paid service, to allow the unit to be shipped. Alstom Grid Submission of equipment to is deemed as authorization to repair and acceptance of quote.
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-3 SCADA COMMUNICATIONS Introduction This section outlines the remote communications interfaces of the MiCOM relay. The relay supports a choice of one of five protocols via the rear communication interface, selected via the model number when ordering. This is in addition to the front serial interface and 2 rear communications port, which supports the Courier protocol only.
• As the field voltage is much higher than that required, Alstom Grid cannot assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage.
To use the rear port to communicate with a PC-based master station using Courier, a KITZ K-Bus to EIA(RS)232 protocol converter is required. This unit is available from Alstom Grid. A typical connection arrangement is shown in Figure 2. For more detailed information on other possible connection arrangements refer to the manual for the Courier master station software and the manual for the KITZ protocol converter.
P846/EN SC/D SCADA Communications (SC) 13-6 MiCOM P846 Move down the ‘Communications’ column from the column heading to the first cell down which indicates the communica tion protocol: Protocol Courier The next cell down the column controls the address of the relay:...
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-7 Up to 32 relays can be connected to one DNP 3.0 spur, and therefore it is necessary for each relay to have a unique address so that m essages from he ma er control station are accepted by only one relay.
Page 260
P846/EN SC/D SCADA Communications (SC) 13-8 MiCOM P846 REAR PORT2 (RP2) The next cell down indicates the language, which is fixed at Courier for RP2. RP2 protocol Courier The next cell down indicates the status of the hardware, e.g. RP2 card statu EIA(RS)232 OK The next cell allows for selection of the port configuration.
Page 261
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-9 RP2 baud rate 19200 Courier communications is asynchronous. Three baud rates are supported by the relay, ‘9600 bits/s’, ‘19200 bits/s’ and ‘38400 bits/s’. K-Bus Application e xa ple Master 2 Master 1...
Page 262
P846/EN SC/D SCADA Communications (SC) 13-10 MiCOM P846 “EIA(RS)232 Application” example Master 2 Master 1 Note: 1 RP could be any chosen protocol, 2 RP is always Courier To SCADA R.T.U. modem odem EIA232 EIA232 EIA232 EIA485 CK222 EIA232 splitter...
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-11 COURIER INTERFACE Courier protocol K-Bus is based on EIA(RS)485 voltage levels with HDLC FM0 encoded synchronous signaling and its own frame format. The K-Bus twisted pair connection is unpolarized, whereas the EIA(RS)485 and EIA(RS)232 interfaces are polarized.
Page 264
P846/EN SC/D SCADA Communications (SC) 13-12 MiCOM P846 Execute Setting Reset Menu Cell Set Value Control Commands Select Setting Group Change Device Address* Set Real Time Note: Commands indicated with a * are not supporte d via the front Courier port.
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-13 2.4.1 Setting transfer mode If it is necessary to transfer all of the relay settings to or from the relay a cell within the communication system data c olumn can be used. This cell (location BF03) when set to 1 makes all of the relay settings visible.
P846/EN SC/D SCADA Communications (SC) 13-14 MiCOM P846 The menu database, P 846/EN MD, contains a table of the events created by the relay and ntents of the above fields are interpreted. Fault records and indicates how the co maintenance records will return a Courier Type 3 event, which contains the above fields together with two additional fields: −...
SCADA Communications P846/EN SC/D MiCOM P846 (SC) 13-15 Programmable scheme logic settings The programmable scheme logic (PSL) settings can be uploaded from and downloaded to the relay using the block transfer mechanism defined in Chapter 12 of the Courier User Guide.
P846/EN SC/D SCADA Communications (SC) 13-16 MiCOM P846 DNP3.0 INTERFACE DNP3.0 protocol The des criptions given here are intended to accompany the device profile document that is included in the menu database, P846/EN MD. The D NP3.0 protocol is not described here, please refer to the documentation available from the u ser group.
P846/EN SC/D SCADA Communications (SC) 13-18 MiCOM P846 3.7.1 Object 1 For every point included in the device profile document there is a che ck box for membership of class 0 and radio buttons for class 1, 2 or 3 membership. Any point that is in class 0 must be a member of one of the change event classes 1, 2 or 3.
Page 271
Symbols and Glossary P846/EN SG/D MiCOM P846 SYMBOLS AND GLOSSARY Date: June 2011 Hardware Suffix: Software Version: Connection Diagrams: 10P846xx (xx = 01 to 07)
Page 272
P846/EN SG/D Symbols and Glossary MiCOM P846...
Page 273
Symbols and Glossary P846/EN SG/D MiCOM P846 (SG) 14-1 Symbol Explanation < Less than: Used to indicate an “under” threshold, such as undercurrent (current dropout). > Greater than: Used to indicate an “over” threshold, such as overcurrent (current overload). &...
