Commissioning

3.5.3

Connecting the outdoor unit

A power cable (3-wire) is connected to the outdoor unit and the
communication cable is connected to the indoor unit (4-wire). Use
cables of the type H07RN-F with sufficient conductor cross-section and
protect the mains power supply with a fuse ( Table 7).
Outdoor unit
Mains fuse
protection
All types
16 A
Table 7
▶ Prepare the end of the power cable ( Fig. 17).
▶ Prepare the end of the communication cable ( Fig. 18).
▶ Remove the covers [3+6] of the electrical connection ( Fig. 19).
Model CLC6101i... only has the cover [3].
▶ Secure power cable [2] and communication cable [1] to the strain
relief [4]. If necessary, insert the supplied inlay [5] in-between.
▶ Secure power cable to terminals N, 1, and
▶ Secure the communication cable to terminals N, 1, 2 and
(assignment of wires to terminals same as indoor unit).
▶ Reattach the covers.
4
Commissioning
4.1

Commissioning checklist

1
Outdoor unit and indoor unit are correctly installed.
2
Pipes are correctly
• connected,
• thermally insulated,
• and checked for tightness.
3
Condensate pipes are functioning correctly and
have been tested.
4
Electrical connection has been correctly
established.
• Power supply is in the normal range
• Protective conductor is properly attached
• Connection cable is securely attached to the
terminal strip
5
All covers are fitted and secured.
6
The horizontal louver of the indoor unit is fitted
correctly and the actuator is engaged.
Table 8
16
Conductor cross-section
Power cable Communication
cable
2
2
≥ 1.5 mm
≥ 1.5 mm
.
4.2

Functional test of device

The system can be tested once the installation including tightness test
has been carried out and the electrical connection has been established:
▶ Connect the power supply.
▶ Switch on indoor unit with the remote control.
▶ Hold the ON/OFF [1] key pressed for 5 seconds to set the Cooling
mode ( Fig. 20)
A beep sounds and the ON indicator flashes.
▶ Test cooling mode for 5 minutes.
▶ Ensure freedom of movement of air baffle [2].
▶ Select the heating mode on the remote control.
▶ Test heating mode for 5 minutes.
▶ Press the ON/OFF key again to stop the operation.
4.3

Handover to the user

▶ When the system has been set up, hand over the installation manual
to the customer.
▶ Explain to the customer how to use the system, referring to the
operation manual.
▶ Advise the customer to carefully read the operation manual.