Trane S9V2B040U3PSBC/D Installation, Operation And Maintenance Manual page 105

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, 2-stage condensing variable speed furnaces
Table of Contents

Advertisement

DEFINITION
RECYCLE Lock Out = 10 recycles within a single
call for heat. Lockout period is for one hour.
Flame is sensed & then lost
All gas appliances in the home should be turned
on to verify gas pressure
Measure flame current.
Is flame current greater
than 0.75 micro-amp?
(0.75-3 µA = Normal)
NO
Possible Causes:
Dirty Sensor
Dirty burners
Poor grounding
Sensor loca on
Wire connec ons
There are two flame sense pads located on the IFC,
marked "FP". To measure flame current, use a VOM set
to DC volts. Flame current will vary depending on the
type of meter used. Typical flame current ranges from
0.75 – 3.0 micro-amps (0.75 – 3.0 VDC)
S9V2-SVX001-1A-EN
2.2 Fault Code
Disconnect electrical
power to furnace.
Connect manometer
to manifold pressure
connector
NO
Cycle power to
furnace and call for
st
1
stage heat
Is manifold pressure
YES
~1.7"WC (NG)
~6.0"WC (LP)
YES
Posible Causes
Plugs
Blower door
YES
Wind gust
Condensate
Power interrupt
Repeat steps with
YES
nd
2
stage hea ng
Adjust manifold gas pressure to
~1.7"WC (NG)
NO
~6.0"WC (LP)
Check opera on
Is minimum outlet
gas manifold
pressure
maintained?
NO
Disconnect electrical
power to furnace.
Connect manometer to
inlet gas pressure
connector
Cycle power to
furnace and call for
st
1
stage heat
Is minimum outlet
gas manifold
Correct incoming
NO
pressure
gas supply pressure
maintained?
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents