COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
IDCFM
AIR TEMP.
ENTERING
ID DB (°F)
OUTDOOR UNIT (°F)
ID WB (°F)
55
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COIL MULTIPLIERS - 5 TON
Air Handler
Coil
AE60DX21
AVC60DX21
ME20DN21
CF/CM64DXA1
MVC20DN21
CF/CM64DXA1
Johnson Controls Ducted Systems
TE4B6021S
1500
80
80
75
57
62
62
T.C.
58.6
58.5
58.3
S.C.
58.6
58.5
58.3
KW
3.15
3.16
3.17
T.C.
56.5
56.6
56.8
S.C.
56.5
56.6
56.8
KW
3.50
3.54
3.52
T.C.
54.3
54.8
55.2
S.C.
54.3
54.8
55.2
KW
3.85
3.92
3.88
T.C.
50.5
52.1
52.3
S.C.
50.5
52.1
52.3
KW
4.29
4.35
4.32
T.C.
46.8
49.4
49.4
S.C.
46.8
49.4
49.4
KW
4.74
4.79
4.76
T.C.
44.8
47.2
47.2
S.C.
44.8
47.2
47.2
KW
5.21
5.25
5.23
T.C.
40.8
42.8
42.7
S.C.
40.8
42.8
42.7
KW
6.16
6
6.17
T.C.
38.8
40.6
40.4
S.C.
38.8
40.6
40.4
KW
6.63
7
6.65
T.C.
S.C.
1.02
1.04
1.02
1.02
1.02
1.03
1.02
1.03
1750
80
80
80
80
75
67
72
57
62
62
63.6
66.7
61.4
60.0
59.8
63.6
66.7
61.4
60.0
59.8
3.17
3.22
3.25
3.25
3.26
61.9
66.4
59.4
58.1
58.3
61.9
66.4
59.4
58.1
58.3
3.54
3.58
3.60
3.62
3.63
60.2
66.1
57.5
56.2
56.8
60.2
66.1
57.5
56.2
56.8
3.91
3.93
3.96
3.99
3.99
57.4
63.9
53.3
53.5
53.7
57.4
63.9
53.3
53.5
53.7
4.35
4.37
4.41
4.44
4.42
54.5
61.6
49.2
50.8
50.7
54.5
61.6
49.2
50.8
50.7
4.80
4.81
4.86
4.89
4.85
52.4
58.9
46.9
48.6
48.5
52.4
58.9
46.9
48.6
48.5
5.27
5.29
5.33
5.35
5.32
48.1
53.6
42.3
44.1
44.0
48.1
53.6
42.3
44.1
44.0
6.22
6.24
6.27
6.27
6.26
45.9
50.9
40.1
41.8
41.8
45.9
50.9
40.1
41.8
41.8
6.69
6.71
6.75
6.73
6.72
FURNACE MULTIPLIERS - 5 TON
KW
Furnaces
0.94
TM8E080C20MP11
0.92
TM8E100C20MP11
0.91
TM8E120C20MP11
0.91
TM9E080C20MP12
TM9E100C20MP12
TMLE080C20MP11
TMLE100C20MP11
TMLE120C20MP11
5855837-CTG-A-0220
2000
80
80
80
80
75
67
72
57
62
62
65.0
67.8
64.1
61.5
61.3
65.0
67.8
64.1
61.5
61.3
3.27
3.31
3.34
3.34
3.36
63.5
67.7
62.4
59.5
59.9
63.5
67.7
62.4
59.5
59.9
3.64
3.67
3.71
3.70
3.73
62.1
67.6
60.7
57.5
58.4
62.1
67.6
60.7
57.5
58.4
4.01
4.04
4.07
4.06
4.10
59.0
65.4
56.1
54.8
55.2
59.0
65.4
56.1
54.8
55.2
4.46
4.47
4.52
4.52
4.52
56.0
63.2
51.5
52.2
51.9
56.0
63.2
51.5
52.2
51.9
4.90
4.91
4.97
4.99
4.95
53.8
60.6
49.0
49.9
49.7
53.8
60.6
49.0
49.9
49.7
5.37
5.39
5.45
5.45
5.41
49.4
55.3
43.9
45.4
45.4
49.4
55.3
43.9
45.4
45.4
6.31
6.34
6.39
6.37
6.34
47.2
52.7
41.3
43.1
43.2
47.2
52.7
41.3
43.1
43.2
6.78
6.81
6.86
6.83
6.80
Coil
T.C.
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
CF/CM64DXA1
1.02
80
80
67
72
66.3
68.8
66.3
68.8
3.37
3.40
65.1
69.0
65.1
69.0
3.74
3.77
63.9
69.1
63.9
69.1
4.11
4.14
60.7
67.0
60.7
67.0
4.56
4.58
57.5
64.8
57.5
64.8
5.01
5.01
55.3
62.2
55.3
62.2
5.47
5.49
50.7
57.1
50.7
57.1
6.41
6.44
48.4
54.5
48.4
54.5
6.88
6.92
S.C.
KW
1.03
0.93
1.03
0.94
1.03
0.93
1.02
0.93
1.03
0.93
1.03
0.93
1.03
0.94
1.03
0.93