Page 274
P846/EN SG/D Symbols and Glossary (SG) 14-2 MiCOM P846 Symbol Explanation Full load current: The nominal rated c urrent for the circuit. Flt. Abbreviation of “Fault”: Typically used to indicate faulted ph ase selection. Fwd. Indicates an element responding to a flow in the “Forward” di rection.
Page 275
Symbols and Glossary P846/EN SG/D MiCOM P846 (SG) 14-3 Symbol Explanation A “miniature circuit breaker”: Used instead of a fuse to protect VT secondary circuits. Not applicable. A normally closed or “break” contact: Often called a “form B” contact. A normally open or “make” co ntact: Often called a “form A”...
Page 276
P846/EN SG/D Symbols and Glossary (SG) 14-4 MiCOM P846 Symbol Explanation Phase A voltage: Might be phase L1, red phase.. or other, in customer terminology. Phase B voltage: Might be phase L2, yellow phase.. or other, in customer terminology. Phase C voltage: Might be phase L3, blue phase..
Page 277
Symbols and Glossary P846/EN SG/D MiCOM P846 (SG) 14-5 Logic Timers Logic Explanation Time Chart Symbols INPUT OUTPUT Delay on pick-up timer, t INPUT OUTPUT INPUT OUTPUT Delay on drop-off timer, t INPUT OUTPUT INPUT OUTPUT Delay on pick-up/drop-off timer...
Page 278
P846/EN SG/D Symbols and Glossary (SG) 14-6 MiCOM P846 Logic Explanation Time Chart Symbols INPUT Dwell OUTPUT Dwell timer Timer INPUT OUTPUT INPUT Straight (non latching): Straight Hold value until input reset signal OUTPUT...
Page 279
Symbols and Glossary P846/EN SG/D MiCOM P846 (SG) 14-7 Logic Gates AND GATE Symbol Truth Table Symbol Truth Table Symbol Truth Table & & & OR GATE Symbol Truth Table Symbol Truth Table Symbol Truth Table R - S FLIP-FLOP...
Installation P846/EN IN/D MiCOM P846 (IN) 15-3 RECEIPT OF RELAYS On receipt, examine relays immediately to ensure there has been no external damage in transit. If there is any damage, make a claim to the transport contractor and promptly notify Alstom Grid.
P846/EN IN/D Installation (IN) 15-4 MiCOM P846 STORAGE If relays are not to be installed immediately on receipt, they should be stored in a place free from dust and moisture in their original cartons. Where de-humidifier bags have been included in the packing they should be retained.
Installation P846/EN IN/D MiCOM P846 (IN) 15-5 RELAY MOUNTING MiCOM relays are dispatched either individually or as part of a panel/rack assembly. Individual relays are normally supplied with an outline diagram showing the dimensions for panel cutouts and hole centers.
Page 288
P846/EN IN/D Installation (IN) 15-6 MiCOM P846 Note: Conventional self-tapping screws, including those supplied for mounting MIDOS relays, have marginally larger heads which can damage the front cover moulding if used. Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the tier.
Page 289
Installation P846/EN IN/D MiCOM P846 (IN) 15-7 Panel mounting The relays can be flush mounted into panels using M4 SEMS Taptite self-tapping screws with captive 3mm thick washers (also known as a SEMS unit). These fastenings are available in packs of 5 (our part number ZA0005 104).
If required, Alstom Grid can supply M4 90° crimp ring terminals in three different sizes depending on wire size (see Table 3). Each type is available in bags of 100.
Page 291
Installation P846/EN IN/D MiCOM P846 (IN) 15-9 EIA(RS)485 port Connections to the EIA(RS)485 port are made using ring terminals. It is recommended that a 2 core screened cable is used with a maximum total length of 1000m or 200nF total cable capacitance.
Page 292
P846/EN IN/D Installation (IN) 15-10 MiCOM P846 Outputs Relay outputs (1-4) are Normally Open standard contact and Fast Closing contact Relay outputs (5-6) are Normally Open standard contact Relay outputs (7-8) are Normally Open/ Normally Closed standard contact Relay outputs (9-14) are Normally Open standard contact...
P846/EN IN/D Installation (IN) 15-12 MiCOM P846 P846 EXTERNAL CONNECTION DIAGRAMS P1755ENb Figure 4: Model A with 8 output contacts and 8 digital inputs...
Page 295
Installation P846/EN IN/D MiCOM P846 (IN) 15-13 P1756ENa Figure 5: Model B with 32 output contacts and 24 digital inputs...
Need help?
Do you have a question about the MiCOM P846 and is the answer not in the manual?
Questions and answers